UNIT-3 TG PG TEST PARAMETERS

CONDENSER PERFORMANCE DATA


LOAD: 351 MW
06.09.2016
SLNO
1

DESCRIPTION
Condenser DP Left

TIME: 13:30

Date:

VALUE
0.27

UNITS
Kg/cm2

Condenser DP Right

0.52

Kg/cm2

2.70

Kg/cm2

2.39

Kg/cm2

2.88

Kg/cm2

2.41

Kg/cm2

34.5
43.5

Deg C
Deg C

34.5

Deg C

43

Deg C

11
12

Condenser Inlet pressure


Left
Condenser Outlet
pressure Left
Condenser Inlet pressure
Right
Condenser Outlet
Pressure Right
CW inlet temperature Left
CW Outlet temperature
Left
CW inlet temperature
Right
CW Outlet temperature
Right
Hotwell temperature
Condenser Vacuum

48.5
0.1265

Deg C
Kg/cm2
(abs)

13
14
15

CW flow left
CW flow Right
Debris Filter left DP

22500
33000
80

M3/HR
M3/HR
Mbar

16

Debris Filter Right DP

4
5
6
7
8
9
10

50

Mbar

REMARKS
0.29 on
3/09/2016
0.51
on3/09/2016

0.15 at 480 MW
corresponding
to hotwell
temperature of
54 C on
3/09/2016
Local gauge of
Debris Filter/
Transmitter
saturated
Transmitter/
Gauge

The above values except flows (taken from Honeywell


system) and debris filter DPs (local gauge/ system
transmitters)are taken from the PG test instruments erected by
BHEL.