You are on page 1of 3

SAUDI ARAMCO ID/PID - 2/19/05 - REV 0 (Standards Cutoff - August 2004)

SAIC NUMBER DATE APPROVED QR NUMBER


SAUDI ARAMCO INSPECTION CHECKLIST
Metal Duct Insulation Installation SAIC-K-4015 18-May-05 HVAC
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Duct joints shall be sealed prior to insulation. SAES-K-001


A1
(SMACNA Para S 1.9) Para 4.8.12.5

Mechanical fasteners, adhesive, tapes, metal straps or any other means


at the intervals specified in the construction drawings or specifications SAES-K-100
A2
shall be used in the installation of the duct insulation Section 1
(UMC Para 604.3).

Internal duct lining shall not be used, except in acoustically sensitive


areas, with the prior approval of Chairman, HVAC Standards Committee.
SAES-K-001
A3 Exception:
Para 4.8.13.2
Internal lining, that includes protective coating to prevent erosion, is
permitted for terminal boxes and air handling units.

Duct liners in systems operating with air velocities exceeding 2,000 feet
per minute (10.2 m/s) shall be fastened with both adhesive and
mechanical fasteners
SAES-K-100
A4 Note: Air velocities may be read from the contract specification or
Section 1
Drawings. However, if the air velocities are not shown, the expected air
velocity at the concerned duct section (s) shall be provided by SAPMT
through designers

Ducts shall be insulated in accordance with Table 6-D of the Uniform SAES-K-001
A5
Mechanical Code. See attachment no. 1 Para 4.8.13.1

Insulation installed outdoor shall be protected from moisture and sunlight


degradation by an approved and acceptable method SAES-K-001
A6
(Material and Method shall be approved by Saudi Aramco prior to Para 4.8.13.5
application)

Insulation applied to the exterior surface of ducts located in buildings


shall have a flame spread index of not more than 25, smoke density
SAES-K-100
A7 index not exceeding 50 when tested as a composite installation including
Section 1
insulation, facing material, tapes and adhesive as normally applied.
(UMC Para 604.3)

Page 1 of 3
SAUDI ARAMCO ID/PID - 2/19/05 - REV 0 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Metal Duct Insulation Installation SAIC-K-4015 18-May-05 HVAC
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

REMARKS:

REFERENCE DOCUMENTS:
1-SAES-K-001 -- Heating, Ventilation and Air Conditioning, May 31, 2004

2--SAES-K-100 -- Saudi Aramco Mechanical Code, May 31, 2004

3-SMACNA -- HVAC Duct Construction Standards, Metal & Flexible, 1995

4-Uniform Mechanical Code (UMC), 1997

ATTACHMENTS:
1. Table 6-D-Insulation of Ducts

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 2 of 3
SAUDI ARAMCO ID/PID - 2/19/05 - REV 0 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Metal Duct Insulation Installation SAIC-K-4015 18-May-05 HVAC

Attachment 1 --
1997 UNIFORM MECHANICAL

Page 3 of 3