This document contains an ampere calculation for an electrical system with the following parameters: a connected load of 15,200 kW, a load factor of 0.75, a power factor of 0.85, an efficiency of 0.88, a system voltage of 11 kV, and a margin of 20%. Based on these inputs, the running load is calculated to be 11,400 kW, the total current is calculated to be 959.91 amps, and applying an equipment rating factor of 0.8 to this results in a final ampere rating of 1,000 amps for the system.
This document contains an ampere calculation for an electrical system with the following parameters: a connected load of 15,200 kW, a load factor of 0.75, a power factor of 0.85, an efficiency of 0.88, a system voltage of 11 kV, and a margin of 20%. Based on these inputs, the running load is calculated to be 11,400 kW, the total current is calculated to be 959.91 amps, and applying an equipment rating factor of 0.8 to this results in a final ampere rating of 1,000 amps for the system.
Copyright:
Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLSX, PDF, TXT or read online from Scribd
This document contains an ampere calculation for an electrical system with the following parameters: a connected load of 15,200 kW, a load factor of 0.75, a power factor of 0.85, an efficiency of 0.88, a system voltage of 11 kV, and a margin of 20%. Based on these inputs, the running load is calculated to be 11,400 kW, the total current is calculated to be 959.91 amps, and applying an equipment rating factor of 0.8 to this results in a final ampere rating of 1,000 amps for the system.