Motor 75 K.w & 440 v & Specify rating Of cables ,
Contactors , O.L , Main Breaker ?

PDF created with pdfFactory Pro trial version www.pdffactory.com

SOLUTION :
In ( line Current ) = 75000 / 1.73 x 440 x 0.79 = 124 A
Line cable carry 1.25 x 124 =155 A
From Table Use cable size 35 mm ( From Line To CM )
MCCB = 1.75 x In=1.75 x 124 =217 A ( 225A Standard )
Motor Side : CM & CD = Delta connection
Id = In / 1.73 = 124 / 1.73 = 71.6 A
Motor Side ( 6 Wire ) cable carry 1.25 x 71.6 =90 A
From Table Use cable size 16 mm ( From Motor To CM
&CD) & ( 3 wire ) between 3 contactors
Contactors Rating :
Ic = 1.15 x I
ICM = 1.15 x Id = 1.15 x 71.6 =82 A ( Standard 80 A )
O.L.C = ( 60 80 A )
ICD = ICM = 80 A
ICS = 1.15 x Is
IS = Id / 1.73 = 71.6 / 1.73 = 41.4 A
ICS = 1.15 x 41.4 = 47.6 A (Standard 50 A )
..................................................................................
: