You are on page 1of 8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..

Louvers

Experts in Noise Control Solutions

Alara-Lukagro Louvers

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Alara-Lukagro louvers offer a good protection for air intake and exhaust openings to technical installations.
The louvers are suitable for commercial and industrial construction, infrastructure, offshore and the
shipbuilding industry.

Acoustic louvers

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Alara-Lukagro acoustic louvers, type AL-R, provide solutions for sound attenuated ventilation openings.

Properties
Limited depth for built-in element.
Low air resistance.
Many designs possible, low maintenance and durable.
Aesthetic added value due to identical appearance of louvers with different insulation values.

Insulation values
Louver type

Rw (C, Ctr)

Louver type

Rw (C, Ctr)

AL-R / 150

12 dB (0,-1)

AL-R / 300V

20 dB (-1,-4)

AL-R / 300

19 dB (-1,-3)

AL-R / 600V

27 dB (-2,-7)

.....................

.....................

Models
Standardized and custom-made models are available.
Sound insulation up to Rw 27 dB tested in accordance with NEN-EN-ISO 140-3.
The high-quality absorption material is re-resistant in accordance with DIN 4102 class A2.
Manufactured from galvanized steel, corrosion resistant steel or (seawater resistant) aluminium.
Supplied with ange assembled in accordance with your specications, delivered separately or
without ange.
Resistant to birds, rain and/or snow.

In combination with ventilator plenums, multileaf dampers, re dampers, dust-/sand traps and drip
catchers.
Model as roof hood is possible.
In-house blasting and preservation is possible (powder coating, primer and wet paint).
Ask for our datasheets, drawings and/or specication texts for detailed technical information or
download these on www.alara-lukagro.com.

Applications
Ask for our reference sheets about projects with specic applications, for instance acoustic louvers for
technical spaces, plant rooms, engine rooms, boilerhouses, rooms for aggregates and compressors,
enclosures, containers, cooling towers, power plants, air-cooled condenser units, parking garages and
wind turbines.

Ventilation louvers

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Alara-Lukagro ventilation louvers offer a suitable solution if no acoustic requirements are set. Otherwise,
properties are comparable to those of the Alara-Lukagro acoustic louvers.

Ask for our datasheets and drawings for detailed technical information or download these on
www.alara-lukagro.com.

Non-intrusive louvers

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
For situations in which a high level of safety, vandalism resistance, intrusion protection or drill safety
are required, the patented Alara-Lukagro louvers, type AL-R/T, are a good choice.

Properties
Suitable for transformer rooms and manufactured in accordance with the performance requirements
and directives of various power companies.
Non-intrusive, self-extinguishing, rodent-tight, and resistant to rain, snow and dust.

Resistant to vandalism.
Blades grounded to frame due to metallic unity.
Aesthetic added value due to a seamless integration with facade/door.
Many designs possible, durable and low maintenance.
Patented louver elements.

Louver type

Net free opening

Louver type

AL-R / THA30

30%

AL-R / TVA30

30%

AL-R / THA47

47%

AL-R / TVA42

42%

AL-R / THA54

54%

........................

Net free opening

........................

Models
Standardized and custom-made models are possible.
Fire resistance >60 minutes tested in accordance with NEN 6069 / NEN-EN 1634 (60 min. WBDBO).
Manufactured in aluminium and steel.
Louver blades (built-in/built-on) and frame are completely welded.
Can be combined with non-ventilating blind louver elements.
Model as roof hood is possible.
Can be manufactured as complete louver facade.
In-house blasting and preservation is possible (powder coating).
Ask for our datasheets, drawings and/or specication texts for detailed technical information or
download these on www.alara-lukagro.com.

Applications
Ask for our reference sheets about projects with specic applications, for instance non-intrusive
louvers for high-, medium- and low voltage areas, transformer- and switching stations, plant rooms,
transformer substations for gas, gas storage spaces, engine rooms and rooms for compressors,
emergency power supply aggregate (NSA) rooms, parking garages, prefab enclosures and nonintrusive louvers for offshore applications.

Subject to change without notice.

Quality guaranteed

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..

