Professional Documents
Culture Documents
Earthing Calculation For Substation Building
Earthing Calculation For Substation Building
Scope
Define the Size of Main Earthing Conductor and Minimum number of earth electrodes required to achieve
an overall earth resistivity of 1
Codes and Standards to be used
IEEE142 Recommended Practice for grounding of Industrial & Commercial Power Systems
BS7430 Code of practice for Earthing
DESIGN CRITERIA
1. The overall earthing network resistance shall be maintained less than 1.
2. The earthing cable/grid shall comprise of stranded copper conductor with green/yellow PVC
Sheathing.
3. Consider Earth electrode of 19mm diameter and 3.6 m length.
5. All earth electrodes shall be interconnected through the earthing grid.
6. Consider Soil resistivity of 30 Ohm-meter
Use Formulas
1. Resistance of earthing electrode
Resistance to earth of an electrode (rod) is given by the formula (Refer BS 7430, Clause no. 10.2)
Where
R=
Find R of one Rod. Calculate how many rods are required to achieve a value of 1 or less?
Rn= R ( 1+an )
Where
a = / (2R s)
Substitute the values and calculate the value of equivalent resistance Rn (it should be less than 1 ohm)
Rn=?
Where,
S = Cross section of copper conductor in mm2
I = Average fault current (RMS)
=
Where,
K= ?
Minimum Conductor Size required