You are on page 1of 8

High voltage engineering, Network protection

Power transformer protection


Overcurrent protection
overcurrent relay
instantaneous tripping in high-voltage side faults
delayed tripping in low-voltage side faults
inrush current (switching current surge)
has to be taken into account
differential relay
Earth fault protection
earthed network
overcurrent relaying
measurement and time delay of the neutral point current
differential current relay
neutral isolated network; measurement of zero-sequence voltage
(delay)
J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

Winding and interturn fault protection


In an interturn fault, there occur high currents in the
turns experiencing an interturn short circuit. However,
only small current changes can be seen outside
the transformer.
Buchholz gas relay
also insulation failures
Differential relay
faster than gas relay
J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

Overload protection

measurement of the oil temperature


time delay with respect to the temperature rise of the winding

winding temperature indicator


resistance element that passes a current proportional to the
load current

Overvoltage protection
> 10 % overvoltage damages the transformer (saturation)
U/f control
J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

Transformer differential protection


The protection has to be stable and sensitive:
Operation:
in faults inside the protection zone
when switching against a fault in the protection zone
when the transformer is overexcited
May not operate:
when switching a transformer to the grid (no fault)
when the voltage is restored to normal after clearing an external
fault
in faults outside the protection zone
when switching a parallel transformer to the grid
when switching a transformer against a fault outside the
protection zone
J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

P1

P2

110/20 kV

P2

P1

J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

Transformer differential protection


Problems to be solved:
saturation of current transformers
transformer inrush current
transformer overexcitation
compensation of the vector group of the transformer
stabilization of the operation
no-load current
on-load tap changer

J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

Inrush current in the transformer


The iron core of the transformer saturates strongly
when, under certain conditions, the transformer is
connected to the network
The inrush current may reach a value of 1020 x In, 500
x I0
depends on the transformer and the instant at which
the transformer is switched out (disconnected) from
the network
occurs always at some phase
dampens in 0.130 s
7

J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

The switching current includes plenty of harmonics;


compared with the excitation current of the normal
state, there occurs also some 2nd harmonic.
blocking based on the ratio I2/In (does not always work)
blocking based on the curve form of the differential current
Transformer
power MVA

Supply to the
high-voltage
side winding

Supply to the
low-voltage
side winding

Time in which the


current decreases to
half / s

7N

12N

0.10.2

5N

9N

0.20.5

10

4N

8N

0.51.0

50

3,5N

7,5N

1.27.2

Measured values of the transformer inrush current.


J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

Transformer overexcitation
Voltage rise of the transformer supply (load drop)
U/f, voltage rise causes an increase in the excitation
current; an increase in harmonics in the differential current
Identification from the 5th current harmonic
Detection from the current curve form:
During the cycle, there are two periods, during which the
differential current is of the magnitude of the normal
excitation current.
9

J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection

The transformer excitation current and the current harmonics in overvoltage


situation. The rated power of the transformer is 60 MVA and the rated
voltage 78 kV. The transformer core material is grain-oriented steel. In the
table below, U is voltage, Un rated voltage, Im transformer excitation current,
In transformer rated current, I1f fundamental harmonic of the excitation
current, I3f 3rd harmonic and I5f 5th harmonic.

U
/%
Un

Im
/%
In

I1 f
Im

/%

I3 f
I1 f

/%

I5 f
I1 f

/%

100

<1

93

34

24

110

76

67

48

120

72

76

54

130

25

76

73

44

140

46

80

68

32

150

70

84

62

22

J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

10

Network protection, Power transformer protection

Current transformer saturation


DC component
there are plenty of 2nd and 3rd harmonics in the secondary
current
High primary current
only odd harmonics
In faults outside the protection zone, the current transformers of
the primary and secondary may saturate at different time instants
differential current
Calculation of differential current right after the instant at which the
polarity (sign) of the current changes removes the above problem.
J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

11

Protection technology, instrument transformers

Saturation of the current transformer

Excitation curve of the iron core


non-linear and saturating
knee-point voltage
Saturates
at a high sinusoidal overcurrent
as a result of the DC component of the primary current
as an effect of remanence

J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

12

Protection technology, instrument transformers

Saturation of the current transformer


Magnetic flux density / T

Time / ms

Magnetic flux density of the core of a current transformer, when there is a high
short-circuit current including a DC component in the primary
(Bs 2.1 T and
13

J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

Protection technology, instrument transformers

Saturation of the current transformer


Current / A
Primary current

Secondary current

Time / ms
Primary and secondary current of a current transformer saturated by a large DC
component. The primary current is referred to the secondary of the current
transformer.
J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

14

Network protection, Power transformer protection

Vector group compensation


Numerical relays: mathematical algorithms
Yd and Dy compensation
subtraction of phase currents
problems in inrush current (phase shift 120) and when the
current transformers are saturating

Delaying of samples
small delay

15

J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

Network protection, Power transformer protection


Vector group compensation by delaying the samples of the phase current and by changing
the polarity (sign reversal). In the table, NS is the number of samples during one cycle. The
factor 1 corresponds to the 180 phase shift of the phase current.

Clock
reading
0
1
2
(3)
4
5
6
7
8
(9)
10
11

Primary current
Delay
Factor
0
(1/12) NS
(2/12) NS
(3/12) NS
0
0
0
(1/12) NS
(2/12) NS
(0)
0
0

1
1
1
(1)
-1
-1
-1
1
1
(1)
1
1

Secondary current
Delay
Factor
0
0
0
(0)
(2/12) NS
(1/12) NS
0
0
0
((3/12) NS)
(2/12) NS
(1/12) NS

J.Partanen
www.ee.lut.fi/fi/lab/sahkomarkkina/

1
1
1
(1)
1
1
1
-1
-1
(1)
1
1
16

You might also like