Appendix A

(Preliminary Drawings)

Appendix B
(Load Calculations)

Permanent load calculations:


For frames (1, 3, 4 and 8) containing perimeter beams, the self-weight of the slab portion was taken into
account as a UDL. Other permanent loads are taken into account by the software. The self-weight of
concrete = 25.0 kN/m3.
An additional load accounting for floor finishes and ceiling loads was taken as 1.0 kN/m 2.
Width of tributary
area (m)
3.9
4.1
4.225
5.375

Frame designation
1
3
4
8

Frame
designation
1
2
3
4
5
6
7
8

Width of slab beam


(m)
0.400
8.000
0.400
0,4
7.875
7.950
9.675
0.400

Load per m length


(kN/m)
38.025
39.975
41.194
52.406

CSP load
(kN/m)
0.400
8.000
0.400
0.400
7.875
7.950
9.675
0.400

Factored permanent load


per m length (kN/m)
51.334
53.966
55.612
70.748

Factored CSP UDL


(kN/m)
0.5
10.8
0.5
0.5
10.6
10.7
13.1
0.5

Imposed load calculations:


The three imposed loads considered were:

Category C2 (Area where people may congregate) = 3.5 kN/m2


Partition loads = 0.8 kN/m2

Total imposed load = 4.3 kN/m2

Frame
designation

Width of
tributary area
(m)

Load per m
length on floor
(kN/m)

Load per m
length on roof
(kN/m)

Factored
imposed load per
m length on
floor (kN/m)

Factored
imposed load
per m length
on roof (kN/m)

3.9

16.77

1.95

25.16

2.93

34.4

51.6

4.1

17.63

2.05

26.45

3.08

4.225

18.17

2.11

27.25

3.17

7.875

33.86

3.94

50.79

5.91

7.95

34.19

3.98

51.28

5.96

9.675

41.6

4.84

62.4

7.26

5.375

23.11

2.69

34.67

4.03

Block wall calculations (In toilet region):

Density of 200 mm wide cellular block wall = 3.5 kN/m2


Height of wall = 3550 mm
Dimension of slab considered: 10750 x 8200 mm. (Enclosed by frames 2, 7 and 8)

Area of floor = (10.75 x 7.45) m2 = 88.15 m2


For floor 1, 3 and 5:
Perimeter length of wall = 2 (7450 + 5900) mm = 26.7 m
Length of interior separations = (8 x 1600) mm + (6 x 900) mm = 18.2m
Total length of block wall = 45 m
Total weight of block wall = 3.5 x 3.55 x 45 = 559.1 kN
The load is assumed as a uniform pressure on the floor slab, so that the pressure = (559.1/ 88.15) kN/m 2 =
6.35 kN/m2
The same conservative value is adopted for floors 2 and 4.
The floor is 2-way spanning with aspect ratio 1.4. The load is hence a triangular load on the shorter side
and a trapezoidal load on longer side.
Results:

1. On shorter side, load is a triangular load with peak value at mid-span = (6.35 x 8.2 x 0.5) = 26
kN/m
This was approximated to a UDL of 2/3rd the actual value i.e. a UDL of 17.4 kN/m.
Factored UDL = 23,5 kN/m
2. On longer side, load is a trapezoidal load, with peak load of 26 kN/m.
Factored peak = 35.1 kN/m.

Appendix D
(Structural design calculations)

Appendix E
(Design drawings)

Appendix F
(Schedule of works)

Appendix G
(Minutes of Meeting)

Appendix C
(Results from PROKON)