You are on page 1of 9

LOOP SPRINKLER SYSTEM

Fire Sprinkler Reports

for

EMPRESAS ABC
David, Chiriqui

Prepared By:
Ing. J. Villarreal
Greenfire solutions
Panama

228 2463
09/02/2015

Fire - Fire Sprinkler Hydraulics Calculation Program


Elite Software Development
College Station, TX 77845-4491

Elite Software Development, Inc.


Loop sprinkler system
Page 2

General Project Data Report


General Data
Project Title:
Designed By:
Code Reference:
Client Name:
Address:
Company Name:
Company Address:
Phone:
Building Name:
Contact at Building:
Address Of Building:

Loop sprinkler system


Ing. J. Villarreal
NFPA 13, 16
EMPRESAS ABC
David, Chiriqui
Greenfire solutions
Panama
228 2463
Tanque No.1

Project File Name:


Date:
Approving Agency:
Phone:
City, State Zip Code:
Representative:
City And State:

Jaime 1..fiw
09/02/2015
Panama FD
507 234 1234
Jaime Villarreal

Building Owner:
Juan de Dios
Phone at Building:
City, State Zip Code:

Project Data
Description Of Hazard:
Ex. Haz. Gp. 1
Design Area Of Water Application:
2500
Default Sprinkler K-Factor:
7.20
Inside Hose Stream Allowance:
0.00
In Rack Sprinkler Allowance:
0.00
Sprinkler Specifications
Make:
Size:

ft
K
gpm
gpm

VIKING
1/2

Sprinkler System Type:


Dry
Maximum Area Per Sprinkler:
100 ft
Default Pipe Material:
SCHED 40 STEEL,DRY
Outside Hose Stream Allowance:
0.00 gpm

Model:
Temperature Rating:

E
212 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID:
Hydrant Elevation:
Test Flow Rate:
Calculated System Flow Rate:

Date Of Test:
0 ft
0.00 gpm
496.39 gpm

Static Pressure:
Test Residual Pressure:
Calculated Inflow Residual Pressure:

0.00 psi
0.00 psi
71.33 psi

Minimum Desired Flow Density:


Maximum Frictional Loss / 100 feet:

0.30 gpm/ft
20.00 psi

Calculation Project Data


Calculation Mode:
HMD Minimum Residual Pressure:
Maximum Water Velocity:
Number Of Active Nodes:
Number Of Active Pipes:
Number Of Active Sprinklers:
60 psig en el mas desfavorable

Demand
60.00 psi
20.00 ft/s
10
10
7

Number Of Inactive Pipes:


Number Of Inactive Sprinklers:

C:\Users\User\Documents\Elite Software\Fire 6 Projects\Jaime 1..fiw

0
0

mircoles, 02 de septiembre de 2015, 5:03 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Elite Software Development
College Station, TX 77845-4491

Elite Software Development, Inc.


Loop sprinkler system
Page 3

Fire Sprinkler Input Data


Node Input Data
Area Group
Branch Dia.
(in)

Sprinkler
KFactor (K)
Branch Len.
(ft)

Pressure
Estimate (psi)
Branch Stnd
Fittings

Node Elev (ft)


Branch NonStnd Fittings
(ft)

Non-Sprinkler
Flow (gpm)
Branch Sprk
KFactor (K)

No Discharge
----

---0.000

N/A
0.0

71.33
----

0.00
0.0

0.00
0.00

20

No Discharge
----

---0.000

N/A
0.0

64.81
----

0.00
0.0

0.00
0.00

30

Sprinkler
----

---0.000

7.20
0.0

63.47
----

0.00
0.0

0.00
0.00

40

Sprinkler
----

---0.000

7.20
0.0

60.90
----

0.00
0.0

0.00
0.00

50

Sprinkler
----

---0.000

7.20
0.0

60.17
----

0.00
0.0

0.00
0.00

60

Sprinkler
----

---0.000

7.20
0.0

60.00
----

0.00
0.0

0.00
0.00

70

Sprinkler
----

---0.000

7.20
0.0

61.64
----

0.00
0.0

0.00
0.00

80

Sprinkler
----

---0.000

7.20
0.0

62.84
----

0.00
0.0

0.00
0.00

90

Sprinkler
----

---0.000

7.20
0.0

64.05
----

0.00
0.0

0.00
0.00

100

Non-Sprinkler
----

---0.000

N/A
0.0

59.49
----

0.00
0.0

100.00
0.00

Node
No.

