SUBMITTAL DH105CAV MSP 36,000 Btu/h Heat Pump

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction
Unit Designation Schedule #

Specifications
General
Nom Cooling Capacity (Btu/h) 36,000
SEER 15.1
Cool Capacity Range (Btu/h) 9,900 to 39,000
Nom Heating Capacity (Btu/h) 38,200
HSPF 9.3
Heating COP 3.6
Heat Capacity Range (Btu/h) 11,500 to 52,900
Refrigerant Type R410A
De-Hum (Pints/Hr) 8.0
Power Voltage 208/230v-1Ph-60Hz Construction
Breaker Size 35A Indoor Unit shall be made from galvanized steel
RLA Cooling/Heating (Amps) 15.2A/14.5A The Outdoor unit shall be galvanized steel with a
Controls Wired baked on powder coated finish for durability
Indoor Unit DH105CAV
Airflows H-M-L (CFM) 790 - 640 - 510 Heat Exchangers
Max External Static ("WC) 0.47" The heat exchangers shall be mechanically bonded fin
Noise Level Low/High (Db) 48/49 to copper tube.
Width (Inches) 45 1/4"
Height (Inches) 12 5/8" Refrigerant System
Total Depth (Inches) 18 7/8" Compressors shall be a hermetically sealed DC
Weight (lbs) 86 Inverter drive rotary type
Supply Duct Connection (") 35 1/2" x 9" Refrigerant shall be R410A.
Outdoor Unit UH105CAV Refrigerant flow shall be controlled by Electronic
Outdoor Noise Level (Db) 66 Expansion Valve
Width (Inches) 36 11/16"
Height (Inches) 44 7/16" Indoor Fan
Total Depth (Inches) 14 3/4" Indoor Fan are twin backward curved centrifugal
Weight (lbs) 198 type with a single fan motor
Line Sets Units are capable of acting against 0.5" ESP
Size 3/8" & 5/8" The outdoor unit fan shall be a propeller type
Max Line Set Length inc 246ft
Max Vertical Separation of 98ft Controls
Charged with R410A for 25ft (95.2oz R410A) The unit shall be operated via a wired remote control
Addl R410A charge required 0.4oz/ft over 25ft Control signal shall be a DDC type signal
Certifications Controls shall integrate with a BMS system
Safety UL & Ulc Control wiring shall require 16AWG shielded wire
Performance ARI Certified Unit operating range shall be
ARI Certification Reference # 1502437 Cooling 5 DegF to 122 DegF
Warranty 5 Years Compressor Heating -4 DegF to 75 DegF
3 Years Parts
120 Days ltd labor Air Filtration
Options 25 or 50ft Line Sets As standard the unit has no air filtration
Condensate Pumps Filtration is field installed, pressure drop across the
Condenser Brackets filter must be factored into the total ESP applied
Quietside 8750 Pioneer Blvd, Santa Fe Springs CA 90670 Tel : 562 699 6066, Fax : 562 699 4351
6 Pine Hill Dr, Carlisle PA 17013 Tel : 717 243 2535, Fax : 717 243 7917
www.quietside.com
Due to Samsung's policy of on-going product development specifications are subject to change without notice
SAM-SUBDH105 04-2008
SUBMITTAL DH140CAV MSP 48,000 Btu/h Heat Pump
Job Name Location
Purchaser Engineer
Submitted to Reference Approval Construction
Unit Designation Schedule #