Custom-made and specials


Whether you are searching for standard louvers or custom-made louvers, with over 40 years of
experience, we are able to produce the most varied and exceptional projects for you.

Guarantee and quality


Alara-Lukagro designs, manufactures and preserves the products in-house. This way, the entire
process can be controlled and we are able to offer you a high degree of quality, user-friendliness and
a good price-quality ratio.

Alara-Lukagro is ISO 9001 and ISO 14001 certied. As a result, the durability of all materials that are
used can be guaranteed. All product-specic properties are secured due to extensive testing in
laboratories in accordance with international standards (for instance NEN, EN and ISO) and are
supported by certicates.

Service and assembly


Alara-Lukagro offers total solutions, ranging from advice and design to production and assembly.
Delivery and assembly is possible around the world. Our installers are VCA (Safety Checklist

ALR1

Contractors) and NOGEPA certied.

Worldwide delivery and implementation


;dYbeikh[iWdZmWbbi
:eehi
I_b[dY[hi
Bekl[hi
L_XhWj_ed_iebWjehi
HeecWYekij_Yi
8bWij_d]WdZfh[i[hlWj_ed

...................................................................................
Alara-Lukagro bv | Huijgensweg 3 | NL-2964 LL Groot-Ammers | P.O. Box 15 | NL-2964 ZG Groot-Ammers
T +31 (0) 184 661 700 | F +31 (0) 184 662 721 | E info@alara-lukagro.com | I www.alara-lukagro.com

..................................................................................................................

Datasheet
Acoustic louvers AL-R/150 - 300 - 300V - 600V
Dimensions

Applicable in combination with

Standardized and custom-made models are available - the

Ventilator plenums, multileaf dampers, fire dampers, dust-/sand

acoustic louvres are available in almost any size. Up to a width x

traps and drip catchers. Resistant to birds, rain and/or snow.

height = 2.450 x 2.850 mm the louvres are produced in one piece.

Model as roof hood is possible.

Larger louvres are supplied in parts.

Flange

Absorbtion material

Supplied with flange assembled in accordance with your

The high-quality absorption material is fire-resistant in accordance

specifications, delivered separately or without flange.

with DIN 4102 class A2.

Material

Properties

Manufactured from galvanized steel, corrosion resistant steel or

High sound attenuation, limited depth for built-in element, low air

(seawater resistant) aluminium.

resistance, many designs possible, low maintenance and durable,


aesthetic added value due to identical appearance of louvers with

Preservation
In-house blasting and preservation is possible (powder coating,

different insulation values.

primer and wet paint).

Pressure loss
In the below graphs the free area can be found. The speed between the blades can be calculated with the formula:
Where vs = air speed between blades [m/s] qv = air flow [m3/uur] B = louvre width [m] H = louvre height [m] VD = free area [%]
Subsequently, the pressure loss at the air speed can be read from the graph on the right. These pressure losses are based on a surface
in the front mounted louvre. Depending on the positioning the pressure loss may deviate 5 to 10%.

Insertion loss

Air borne sound insulation

According to ISO 7235:2003 (Peutz report A 1659-1):

According to ISO 140-3:1995 (Peutz report A 1659-1):

63

125

250

500

1k

2k

4k

8k

63

125

250

500

1k

2k

4k

8k

Rw(C, Ctr)

AL-R/150

13

13

12

12

10

13

13

12

12

12 (0,-1)

AL-R/300

14

21

22

16

14

10

10

14

21

22

16

14

19 (-1,-3)

AL-R/300V

15

22

24

23

24

10

15

22

24

23

24

20 (-1,-4)

AL-R/600V

10

13

23

38

39

32

30

12

14

24

38

40

32

30

27 (-2,-7)
Subject to change without notice.

Dimensions
Standardized and custom-made models are available - the acoustic louvres are available in almost any size. Up to a width x height =
2.450 x 2.850 mm the louvres are produced in one piece. Larger louvres are supplied in parts.

AL-R 300

AL-R 300V

AL-R 600V

P.O. box 15 | NL-2964 ZG Groot-Ammers | The Netherlands | T +31 (0)184 661 700 | E info@alara-lukagro.com | I www.alara-lukagro.com

ALR300-2

AL-R 150

You might also like