Professional Documents
Culture Documents
MEPL Reference
Fuel
100% BMCR Worst coal
Volume
84.61
174 Nm3/Sec
Volume
304596.61
627499 Nm3/Hr
Temp of gas
140
135 Deg.C.
Volume
460800
937800 Am3/Hr
Velocity at top
25.00
27.83 m/sec
CSA reqd
5.12
9.36 m2
Dia of one flue
2.550
3.450 mtrs
Distance betn two flues
1.500
1.500 mtrs
Distance betn flue & shell
1.200
1.200 mtrs
Nominal ID of RCC Chimney
9.000
10.800 mtrs
Diameter of each flue 2.55 mtrs. Nominal diameter of RCC Chimney at top 9 mtrs.
Single Flue
Fuel
100% BMCR Worst coal
Volume
84.61
Volume
304596.610169492
Temp of gas
135
Volume
455221.307506053
Velocity at top
25.00
CSA reqd
5.06
Dia of one flue
2.540
Chk for Staircase dimension addition
Nm3/Sec
Nm3/Hr
Deg.C.
Am3/Hr
m/sec
m2
mtrs
100.00 m
98.00 m
STEEL FLUES
Steel Flues for top 6 meters: (AISI 316L OR BS-1449) 6 thick plate
Steel Flues rest portion: MILD STEEL. IS 2062. 10 mm thick plate
12.00 m
(Plan)
100.00 m
12.00 m
Gas from Boiler
Ash Hopper
0.00 m
Base Diameter as per Civil
design
(Elevation)
(Plan)