Zone Sizing Summary For V34-BAC-1E: Air System Information
Zone Sizing Summary For V34-BAC-1E: Air System Information
08/07/2015
03:20PM
1
10350.0 ft
Dubai, United Arab Emirates
Number of zones
Floor Area
Location
Jul to Aug
Calculated
Calculation Months
Sizing Data
Zone Name
Zone 1
Maximum
Cooling
Sensible
(MBH)
566.5
Design
Air
Flow
(CFM)
29325
Minimum
Air
Flow
(CFM)
29325
Time
of
Peak
Load
Jul 1700
Maximum
Heating
Load
(MBH)
19.9
Total
Coil
Load
(MBH)
908.8
Sens
Coil
Load
(MBH)
664.7
Coil
Entering
DB / WB
(F)
77.4 / 65.7
Coil
Leaving
DB / WB
(F)
56.4 / 55.4
Water
Flow
@ 10.0 F
(gpm)
-
Heating
Coil
Ent/Lvg
DB
(F)
-1.0 / -1.0
Htg Coil
Water
Flow
@20.0 F
(gpm)
0.00
Fan
Design
AirFlow
(CFM)
29325
Fan
Motor
(BHP)
5.234
Zone
Floor
Area
(ft)
10350.0
Zone
CFM/ft
2.83
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1300
Zone Name
Zone 1
Heating
Coil
Load
(MBH)
0.0
Fan
Motor
(kW)
4.152
OA Vent
Design
AirFlow
(CFM)
2169
Zone Name /
Space Name
Zone 1
E34 - B.D-2 WALK-INCLO
E34 - B.D-3 WALK-INCL0
E34 - B.D-4 WALK-INCLO
E34 - BEDROOM - 02
E34 - BEDROOM - 03
E34 - BEDROOM - 04
E34 - DIRTY KITCHEN
E34 - DRIVER'S RM
E34 - FAMILY HALL
E34 - FORMAL DINING
E34 - FOYER
E34 - GAME ROOM
E34 - GYM
E34 - KITCHEN
E34 - LAUNDRY
E34 - MAID'S RM
E34 - MAIN LOBBY+STAIR
E34 - MEN'S MAJILIS
E34 - OFFICE
E34 - SEATING AREA
Hourly Analysis Program v4.70
Mult.
Cooling
Sensible
(MBH)
Time
of
Load
Air
Flow
(CFM)
Heating
Load
(MBH)
Floor
Area
(ft)
Space
CFM/ft
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
12.1
4.6
4.9
26.3
23.9
23.9
35.7
7.8
41.8
37.3
16.0
20.9
28.8
27.0
14.4
4.6
60.7
45.5
45.3
28.4
Jul 0100
Jul 0100
Jul 0100
Jul 0900
Jul 1700
Jul 1700
Jul 2300
Jul 2300
Aug 1300
Jul 1700
Jul 0400
Jul 1700
Jul 0900
Jul 2300
Jul 2300
Jul 2300
Aug 0500
Jul 1700
Jul 0900
Aug 0500
624
235
252
1355
1229
1229
1836
404
2153
1919
822
1078
1483
1391
741
236
3125
2341
2333
1463
0.5
0.1
0.1
2.3
1.6
1.7
0.0
0.0
1.3
1.4
0.4
1.4
1.1
0.1
0.0
0.0
0.8
2.5
1.9
1.2
221.6
91.4
106.5
465.9
492.8
536.9
723.0
153.8
781.1
579.9
296.9
271.1
322.8
420.0
237.7
120.6
1603.8
807.0
695.0
529.3
2.81
2.57
2.37
2.91
2.49
2.29
2.54
2.63
2.76
3.31
2.77
3.98
4.59
3.31
3.12
1.96
1.95
2.90
3.36
2.76
Page 1 of 2
Zone Name /
Space Name
E34 - STORAGE RM-1
E34 - STORAGE RM-2
E34 - STORE RM 01
E34 - STORE RM 02
E34 - TV ROOM
Mult.
1
1
1
1
1
08/07/2015
03:20PM
Cooling
Sensible
(MBH)
4.3
5.2
7.5
4.9
37.9
Time
of
Load
Jul 2300
Aug 0100
Jul 2300
Jul 2300
Aug 1300
Air
Flow
(CFM)
222
265
386
252
1952
Heating
Load
(MBH)
0.0
0.5
0.0
0.0
0.8
Floor
Area
(ft)
248.5
82.8
80.7
57.0
423.9
Space
CFM/ft
0.89
3.20
4.79
4.42
4.61
Page 2 of 2