You are on page 1of 6

STRUCTURAL CERTIFICATION

OFFICE BUILDING, HBR LAYOUT, BANGALORE.

PREPARED FOR:

G4S Security Services (India) Pvt. Ltd.  


# 507, H.B.R layout, 1 st Stage, 4th Block,
Outer Ring Road, Bangalore -560029
 
 
Assignment:

Structural Certification of the 5 Floors Office Building situated in HBR


layout
Bangalore.

Scope of Services:

To analyze the structure as per IS Codes and check the designs & detailing
implemented in the structure.  

Background Information:

G4S requested us (KRSNA Service Consultants ) to provide the structural


certification
for their 5 Floors Office Building situated at HBR layout. Also G4S as
supplied
• Architectural drawing
• Structural drawing
• Soil report
Investigation:

Based on the above inputs the structural analysis was carried out in
accordance with the IS Codes: IS 456, SP16, IS 13920, IS 875, IS 1893.
The structural model was prepared and was analyzed for Dead loads,
Live loads, Seismic loads.

Basic Load Combinations:

Eighteen load combinations per IS Codes were considered for each of


the four load cases as follows:

• DL = dead load
• LL=Live Load
• EQ = earthquake load
1) (DL+LL) 10) (DL-EQZ) 1.5
2) (DL+LL) 1.5 11) (0.9DL+1.5EQX)
3) (DL+LL+EQX) 1.2 12) (0.9DL+1.5EQZ)
4) (DL+LL+EQZ) 1.2 13) (0.9DL-1.5EQX)
5) (DL+LL-EQX) 1.2 14) (0.9DL-1.5EQZ)
6) (DL+LL-EQZ) 1.2 15) (DL+0.5LL+EQX)1.2
7) (DL+EQX) 1.5 16) (DL+0.5LL+EQZ)1.2
8) (DL+EQZ) 1.5 17) (DL+0.5LL-EQX)1.2
9) (DL-EQX) 1.5 18) (DL+0.5LL-EQZ)1.2
Results:
By referring to the analysis and structural drawings the following
observations are made
All the footing except Grid 2 -B is found to be safe.
All the columns except few columns in the 3 rd and 4th Floors are
found to be under reinforced i.e., unsafe.
All the slabs are safe to carry commercial (office) loads. · All the
beams are found to safe except B10 and B5 are under reinforced.
The staircase reinforcement is found to be satisfactory.

Summary:

  Overall the Columns in the structure are found to be under


reinforced, also the footings, slabs, beams and staircase can carry
commercial loads . Since the Column being the main member which
transfers the loads from Beams to Footing it as to strengthened on the
priority basis.