You are on page 1of 1

LAMPIRAN JAWABAN A NO.

PROYEK

PUSAT PERBELANJAAN & FASILITASNYA - JAKARTA

BAGIAN

PEMADAM KEBAKARAN

PERIHAL

PERHITUNGAN ORIFICE PLATE

REV. / TANGGAL

0 / 10 DESEMBER 2014

DIBUAT OLEH

PT. METAKOM CPRANATA

No

Floor

( ft )

J14/(1+(((385.57*I14*I14*H14*((J14)^4))/(K14^2))))^0.25
D/((1+(385.57*K*K*h*D^4)/Q^2))^0.25
D

( inchi )

( Gpm )

( inchi )

Lt. LG

(-

9.00

133.0

0.61

2.5

250

1.3185

Lt. GF1

(-

4.50

118.0

0.61

2.5

250

1.3552

Lt. GF2

(+/-

0.00

103.0

0.61

2.5

250

1.3976

Lt. UG

(+

5.00

86.4

0.61

2.5

250

1.4538

Lt. 1

(+

9.50

71.4

0.61

2.5

250

1.5157

Lt. 2

(+

14.00

56.4

0.61

2.5

250

1.5936

Lt. 3

(+

18.50

41.4

0.61

2.5

250

1.6967

Lt. 5

(+

23.00

26.4

0.61

2.5

250

1.8452

Lt. 6

(+

27.50

11.4

0.61

2.5

250

2.0954

10

Lt. P1

(+

32.00

91.1

0.61

2.5

250

1.4368

11

Lt. P2

(+

35.40

79.8

0.61

2.5

250

1.4795

12

Lt. P3

(+

38.80

68.4

0.61

2.5

250

1.5296

13

Lt. P4

(+

42.20

57.1

0.61

2.5

250

1.5894

14

Lt. 7

(+

45.60

46.6

0.61

2.5

250

1.6571

15

Lt. 8

(+

49.10

35.0

0.61

2.5

250

1.7531

16

Lt. 9

(+

52.60

23.3

0.61

2.5

250

1.8856

17

Lt. 10

(+

56.10

11.7

0.61

2.5

250

2.0906

18

Lt. Atap

(+

59.60

0.0

0.61

2.5

250

2.5000

LOW ZONE

HIGH ZONE

REMARKS :
Q

: Flow (GPM).

: Dia. of orifice or nozzle opening (inchi).

: Head at orifice (ft).

: Dia. Of pipe in which orifice is placed (inchi).

: Discharge coefficient.

292722070.xls