Professional Documents
Culture Documents
1. Introduction
Power Generation
(generators, turbines)
Transmission Systems
Distribution Systems
Energy Sink
Introduction
(Cont.)
Power Plants Transformers Transmission Lines Circuit Breakers & Disconnect Switches Loads
Power Plants
At the power plant, the energy resources such as fossil fuels (oil, gas, coal), hydro and nuclear are converted into electricity The main parts of power plant are:
the burner (in fossil fuel plants), the reactor (in nuclear power plants) , the dam (in hydro plants), the turbine and the generator
7
The source of mechanical energy is the prime mover which is directly coupled to the generator.
Mechanical Energy Prime mover Rotating electric generator Electrical Energy
Fuel
4. Transformers
(as the current is proportionally stepped down) at a much higher level so that power can be transmitted up to hundreds of kilometers while conductor size and losses are kept down within practical limits.
10
5. Transmission Lines
The transmission line delivers the electrical power from the generating plant to the customer The bulk power of the generating plant is transmitted to the load centers over long distance line called High Voltage lines The transmission consists of three conductors (either as three single wires or as bundles of wires) and one or more Shield conductors. The conductors are hanged to insulators (non conductive material) to hold them away from the tower structure The insulators must withstand the forces during wind storms & freezing rain conditions.
shield conductors Three-phase conductors Insulators
Supporting structure
11
The transmission lines that distribute the power within a city are called medium voltage distribution lines Since the voltage distribution is much lower, the distribution towers are shorter and their insulators are smaller (wooden, steel, concrete poles)
Commercial and industrial customers use transmission lines and their own transformers to step down the voltage to the level required In residential areas utilities install transformers to reduce the voltage to 100 -240 V level depending on the standard practice of the country.
12
Circuit Breaker
Disconnect Switches
3-phase Supply
Oil or gas (SF6: sulfur hexafluoride) are used to suppress the arc when the circuit breakers contacts are opened under load.
Disconnect switches are placed in series with circuit breakers to completely isolate (or de-energize) them after they open (no-load).
13
10. Loads
Peak load
System load varies through daily and annual cycles, creating difficult operating problems. A typical load curve is shown in the figure.
Power 12
Any device that utilizes electric power can be said to impose a load on the electric system.
8 AM
12
8 Time
PM
12
14
Country
Brazil Canada
Frequency (Hz)
60 60 50 50 50 50 60 50/60
China
Egypt Oman UK USA
Japan
15
Thomas Edison came up with a high-resistance lamp filament that operated well at 120 V.
the cross section of the copper wires is smaller for higher voltages.
Lower voltage circuits are safer than the high voltage ones
16
In Europe, Siemens and AEG have established the 50Hz as a standard for their power grid. Most of Asia, parts of South America, all Africa, and the Middle East have adopted the same 50Hz standard. In the USA, Westinghouse adopted the 60Hz standard.
60 Hz is high enough frequency to eliminate light flickers in certain types of incandescent lamps
17