(Preliminary Drawings)
Appendix B
(Load Calculations)
Frame designation
1
3
4
8
Frame
designation
1
2
3
4
5
6
7
8
CSP load
(kN/m)
0.400
8.000
0.400
0.400
7.875
7.950
9.675
0.400
Frame
designation
Width of
tributary area
(m)
Load per m
length on floor
(kN/m)
Load per m
length on roof
(kN/m)
Factored
imposed load per
m length on
floor (kN/m)
Factored
imposed load
per m length
on roof (kN/m)
3.9
16.77
1.95
25.16
2.93
34.4
51.6
4.1
17.63
2.05
26.45
3.08
4.225
18.17
2.11
27.25
3.17
7.875
33.86
3.94
50.79
5.91
7.95
34.19
3.98
51.28
5.96
9.675
41.6
4.84
62.4
7.26
5.375
23.11
2.69
34.67
4.03
1. On shorter side, load is a triangular load with peak value at mid-span = (6.35 x 8.2 x 0.5) = 26
kN/m
This was approximated to a UDL of 2/3rd the actual value i.e. a UDL of 17.4 kN/m.
Factored UDL = 23,5 kN/m
2. On longer side, load is a trapezoidal load, with peak load of 26 kN/m.
Factored peak = 35.1 kN/m.
Appendix D
(Structural design calculations)
Appendix E
(Design drawings)
Appendix F
(Schedule of works)
Appendix G
(Minutes of Meeting)
Appendix C
(Results from PROKON)