Specifications
General
Nom Cooling Capacity (Btu/h) 48,000
SEER 13.6
Cool Capacity Range (Btu/h) 10,000 to 52,600
Nom Heating Capacity (Btu/h) 54,600
HSPF 9.1
Heating COP 3.6
Heat Capacity Range (Btu/h) 15,400 to 61,000
Refrigerant Type R410A
De-Hum (Pints/Hr) 10.8
Power Voltage 208/230v-1Ph-60Hz Construction
Breaker Size 40A Indoor Unit shall be made from galvanized steel
RLA Cooling/Heating (Amps) 22.0A/20.7A The Outdoor unit shall be galvanized steel with a
Controls Wired baked on powder coated finish for durability
Indoor Unit DH140CAV
Airflows H-M-L (CFM) 1260 - 1100 - 970 Heat Exchangers
Max External Static ("WC) 0.47" The heat exchangers shall be mechanically bonded fin
Noise Level Low/High (Db) 49/50 to copper tube.
Width (Inches) 47 1/4"
Height (Inches) 14 1/8" Refrigerant System
Total Depth (Inches) 25 5/8" Compressors shall be a hermetically sealed DC
Weight (lbs) 121 Inverter drive rotary type
Supply Duct Connection (") 39 3/4" x 10" Refrigerant shall be R410A.
Outdoor Unit UH140CAV Refrigerant flow shall be controlled by Electronic
Outdoor Noise Level (Db) 66 Expansion Valve
Width (Inches) 36 11/16"
Height (Inches) 44 7/16" Indoor Fan
Total Depth (Inches) 14 3/4" Indoor Fan are twin backward curved centrifugal
Weight (lbs) 207 type with a single fan motor
Line Sets Units are capable of acting against 0.5" ESP
Size 3/8" & 3/4" The outdoor unit fan shall be a propeller type
Max Line Set Length inc 246ft
Max Vertical Separation of 98ft Controls
Charged with R410A for 25ft (116.4oz R410A) The unit shall be operated via a wired remote control
Addl R410A charge required 0.45oz/ft over 25ft Control signal shall be a DDC type signal
Certifications Controls shall integrate with a BMS system
Safety UL & Ulc Control wiring shall require 16AWG shielded wire
Performance ARI Certified Unit operating range shall be
ARI Certification Reference # 1505148 Cooling 5 DegF to 122 DegF
Warranty 5 Years Compressor Heating -4 DegF to 75 DegF
3 Years Parts
120 Days ltd labor Air Filtration
Options 25 or 50ft Line Sets As standard the unit has no air filtration
Condensate Pumps Filtration is field installed, pressure drop across the
Condenser Brackets filter must be factored into the total ESP applied
Quietside 8750 Pioneer Blvd, Santa Fe Springs CA 90670 Tel : 562 699 6066, Fax : 562 699 4351
6 Pine Hill Dr, Carlisle PA 17013 Tel : 717 243 2535, Fax : 717 243 7917
www.quietside.com
Due to Samsung's policy of on-going product development specifications are subject to change without notice
SAM-SUBDH140 04-2008
SUBMITTAL EH035CAV Slim Duct 12,000 Btu/h Heat Pump
Job Name Location
Purchaser Engineer
Submitted to Reference Approval Construction
Unit Designation Schedule #

Specifications
General EH035CAV
Nom Cooling Capacity (Btu/h) 12,000
SEER 17.8
Cool Capacity Range (Btu/h) 3,300 to 14,300
Nom Heating Capacity (Btu/h) 13,600
HSPF 9.2
Heating COP 3.4
Heat Capacity Range (Btu/h) 3,100 to 18,000
Refrigerant Type R410A
De-Hum (Pints/Hr) 5.6
Power Voltage 208/230v-1Ph-60Hz Construction
Breaker Size 20A Indoor Unit shall be made from galvanized steel
RLA Cooling/Heating (Amps) 5.5/5.4A The Outdoor unit shall be galvanized steel with a
Controls Wired baked on powder coated finish for durability
Indoor Unit EH035CAV
Airflows H-M-L (CFM) 370/320/265 Heat Exchangers
Max External Static ("WC) 0.125" The heat exchangers shall be mechanically bonded fin
Noise Level High (Db) 40 to copper tube.
Width (Inches) 35 7/16"
Height (Inches) 7 13/16" Refrigerant System
Total Depth (Inches) 23 5/8" Compressors shall be a hermetically sealed DC
Weight (lbs) 57 Inverter drive rotary type
Supply Duct Connection (") 6" x 33 3/4" Refrigerant shall be R410A.
Outdoor Unit UH035CAV Refrigerant flow shall be controlled by Electronic
Outdoor Noise Level (Db) 53 Expansion Valve
Width (Inches) 31 1/8"
Height (Inches) 21 7/8" Indoor Fan
Total Depth (Inches) 11 1/4" Indoor Fan are twin backward curved centrifugal
Weight (lbs) 74 type with a single fan motor
Line Sets Units are capable of acting against 0.125" ESP
Size 1/4" & 3/8" The outdoor unit fan shall be a propeller type
Max Line Set Length inc 65ft
Max Vertical Separation of 23ft Controls
Charged with R410A for 50ft The unit shall be operated via a wired remote control
Addl R410A charge required 0.15 oz/ft over 50ft Control signal shall be a DDC type signal
Certifications Controls shall integrate with a BMS system
Safety UL & Ulc Control wiring shall require 16AWG shielded wire
Performance ARI Certified Unit operating range shall be
ARI Certification Reference # 1362349 Cooling 23 DegF to 115 DegF
Warranty 5 Years Compressor Heating 5 DegF to 70 DegF
3 Years Parts
120 Days ltd labor Air Filtration
Options 25 or 50ft Line Sets As standard the unit has no air filtration
Condensate Pumps Filtration is field installed, pressure drop across the
Condenser Brackets filter must be factored into the total ESP applied

