Zonal Cavity Ratio Method PDF
Zonal Cavity Ratio Method PDF
Ceiling
hcc
Room Cavity
hrc
Workplane
Floor
5 hcc (L+W)
LxW
5 hrc (L+W)
LxW
5 hfc (L+W)
LxW
Ceiling Cavity
Luminaires
hfc
Floor Cavity
Where:
hcc = distance in feet from luminaire to ceiling
hrc = distance in feet from luminaire to work plane
hfc = distance in feet from work plane to floor
L = length of room, in feet
W = width of room, in feet
An alternate formula for calculating any cavity ratio is:
Cavity Ratio =
10
HOLOPHANE
Step 2: Effective cavity reflectances must be determined for the ceiling cavity
and for the floor cavity. These are located in Table A (see below) under the
applicable combination of cavity ratio and actual reflectance of ceiling, walls
and floor. The effective reflectance values found will then be cc (effective ceiling cavity reflectance) and fc (effective floor cavity reflectance) . Note that if
the luminaire is recessed or surface mounted, or if the floor is the work plane,
the CCR or FCR will be 0 and then the actual reflectance of the ceiling or floor
will also be the effective reflectance.
When the initial illuminance level required is known and the number of fixtures needed to obtain that level is desired, a variation of the standard lumen formula is used.
# of luminaires =
Step 3: With these values of cc, fc, and w (wall reflectance), and knowing
the room cavity ratio (RCR) previously calculated, find the coefficient of utilization in the luminaire coefficient of utilization (CU) table. Note that since the
table is linear, linear interpolations can be made for exact cavity ratios and
reflectance combinations.
maintained
footcandles desired
x area in sq. ft.
lamp/fixture x
lumen/lamp x CU x LLF
The total light loss factor (LLF) consists of three basic factors: lamp lumen
depreciation (LLD), luminaire dirt depreciation (LDD) and ballast factor (BF). If
initial levels are to be found, a multiplier of 1 is used. Light loss factors, along
with the total lamp lumen output, vary with manufacturer and type of lamp or
luminaire and are determined by consulting the manufacturers published data.
The coefficient of utilization found will be for a 20% effective floor cavity
reflectance. Thus, it will be necessary to correct for the previously determined
fc. This is done by multiplying the previously determined CU by the factor
from Table B (pg.12).
Ballast factor (BF) is defined as the ratio between the published lamp lumens and
the lumens delivered by the lamp on the ballast used. Typical HID ballast factors
vary between .9 and .95. Holophane ballasts are designed to have a BF=1.0.
CU final = CU (20% floor) x Multiplier for actual fc. If it is other than 10% or
30%, interpolate or extrapolate and multiply by this factor.
Occasionally, other light loss factors may need to be applied when they are
applicable. Some of these are luminaire ambient temperature, voltage factor
and room surface dirt depreciation.
Table A
Percent effective ceiling or floor cavity reflectance for various reflectance combinations.
% Ceiling
or floor
reflectance
% Wall
reflectance
90
80
70
50
30
10
90
70
50
30
80
70
50
30
70
50
30
70
50
30
70
50
30
10
50
30
10
Cavity ratio
0.2
0.4
0.6
0.8
1.0
89
88
87
87
86
88
86
84
82
80
86
84
80
77
75
85
81
77
73
69
78
77
76
75
74
78
76
75
73
72
77
74
71
69
67
76
72
68
65
62
68
67
65
64
62
67
65
63
60
58
66
63
59
56
53
49
48
47
47
46
48
47
45
44
43
47
45
43
40
38
30
30
30
30
30
29
29
28
28
27
29
28
26
25
24
28
26
25
23
22
10
11
11
11
12
10
10
10
10
10
09
09
08
08
08
1.2
1.4
1.6
1.8
2.0
85
85
84
83
83
78
77
75
73
72
72
69
67
64
62
66
62
59
56
53
73
72
71
70
69
70
68
67
66
64
64
62
60
58
56
58
55
53
50
48
61
60
59
58
56
57
55
53
51
49
50
47
45
42
40
45
45
44
43
43
41
40
39
38
37
36
35
33
31
30
30
30
29
29
29
27
26
25
25
24
23
22
22
21
20
21
19
18
17
16
12
12
12
13
13
10
10
09
09
09
07
07
07
06
06
2.2
2.4
2.6
2.8
3.0
82
82
81
81
80
70
69
67
66
64
59
58
56
54
52
50
48
46
44
42
68
67
66
65
65
63
61
60
59
58
54
52
50
48
47
45
43
41
39
37
55
54
54
53
52
48
46
45
43
42
38
37
35
33
32
42
42
41
41
40
36
35
34
33
32
29
27
26
25
24
29
29
29
29
29
24
24
23
23
22
19
19
18
17
17
15
14
14
13
12
13
13
13
13
13
09
09
09
09
09
06
06
06
05
05
3.2
3.4
3.6
3.8
4.0
79
79
78
78
77
63
62
61
60
58
50
