HVAC

S.NO ITEM DESCRIPTION CAPACITY


AHUS CMH CFM OUTSIDE AIR
1 AIR HANDLING UNIT-1 6500 3824
2 AIR HANDLING UNIT-2 23020 13543
3 AIR HANDLING UNIT-3 13000 7648
4 AIR HANDLING UNIT-4 16700 9825
5 AIR HANDLING UNIT-5 10200 6001
6 AIR HANDLING UNIT-6 16700 9825
7 AIR HANDLING UNIT-7 23020 13543
8 AIR HANDLING UNIT-8 23020 13543
9 AIR HANDLING UNIT-9 23020 13543
10 AIR HANDLING UNIT-10 23020 13543
11 AIR HANDLING UNIT-11 23020 13543
TOTAL 201220 118378

NOTE:
1 ABOVE ALL AHUS INCLUDES ERV UNITS(ENERGY RECOVERY VENTILATORS UNITS)
FAN COIL SECTION, COIL SECTION, PRE-FILTER(MERV8-10 MICRON) & RETURN AIR
MIXING BOX, PLENUM FOR BAG TYPE FILTER(MERV13-5 MICRON).
2 SUPPLY AIR CENTRIFUGAL BACKWARD CURVE FAN WITH EFFICIENCY > 65%.
3 COIL OF COPPER TUBE AND ALUMINIUM CONSTRUCTION SIZED AT MAXIMUM
FACE VELOCITY 2.5 mtr/Sec.
4 FAN OUTLET VELOCITY NOT TO EXCEED 10 M/SEC.
5 EACH ERV UNITS SHALL BE PROVIDED WITH NECESSARY PRESSURE SENSOR AND
TEMPERATURE SENSOR AT FRESH AIR PATH AND RETURN AIR PATH.EXHAUST
SECTION OF THE UNIT SHALL BE PROVIDED WITH MOTOR ACTUATED GSS DAMPER
DULY INTERLOCKED WITH THE FAN.THE UNITS SHALL BE PROVIDED WITH
NECESSARY CONTROLLER.
6 HRW SHALL BE LOCATED BETTWEEN FRESH AIR & EXHAUST AIR STREAMS DESIGNED
FOR FRESH AIR & EXHAUST AIR QUANTITY FOR ERV UNIT.
7 HRW SHALL BE DESIGNED FOR AMB. TEMP. OF DBT 106 DEG F & WBT 78 DEG F &
EXHAUST AIR TEMP. OF 77 DEG F & RH 55%.
8 UNIT MOUNTED PRE-FILTERS (MERV 8) IN FRESH AIR STREAM/EXHAUST AIR STREAM
9 MIXING AIR COOLING COIL CAPACITY : 7/12 DEG C

S.NO ITEM DESCRIPTION


FAN COIL UNITS

PENDING
S.NO ITEM DESCRIPTION
CAPACITY QTY
KW TR Nos
10 1
30 1
20 1
25 1
15 1
25 1
30 1
30 1
30 1
30 1
30 1
275 11

ORS UNITS)
RETURN AIR

> 65%.
AXIMUM

NSOR AND
XHAUST
GSS DAMPER
ITH

AMS DESIGNED

78 DEG F &

ST AIR STREAM

QTY
TR Nos
QTY
TR Nos
HVAC
S.NO ITEM DESCRIPTION CAPACITY QTY
CHILLER TR Nos
1 SUPPLY OF WATER COOLED SCREW CHILLER UNIT 275=300 1
REFRIGANT SHALL BE R134a ONLY

TOTAL 1

NOTE:
MINIMUM COP AT AHRI CONDITION SHOULD BE 6.1 AS RECOMMENDED
BY ENERGY CONSERVATION BUILDING CODE (ECBC)