Node Description
Branch Description

10

C:\Users\User\Documents\Elite Software\Fire 6 Projects\Jaime 1..fiw

mircoles, 02 de septiembre de 2015, 5:03 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Elite Software Development
College Station, TX 77845-4491

Elite Software Development, Inc.


Loop sprinkler system
Page 4

Fire Sprinkler Input Data


Pipe Input Data
Nominal
Diameter
(inch)

Type
Group

Fitting
Data

Nominal
Length
(feet)

Fitting
Length
(feet)

Total
Length
(feet)

CFactor
(gpm/inc
h-psi)

SCHED 40 STEEL,DRY

4.000

50.00

15.60

65.60

100

30

SCHED 40 STEEL,DRY

3.000

10.00

0.00

10.00

100

90

20

SCHED 40 STEEL,DRY

3.000

10.00

0.00

10.00

100

30

40

SCHED 40 STEEL,DRY

2.500

10.00

0.00

10.00

100

40

100

SCHED 40 STEEL,DRY

2.000*

10.0

0.7

10.7

100

40

50

SCHED 40 STEEL,DRY

2.000*

10.0

0.0

10.0

100

50

60

SCHED 40 STEEL,DRY

1.500*

10.0

0.0

10.0

100

60

70

SCHED 40 STEEL,DRY

1.250*

10.0

0.0

10.0

100

70

80

SCHED 40 STEEL,DRY

2.000*

10.0

0.0

10.0

100

2.500*

10.0

0.0

10.0

100

Beg.
Node

End.
Node

Pipe Description

10

20

20

80
90
SCHED 40 STEEL,DRY
* Indicates the pipe section was autosized.

C:\Users\User\Documents\Elite Software\Fire 6 Projects\Jaime 1..fiw

mircoles, 02 de septiembre de 2015, 5:03 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Elite Software Development
College Station, TX 77845-4491

Elite Software Development, Inc.


Loop sprinkler system
Page 5

Fire Sprinkler Output Data


Overall Node Groupings Output Data
Pipe Segment
Beg.
End.
Node
Node

Pipe
Type
Group

Pipe
Flow Rate
(gpm)

Sprinkler Flow
At Beg. Node
(gpm)

Non-Sprinkler Flow
Out (+)
In (-)
(gpm)
(gpm)

Beg. Node
Residual
Pressure (psi)

Imbalance
Flow At Beg.
Node (gpm)

10

20

496.39

0.00

0.00

-496.39

71.33

20
20
20

10
30
90

0
0
0

-496.39
286.33
210.06

0.00

0.00

0.00

64.81

0.00000

30
30

20
40

0
0

-286.33
228.97

57.36

0.00

0.00

63.47

0.00000

40
40
40

30
100
50

0
0
0

-228.97
100.00
72.78

56.19

0.00

0.00

60.90

0.00000

50
50

40
60

0
0

-72.78
16.94

55.85

0.00

0.00

60.17

0.00000

60
60

50
70

0
0

-16.94
-38.84

55.77

0.00

0.00

60.00

0.00000

70
70

60
80

0
0

38.84
-95.36

56.53

0.00

0.00

61.64

0.00000

80
80

70
90

0
0

95.36
-152.44

57.08

0.00

0.00

62.84

0.00000

90
90

20
80

0
0

-210.06
152.44

57.62

0.00

0.00

64.05

0.00000

100

40

-100.00

0.00

100.00

0.00

59.49

0.00000

C:\Users\User\Documents\Elite Software\Fire 6 Projects\Jaime 1..fiw

mircoles, 02 de septiembre de 2015, 5:03 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Elite Software Development
College Station, TX 77845-4491

Elite Software Development, Inc.