Quietside 8750 Pioneer Blvd, Santa Fe Springs CA 90670 Tel : 562 699 6066, Fax : 562 699 4351
6 Pine Hill Dr, Carlisle PA 17013 Tel : 717 243 2535, Fax : 717 243 7917
www.quietside.com
Due to Samsung's policy of on-going product development specifications are subject to change without notice SAM-SBEH035-10-07
SUBMITTAL EH052CAV Slim Duct 18,000 Btu/h Heat Pump
Job Name Location
Purchaser Engineer
Submitted to Reference Approval Construction
Unit Designation Schedule #

Specifications
General
Nom Cooling Capacity (Btu/h) 18,000
SEER 14.7
Cool Capacity Range (Btu/h) 5,500 to 21,000
Nom Heating Capacity (Btu/h) 20,500
HSPF 8.5
Heating COP 3.2
Heat Capacity Range (Btu/h) 5,800 to 30,700
Refrigerant Type R410A
De-Hum (Pints/Hr) 7.6
Power Voltage 208/230v-1Ph-60Hz Construction
Breaker Size 25A Indoor Unit shall be made from galvanized steel
RLA Cooling/Heating (Amps) 7.0/8.2A The Outdoor unit shall be galvanized steel with a
Controls Wired baked on powder coated finish for durability
Indoor Unit EH052CAV
Airflows H-M-L (CFM) 500-440-390 Heat Exchangers
Max External Static ("WC) 0.16" The heat exchangers shall be mechanically bonded fin
Noise Level High (Db) 40 to copper tube.
Width (Inches) 43 3/8"
Height (Inches) 7 13/16" Refrigerant System
Total Depth (Inches) 23 5/8" Compressors shall be a hermetically sealed DC
Weight (lbs) 70 Inverter drive rotary type
Supply Duct Connection (") 6" x 41 3/4" Refrigerant shall be R410A.
Outdoor Unit UH052CAV Refrigerant flow shall be controlled by Electronic
Outdoor Noise Level (Db) 58 Expansion Valve
Width (Inches) 34 5/8"
Height (Inches) 25 1/8" Indoor Fan
Total Depth (Inches) 12 1/4" Indoor Fan are twin backward curved centrifugal
Weight (lbs) 110 type with a single fan motor
Line Sets Units are capable of acting against 0.16" ESP
Size 1/4" & 1/2" The outdoor unit fan shall be a propeller type
Max Line Set Length inc 100ft
Max Vertical Separation of 49ft Controls
Charged with R410A for 25ft The unit shall be operated via a wired remote control
Addl R410A charge required 0.2oz/ft over 25ft Control signal shall be a DDC type signal
Certifications Controls shall integrate with a BMS system
Safety UL & Ulc Control wiring shall require 16AWG shielded wire
Performance ARI Certified Unit operating range shall be
ARI Certification Reference # 1362350 Cooling 23 DegF to 115 DegF
Warranty 5 Years Compressor Heating 5 DegF to 70 DegF
3 Years Parts
120 Days ltd labor Air Filtration
Options 25 or 50ft Line Sets As standard the unit has no air filtration
Condensate Pumps Filtration is field installed, pressure drop across the
Condenser Brackets filter must be factored into the total ESP applied

