Professional Documents
Culture Documents
Mechanical Design of Transmission Line
Mechanical Design of Transmission Line
Introduction
The mechanical design of this transmission line includes pole structure,
wind load pressure, sag and the tensions on the conductor and also the
guy wires. Some details on the line insulators and the line accessories are
further discussed in this part.
Determination of Conductor Sag and Tension in Overhead Lines:
While erecting an overhead line, it is very important that conductors
are safe tension. If the conductors are too much stretched between
supports in a bid to save conductor material, the stress in the conductor
may reach unsafe value and in certain cases the conductor may break
due to excessive tension. In order to permit safe tension in the
conductors, they are not fully stretched but are allowed to have a dip or
sag.
The difference in level between points of supports and the lowest point
on the conductor is called sag.
Conductor Sag and Tension:
This is an important consideration in the mechanical design of
overhead lines. The conductor sag should be kept to a minimum in order
to reduce the conductor material required and to avoid extra pole height
for sufficient clearance above ground level. It is also desirable that tension
in the conductor should be low to avoid mechanical failure of conductor
and to permit the use of less strong supports. However, low conductor
tension and minimum sag are not possible. It is because low sag means a
tight wire and high tension, whereas a low means a loose wire and
Where
Kz = velocity pressure exposure coefficient
Kz = 2.01(h/900)(2/9.5)
Where h = height of the wire at the structure and is between 33 feet and
900 feet
h = 30 + 0.3 (KV) = 30 +0.3(345kv) = 133.5 ft
Kz = 2.01 x
133.5 2 /9.5
= 1.34
900
PxD
lb/ft
12
WW=
37.08 x 1.213
lb/ft
12
W W =3.74 lb/ft
Conductor Load
From Table, The conductor ORTOLAN w/ a cross sectional area of 1033 Kcmil,
the nominal weight is 1165/1000 ft.
W C=
1165
1000
W C =1.165 lb
/ft
W T =3.91lb/ ft
calculate sag and tension of a conductor when (i) supports are at equal level
(ii) supports are at unequal levels.
(i)
Sag, S =
w l2
8T
The sag is as result of the tensioning of the line and must not be too
low otherwise the safety clearances may not be met. Also, the sag had to be
such that it caters for ice loading in the winter of temperate climates. If the
sag is large, and the line becomes heavily loaded, then the sag will further
increase and branch the safety clearances. Similarity, if the sag is low, then
when the line contracts in the winter, low sag will indicate a high tension,
and as a result of this contraction, the line may snap.
Required Clearances:
1. Clearance of conductors passing by buildings
2. Minimum clearances of conductors above ground or rails
3. Crossing clearances of wires carried of wires carried on different
supports
4. Horizontal clearances at support between line conductors based on
sag.
Working Tension
Given:
Conductor Name = ORTOLAN
Ultimate Strength = 27,700 lb
Safety Factor = 2
L = 250 m 820.21 ft. span length
T=
Ultimate Strength
Safety factor
T=
27700
2
= 13850lb
Sag of Conductor
Sag=
1.165 x 820.212
8 x 13850
Sag=7.07 ft
For bundling
Sag = 7.07 ft x 2
Sag = 14.14 ft. or 4.3 m
b. Consider both conductor and wind load
W T x L2
Sag=
8 xT
3.91 x 820.212
Sag=
8 x 13850
Sag T =23.74 ft
Calculations:
Span 820.12 ft
X1 + X2 = 820.12;
X1 = 820.12 - X2
h=
WC
( X 2 X 12 )
2 xT 2
20=
1.165
2
2
X 2 ( 820.12X 2 ) )
(
2 x 13850
20 x
2 x 13850
=( X 22820.122+1640 X 2X 22 )
1.165
X 2=700 ft
X 1=820.12X 2 ft
X 1=820.12700=120.12 ft
S 1=
W C x X 12 1.165 x 120.122
=
2 xT
2 x 13850
s 1=6.225 ft
W C x X 22 1.165 x 700 2
S 2=
=
2 xT
2 x 13850
S 2=20.60 ft
LINE SUPPORTS
The supporting structure for overhead line conductors are various type
of pole towers called line supports. In general, the line support should have
the following properties:
a. High mechanical strength to withstand the weight of conductor and
b.
c.
d.
e.
power are of various types including wooden poles, steel poles, RCC poles,
and lattice steel towers. The choice od supporting structure for a particular
case depends upon the line span, cross-sectional area, line voltage, cost and
local conditions.
Steel Poles. The steel poles are often used as a substitute for wooden
poles. They possess greater mechanical strength, longer life and permit
longer spans to be used. Such poles are generally used for distribution
purposes in the cities. This type of supports need galvanized or painted in
order to prolong its life. The steel poles are three types., (i)rail poles (ii)
tubular poles and (iii)rolled steel joints.
Spacing and Clearance
1. Vertical Clearance - NESCode 232 Vertical Clearance (Above Ground,
Roadway, Rail or Water Suface)
M
53,584,542
3
=
0.00026386S
0.0002638646,350.36
C=163.63
Butt Diameter:
C 163.63
Butt Diameter= =
=54.54
12
1 ft
Top Diameter:
Ratio of the top to bottom is 0.60
1m
3.28 ft
= 1.38 m
1m
3.28 ft
= 0.83 m
Taper=
C bottom C top
60
163.63102.8
=1.01
60
Projected Area:
D
( top+ Dbutt ) x 2 x LPole x 12
A=
A= (54.54 +32.72 ) (2)(133.5)(12)
A=279,581.04 ft 2
The additional 13.35 ft will be the depth of the pole to be under the
ground. These giving the total length of the pole to:
H = 133.5 + 13.35
H = 146.85 ft.
CORNER POLE:
The Angle 30 & 40 of two cables
Since T1 = T2 = 13,850 Kg is already computed
Fv=0
Vertical Force:
Fv = T1 Sin 30 T2 Sin 40
Fv=13,850 Sin 30 13,850 Sin 40
Fv= -1977.60
Horizontal Force:
Fh = T1 Cos 30 T2 Cos 40
Fh = 13,850 Cos 30 - 13,850 Cos 40
Fh = 1384.74
Resultant Force:
R= F h 2+ Fv 2
R= (1977.6)2 +(1384.74)2
R=2,414.2 0
Angle:
=tan 1
Fv
Fh
=tan 1
1384.74
1977.6
=35
GUY WIRES
The various grades of guy strand are almost universally furnished in
accordance with ASTM specifications. The ultimate strength for each size
and grade is given. The so-called double galvanized is commonly used. In
transmission construction a factor of safety of 2 is general for guys,
although this may be somewhat reduced.
GUY REQUIREMENT: IEEE C2-1997 (EE Handbook pp(18-66))
Distance dig from the pole not less than or more than 1 to 1 of the
height of the guy attachment.
GUY WIRE TENSIONS
D = 0.551 x H
D = 0.551 (146.85)
D= 80.91 ft
Length of guy
L1 = D 2 + H 2
L1= 80.912+ 75.822
L1=110.88 ft
L2 = D 2 + H 2
L2= 80.912+ 103.02
L2=130.99 ft
L3 = D 2 + H 2
L3= 80.912+ 130.222
L3=153.30 ft
L4 = D 2 + H 2
L4= 80.912 +133.5
L4=156.10 ft