00 28-Feb-18
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
A Installation Inspection
Coating shall not be applied when the substrate temperature is less than SAES-H-001
A2
10°C; or less than 3°C above dew point. Sec. 6.1.1
Coating shall not be applied when wind is strong enough to blow sand, salt SAES-H-001
A3
spray, or other foreign matter onto the surface being coated. Sec. 6.1.1 - d)
SAES-H-003
A4 Only Saudi Aramco Approved Products shall be allowed for used.
Sec. 4
The coating shall be visually inspected for defects and shall meet the SAES-H-003
A6
requirements of the coating manufacturer's data sheets. Sec. 9.3.2
B Final Inspection
The applicator shall repair all coating defects in accordance with the SAES-H-003
B1
coating manufacturers' recommendations and SAES-H-101V. Sec. 9.5.1
All defects shall be corrected and all damage from inspections (i.e., SAES-H-003
B2
adhesion testing, wet film thickness tests etc.), shall be repaired. Sec. 9.5.2
REMARKS:
REFERENCE DOCUMENTS:
1- SAES-H-003 -- Coating Requirements for Concrete Surfaces, 22 February 2018
2- SAES-H-001 - Coating Selection and Application Requirements for Industrial Plants and Equipment,21 February 2018