Quietside 8750 Pioneer Blvd, Santa Fe Springs CA 90670 Tel : 562 699 6066, Fax : 562 699 4351
6 Pine Hill Dr, Carlisle PA 17013 Tel : 717 243 2535, Fax : 717 243 7917
www.quietside.com
Due to Samsung's policy of on-going product development specifications are subject to change without notice SAM-SBEH052-02-08
SUBMITTAL EH070CAV Slim Duct 24,000 Btu/h Heat Pump
Job Name Location
Purchaser Engineer
Submitted to Reference Approval Construction
Unit Designation Schedule #

Specifications
General
Nom Cooling Capacity (Btu/h) 24,000
SEER 15.8
Cool Capacity Range (Btu/h) 6,500 to 27,000
Nom Heating Capacity (Btu/h) 27,000
HSPF 8.5
Heating COP 3.5
Heat Capacity Range (Btu/h) 7,000 to 37,000
Refrigerant Type R410A
De-Hum (Pints/Hr) 10.2
Power Voltage 208/230v-1Ph-60Hz Construction
Breaker Size 30A Indoor Unit shall be made from galvanized steel
RLA Cooling/Heating (Amps) 10.5/10.5A The Outdoor unit shall be galvanized steel with a
Controls Wired baked on powder coated finish for durability
Indoor Unit EH070CAV
Airflows H-M-L (CFM) 635-565-500 Heat Exchangers
Max External Static ("WC) 0.16" The heat exchangers shall be mechanically bonded fin
Noise Level High (Db) 42 to copper tube.
Width (Inches) 43 3/8"
Height (Inches) 7 13/16" Refrigerant System
Total Depth (Inches) 23 5/8" Compressors shall be a hermetically sealed DC
Weight (lbs) 70 Inverter drive rotary type
Supply Duct Connection (") 6" x 41 3/4" Refrigerant shall be R410A.
Outdoor Unit UH070CAV Refrigerant flow shall be controlled by Electronic
Outdoor Noise Level (Db) 60 Expansion Valve
Width (Inches) 34 5/8"
Height (Inches) 27 3/4" Indoor Fan
Total Depth (Inches) 12 1/4" Indoor Fan are twin backward curved centrifugal
Weight (lbs) 125 type with a single fan motor
Line Sets Units are capable of acting against 0.16" ESP
Size 1/4" & 5/8" The outdoor unit fan shall be a propeller type
Max Line Set Length inc 100ft
Max Vertical Separation of 49ft Controls
Charged with R410A for 25ft The unit shall be operated via a wired remote control
Addl R410A charge required 0.1oz/ft over 25ft Control signal shall be a DDC type signal
Certifications Controls shall integrate with a BMS system
Safety UL & Ulc Control wiring shall require 16AWG shielded wire
Performance ARI Certified Unit operating range shall be
ARI Certification Reference # 1362351 Cooling 23 DegF to 115 DegF
Warranty 5 Years Compressor Heating 5 DegF to 70 DegF
3 Years Parts
120 Days ltd labor Air Filtration
Options 25 or 50ft Line Sets As standard the unit has no air filtration
Condensate Pumps Filtration is field installed, pressure drop across the
Condenser Brackets filter must be factored into the total ESP applied

Quietside 8750 Pioneer Blvd, Santa Fe Springs CA 90670 Tel : 562 699 6066, Fax : 562 699 4351
6 Pine Hill Dr, Carlisle PA 17013 Tel : 717 243 2535, Fax : 717 243 7917
www.quietside.com
Due to Samsung's policy of on-going product development specifications are subject to change without notice SAM-SBEH070-02-08