You are on page 1of 2

DEIGN OF PIPE UNDER GRAVITY FROM A SOURCE

Mian Zafar T.W.W.Course:

Location = Aman Garh

INPUT DATA
DIAMETER OF THE PIPE

0.127

ROUGHNESS "N" VALUES FOR

0.012

&m

CONCRETE, GI, PVC PIPES ARE 0.013,


0.012 & 0.01RESPECTIVELY
SLOPE OF THE PIPE

0.025

Pipe sizes in inches

m/m

OUTPUT DATA

inches

0.0254

0.0508

0.0762

0.1016

X.SECTIONAL AREA "A" OF THE PIPE

0.012661 m2

0.1524

INSIDE PERIPHERY "P" OF THE PIPE

0.39878 m

0.2032

HYDRAULIC RADIUS "R"

0.03175 m

0.2286

12

0.3048

15

0.381

18

0.4572

USING MANNING,S EQUATION FOR

1.320995 m/sec

INSIDE VELOCITY

DISCHARGE

16.73 Lps

GI & PVC PIPES UNDER PRESURE CONNECTING DIRECTLY TO THE PUMP


Name of Scheme:
Location:
Misri Banda
Habib Ghafoor TWWC
INPUT DATA
DISCHARGE
DIAMETER OF THE PIPE
LENGTH OF THE PIPE
SUCTION HEAD
DELIVERY HEAD
USE THE VALUE OF"C"FOR GI &PVC
PIPES 120 & 140 RESPECTIVELY
ELECTRIC AND DIESEL EFFICIENCIES
ARE 0.6 & 0.4 RESPECTIVELY
USE THE LIMITING VELOCITIES OF 2.8
&1.5 M/SEC FOR GI &PVC PIPES

10
101.6
450
4
9
140

Lps
mm
m
m
m

0.6
1.5

m/sec

0.0081
1.234

m2
m/sec

6.926
1.039
20.965
4.60

m
m
m
HP

OUT PUT DATA


X-SECTIONAL AREA
VELOCITY INSIDE THE PIPE
HEAD LOSS DUE TO FRICTION(Hf)
MINOR LOSSES
TOTAL HEAD
PUMP HORSE POWER "HP" REQUIRED
IF VELOCITY INSIDE THE PIPE IS OK ,THEN USE
THAT SIZE,OTHER WISE TRY ANOTHER ONE

Designed by:_____________________
WMO

OK

Pipe sizes in inches


& mm
inches
mm
1
25.4
1.5
38.1
2
50.8
2.5
63.5
3
76.2
4
101.6
5
127
6
152.4
8
203.2