You are on page 1of 2

No.

Nos of
bank
2

No. of
cells/Bnk
108

Type of Battery
Absolyte GP
3-100G21

Int. R
milli-

Recharge cell
voltage (V)

Rechg
Time (hr)

0.275

2.35

Ah
1000

Atonomy End of cell


(hr)
V
8
1.80

Dischg
Amp
122

Heat loss on Rechg


BTU/hr

Heat loss on Disch BTU/hr


per bank

Total

per bank

Total

12075

24150

8758

17516

PT. SEI Project Banyu Urib


UPS/Charger System Parameter.
Battery Autonomy
Final voltage of battery
Discharge current is
Battery Recharge Time
Battery Type & Quantity per bank
Type of Battery Absolyte GP

:
:
:
:
:
:

model

8 hr(C5)
1.80 Vper cell
122 Amp
8 hr
108 cells
3-100G21

A) Heat Loss on Discharge


n

Heat Loss (watt)

(In)2 ( Tn) Rt

X=1
The heat loss during discharge can also be expressed in BTUs per hour :

[(In)2 ( Tn) Rt]

Heat Loss (BTU/hour) =

x (3.41443)

X=1
Where

In
Tn
Rt

Where

In
Tn
Rt

= The current required load for each part of the duty cycle
= The time in hour of each part f the duty cycles
= The total resistance of the battery string
=
=
=

Battery bank support the following load


1.80 V per cell

122 A

8 hr
29.7 milli-
8 hr

Total Heat Loss during discharge, in BTU/hour =

discharge

[(In)2 (Tn) Rt]

108 cells per bank

122.00 A to end voltage of


x (3.41443)
1000

12,075 BTU/hr per bank

B) Heat Loss on Recharge Battery

Heat Loss (Watts)

= (FV-OC)(#Cells)(Ah)
Recharge Time

The heat loss on recharge in BTUs per hour :


= (FV-OC)(#Cells)(Ah) x 3.41443
Heat Loss (BTU/hpur)
Recharge Time

Where :

FV
OCV
# Cells
Ah
Recharge Time

=
=
=
=
=

Where :

=
=
=
=
=

FV
OCV
# Cells
Ah
Recharge Time

Heat Loss on recharging

Equalised or recharge voltage


Open circuit voltage
total nos of cell in the battery string.
Number of Amp.-hour to be returned to the cells
Total time of recharge, in hours

2.35
2.16
108
1000
8

Vpc
Vpc
cells
Ah
hr

8,758 BTU/hour