Loop sprinkler system
Page 6

Fire Sprinkler Output Data


Overall Pipe Output Data
Beg.
End.
Node

Nodal
KFactor
(K)

Spk/Hose
Elevation
Discharge
(feet)
(gpm)

Residual Nom. Dia.


Pressure Inside Dia.
(psi)
C-Value

q (gpm)
Q (gpm)
Velocity
(fps)

F. L./ft
(psi/ft)
Fittings
Type-Grp

Pipe-Len.
Fit-Len.
Tot-Len.
(ft)

PF-(psi)
PE-(psi)
PT-(psi)

10
20

0.00
0.00
0.00
0.00
0.00
0.00
SCHED 40 STEEL,DRY

71.33
64.81

4.00
4.026
100

0.00
496.39
12.51

0.09932
C
0

50.00
15.60
65.60

6.516
0.000
6.516

20
30

0.00
0.00
0.00
7.20
0.00
57.36
SCHED 40 STEEL,DRY

64.81
63.47

3.00
3.068
100

57.36
286.33
12.43

0.13480
----0

10.00
0.00
10.00

1.348
0.000
1.348

90
20

7.20
0.00
57.62
0.00
0.00
0.00
SCHED 40 STEEL,DRY

64.05
64.81

3.00
3.068
100

57.62
210.06
9.12

0.07600
----0

10.00
0.00
10.00

0.760
0.000
0.760

30
40

7.20
0.00
57.36
7.20
0.00
56.19
SCHED 40 STEEL,DRY

63.47
60.90

2.50
2.469
100

56.19
228.97
15.34

0.25673
----0

10.00
0.00
10.00

2.567
0.000
2.567

40
100

7.20
0.00
56.19
0.00
0.00
100.00
SCHED 40 STEEL,DRY

60.90
59.49

2.00
2.067
100

100.00
100.00
9.56

0.13174
G
0

10.00
0.70
10.70

1.410
0.000
1.410

40
50

7.20
0.00
56.19
7.20
0.00
55.85
SCHED 40 STEEL,DRY

60.90
60.17

2.00
2.067
100

55.85
72.78
6.96

0.07319
----0

10.00
0.00
10.00

0.732
0.000
0.732

50
60

7.20
0.00
55.85
7.20
0.00
55.77
SCHED 40 STEEL,DRY

60.17
60.00

1.50
1.610
100

16.94
16.94
2.67

0.01665
----0

10.00
0.00
10.00

0.166
0.000
0.166

60
70

7.20
0.00
55.77
7.20
0.00
56.53
SCHED 40 STEEL,DRY

60.00
61.64

1.25
1.380
100

38.84
38.84
8.33

0.16377
----0

10.00
0.00
10.00

1.638
0.000
1.638

70
80

7.20
0.00
56.53
7.20
0.00
57.08
SCHED 40 STEEL,DRY

61.64
62.84

2.00
2.067
100

56.53
95.36
9.12

0.12066
----0

10.00
0.00
10.00

1.207
0.000
1.207

80
90

7.20
0.00
57.08
7.20
0.00
57.62
SCHED 40 STEEL,DRY

62.84
64.05

2.50
2.469
100

57.08
152.44
10.22

0.12095
----0

10.00
0.00
10.00

1.209
0.000
1.209

C:\Users\User\Documents\Elite Software\Fire 6 Projects\Jaime 1..fiw

mircoles, 02 de septiembre de 2015, 5:03 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Elite Software Development
College Station, TX 77845-4491

Elite Software Development, Inc.


