DEIGN OF PIPE UNDER GRAVITY FROM A SOURCE

Mian Zafar T.W.W.Course: Location = Aman Garh

INPUT DATA

DIAMETER OF THE PIPE 0.127 m Pipe sizes in inches

ROUGHNESS "N" VALUES FOR 0.012 &m

CONCRETE, GI, PVC PIPES ARE 0.013, inches m

0.012 & 0.01RESPECTIVELY 1 0.0254

SLOPE OF THE PIPE 0.025 m/m 2 0.0508

3 0.0762

OUTPUT DATA 4 0.1016

X.SECTIONAL AREA "A" OF THE PIP 0.012661 m2 6 0.1524

INSIDE PERIPHERY "P" OF THE PIPE 0.39878 m 8 0.2032

HYDRAULIC RADIUS "R" 0.03175 m 9 0.2286

USING MANNING,S EQUATION FOR 1.320995 m/sec 12 0.3048

INSIDE VELOCITY 15 0.381


DISCHARGE 16.73 Lps 18 0.4572
GI & PVC PIPES UNDER PRESURE CONNECTING DIRECTLY TO THE PUMP
Name of Scheme: Habib Ghafoor TWWC Location: Misri Banda
Pipe sizes in inches
INPUT DATA & mm
inches mm
DISCHARGE 10 Lps 1 25.4
DIAMETER OF THE PIPE 101.6 mm 1.5 38.1
LENGTH OF THE PIPE 450 m 2 50.8
SUCTION HEAD 4 m 2.5 63.5
DELIVERY HEAD 9 m 3 76.2
USE THE VALUE OF"C"FOR GI &PVC 140 4 101.6
PIPES 120 & 140 RESPECTIVELY 5 127
ELECTRIC AND DIESEL EFFICIENCIES 0.6 6 152.4
ARE 0.6 & 0.4 RESPECTIVELY 8 203.2
USE THE LIMITING VELOCITIES OF 2.8 1.5 m/sec
&1.5 M/SEC FOR GI &PVC PIPES

OUT PUT DATA

X-SECTIONAL AREA 0.0081 m2


VELOCITY INSIDE THE PIPE 1.234 m/sec
HEAD LOSS DUE TO FRICTION(Hf) 6.926 m
MINOR LOSSES 1.039 m
TOTAL HEAD 20.965 m
PUMP HORSE POWER "HP" REQUIRED 4.60 HP

IF VELOCITY INSIDE THE PIPE IS OK ,THEN USE


OK
THAT SIZE,OTHER WISE TRY ANOTHER ONE

Designed by:_____________________
WMO

You might also like