Saudi Aramco Inspection Checklist: Glass & Glazing Pre-Installation Inspection SAIC-M-1059 18-May-05 Civil
Saudi Aramco Inspection Checklist: Glass & Glazing Pre-Installation Inspection SAIC-M-1059 18-May-05 Civil
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
________________________________________
SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
External Windows are prohibited for in plant buildings and out of plant
buildings located near enough to a plant where it is possible to receive SAES-B-014
A1
3.5 kPa gauge (0.5psig) Peak Side-on Overpressure or more from a Sec. 5.8
Vapor Cloud Explosion.
The rough opening shall be larger in both width and height than the
SAES-M-100
A2 actual net dimension of the product to be installed.
Sec. D
(1997 UBC, Sec. 2404.1)
Glass Shall be transparent or patterned wired flat glass, clear or tinted, SAES-M-100
A3
intended for general glazing applications.(1997 UBC, Sec 2404.4.1 & .2) Sec. D
Glass shall not contain cracks; surfaces shall be clear, sharp, defined
SAES-M-100
A5 and free of obvious flaws that effect appearance and function.
Sec. D
(1997 UBC, Sec 2404.4.1 & .2)
REMARKS:
REFERENCE DOCUMENTS:
1- SAES-M-100 -- Saudi Aramco Building Code, 29 January 2003
2- 1997 UBC -- Uniform Building Code, 1 January 1997
Page 1 of 1