Loop sprinkler system
Page 7

Fire Sprinkler Output Data


Overall Sprinkler Output Data
Flowing
Area (ft)

Flowing
Density
(gpm/ft)

Sprinkler
Discharge
(gpm)

63.47

100.00
100.00

0.574
0.574

57.36
57.36

0.00

60.90

100.00
100.00

0.562
0.562

56.19
56.19

7.20

0.00

60.17

100.00
100.00

0.558
0.558

55.85
55.85

60
Sub Totals For Non-Group

7.20

0.00

60.00

100.00
100.00

0.558
0.558

55.77
55.77

70
Sub Totals For Non-Group

7.20

0.00

61.64

100.00
100.00

0.565
0.565

56.53
56.53

80
Sub Totals For Non-Group

7.20

0.00

62.84

100.00
100.00

0.571
0.571

57.08
57.08

90
Sub Totals For Non-Group

7.20

0.00

64.05

100.00
100.00

0.576
0.576

57.62
57.62

700.00

0.566

396.39

Area Group
Code

Sprinkler
KFactor (K)

Sprinkler
Elevation
(feet)

Residual
Pressure
(psi)

30
Sub Totals For Non-Group

7.20

0.00

40
Sub Totals For Non-Group

7.20

50
Sub Totals For Non-Group

Flowing
Sprinkler
Node No.

Totals For All Groups

C:\Users\User\Documents\Elite Software\Fire 6 Projects\Jaime 1..fiw

mircoles, 02 de septiembre de 2015, 5:03 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Elite Software Development
College Station, TX 77845-4491

Elite Software Development, Inc.


Loop sprinkler system
Page 8

Fire Sprinkler Output Summary


Hydraulically Most Demanding Sprinkler Node
HMD Sprinkler Node Number:
HMD Actual Residual Pressure:
HMD Actual GPM:

60
60.00 psi
55.77 gpm

Sprinkler Summary
Sprinkler System Type:
Specified Area Of Application:
Adjusted Area Of Application:
Minimum Desired Density:
Application Average Density:
Application Adjusted Density (not required by NFPA 13):
Application Average Area Per Sprinkler:
Adjusted Area Per Sprinkler (not required by NFPA 13):
Sprinkler Flow:
Average Sprinkler Flow:

Dry
2500.00
3250.00
0.300
0.159
0.122
357.14
464.29
396.39
56.63

ft
ft
gpm/ft
gpm/ft
gpm/ft
ft
ft
gpm
gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 30 - 40 )
Maximum Velocity Pressure ( In Pipe 30 - 40 )
Allowable Maximum Nodal Pressure Imbalance:
Actual Maximum Nodal Pressure Imbalance:
Actual Average Nodal Pressure Imbalance:
Actual Maximum Nodal Flow Imbalance:
Actual Average Nodal Flow Imbalance:

15.34 ft/sec
1.58 psi
0.0100
0.0000
0.0000
0.0000
0.0000

psi
psi
psi
gpm
gpm

Overall Network Summary


Number Of Unique Pipe Sections:
Number Of Flowing Sprinklers:
Pipe System Water Volume:
Sprinkler Flow:
Non-Sprinkler Flow:
Minimum Required Residual Pressure At System Inflow
Node:
Demand Flow At System Inflow Node:

10
7
15.88 gal
396.39 gpm
100.00 gpm
71.33 psi
496.39 gpm

C:\Users\User\Documents\Elite Software\Fire 6 Projects\Jaime 1..fiw

mircoles, 02 de septiembre de 2015, 5:03 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Elite Software Development
College Station, TX 77845-4491

Elite Software Development, Inc.


Loop sprinkler system
Page 9

Fire Sprinkler Output Data


Hydraulic Supply/Demand Graph

100
90
80
71

Pressure psi

70
60
50
40
30
20
10
0
1

10

Flowrate(x100) gpm

Demand Curve Data


Calculated Residual Pressure: 71.33 psi
Calculated Flow Rate: 496.39 gpm
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 0.00 psi

C:\Users\User\Documents\Elite Software\Fire 6 Projects\Jaime 1..fiw

mircoles, 02 de septiembre de 2015, 5:03 p.m.

You might also like