48
47
45
44
40
38
36
35
33
65
64
63
62
61
57
56
54
53
53
45
44
43
41
40
35
34
32
31
30
51
50
49
49
48
40
39
38
37
36
31
29
28
27
26
39
39
39
38
38
31
30
29
29
28
23
22
21
21
20
29
29
29
28
28
22
22
21
21
21
16
16
15
15
14
12
11
10
10
09
13
13
13
14
14
09
09
09
09
09
05
05
04
04
04
4.2
4.4
4.6
4.8
5.0
77
76
76
75
75
57
56
55
54
53
43
42
40
39
38
32
31
30
28
28
60
60
59
58
58
52
51
50
49
48
39
38
37
36
35
29
28
27
26
25
47
46
45
45
44
35
34
33
32
31
25
24
24
23
22
37
37
36
36
35
28
27
26
26
25
20
19
18
18
17
28
28
28
28
28
20
20
20
20
19
14
14
13
13
13
09
09
08
08
08
14
14
14
14
14
09
08
08
08
08
04
04
04
04
04
11
80
70
50
70
30
10
70
50
30
10
50
30
10
50
30
10
50
30
10
1.070
1.057
1.048
1.040
1.034
1.030
1.026
1.024
1.022
1.020
1.064
1.048
1.037
1.029
1.024
1.020
1.017
1.015
1.014
1.012
1.059
1.039
1.028
1.021
1.015
1.012
l.009
1.007
1.006
1.005
1.049
1.041
1.034
1.030
1.027
1.024
1.022
1.020
1.019
1.017
1.044
1.033
1.027
1.022
1.018
1.015
1.013
1.012
1.011
1.010
1.040
1.027
1.020
1.015
1.012
l.009
1.007
1.006
1.005
1.004
1.028
1.026
1.024
1.022
1.020
1.019
1.018
1.017
1.016
1.015
1.026
1.021
1.017
1.015
1.013
1.012
1.010
1.009
1.009
1.009
1.023
1.017
1.012
1.010
1.008
1.006
1.005
1.004
1.004
1.003
.939
.949
.957
.963
.968
.972
.975
.977
.979
.981
.943
.957
.966
.973
.978
.982
.985
.987
.989
.990
.948
.963
.973
.980
.985
.989
.991
.993
.994
.995
.956
.962
.967
.972
.975
.977
.979
.981
.983
.984
.960
.968
.975
.980
.983
.985
.987
.988
.990
.991
.963
.974
.981
.986
.989
.992
.994
.995
.996
.997
.973
.976
.978
.980
.981
.982
.983
.984
.985
.986
.976
.980
.983
.986
.988
.989
.990
.991
.992
.993
.979
.985
.988
.991
.993
.995
.996
.997
.998
.998
50
30
10
1.012
1.013
1.014
1.014
1.014
1.014
1.014
1.013
1.013
1.013
1.010
1.010
1.009
1.009
1.009
1.008
1.008
1.007
1.007
1.007
1.008
1.006
1.005
1.004
1.004
1.003
1.003
1.003
1.002
1.002
.989
.988
.988
.987
.987
.987
.987
.987
.988
.988
.991
.991
.992
.992
.992
.993
.993
.994
.994
.994
.993
.995
.996
.996
.997
.997
.998
.998
.999
.999
For 30 per cent effective floor cavity reflectance (20 per cent = 1.00)
Room cavity
ratio
1
2
3
4
5
6
7
8
9
10
1.092
1.079
1.070
1.062
1.056
1.052
1.047
1.044
1.040
1.037
1.082
1.066
1.054
1.045
1 038
1.033
1.029
1.026
1.024
1.022
1.075
1.055
1 042
1.033
1.026
1.021
1.018
1.015
1.014
1.012
1.068
1.047
1.033
1.024
1.018
1.014
1.011
1.009
1.007
1.006
1.077
1.068
1.061
1.055
1.050
1.047
1.043
1.040
1.037
1.034
For 10 per cent effective floor cavity reflectance (20 per cent=1.00)
Room cavity
ratio
1
2
3
4
5
6
7
8
9
10
.923
.931
.939
.944
.949
.953
.957
.960
.963
.965
.929
.942
.951
.958
.964
.969
.973
.976
.978
.980
.935
.950
.961
.969
.976
.980
.983
.986
.987
.965
.940
.958
.969
.978
.983
.986
.991
.993
.994
.980
.933
.940
.945
.950
.954
.958
.961
.963
.965
.967
Example:
A typical lecture hall is 60' long and 30' wide with a
14 ceiling height. Reflectances are: ceiling 80%, walls
30%, floor 10%. Four-lamp Prismawrap (coefficients
of utilization shown below) is to be used on 4' stems,
and the work plane is 2' above the floor. Find the
illuminance level if there are 18 luminaires in the room.
Solutions:
(1) Calculate cavity ratios as follows:
CCR = 5(4)(30+60) = 1.0
30 x 60
RCR = 5(8)(30+60) = 2.0
30 x 60
FCR = 5(2) (30+60) = 0.5
30 x 60
(2) In Table A, look up effective cavity reflectances for
these ceiling and floor cavities. cc for the ceiling cavity
is determined to be 62%, while fc for the floor cavity
is 10%.
RCR
50%
.70
.63
.56
.51
.46
.41
.37
.34
.30
.27
.25
50%
30%
.70
.61
.54
.47
.42
.37
.33
.29
.26
.23
.20
10%
.70
.59
.51
.44
.39
.34
.30
.26
.23
.20
.17
50%
.66
.59
.53
.48
.44
.39
.36
.32
.29
.26
.24
FC initial =
# of fixtures x lamps/fixture
x lumens/lamp x CU
area
FC initial =
18 x 4 x 3150 x .53
60 x 30
FC initial = 67
Check spacing of luminaires.
A possible arrangement for these fixtures is three
columns of six fixtures spaced ten feet on center in
each direction. The Spacing Criterion is 1.4, making the
maximum allowable spacing 11.2 feet. The actual
spacing is less than the maximum allowable spacing.
Therefore, the illumination on the work plane should be
uniform.
30%
30%
.66
.58
.51
.45
.40
.36
.32
.28
.25
.22
.20
10%
.66
.56
.49
.43
.38
.33
.29
.25
.22
.19
.17
50%
.62
.56
.50
.46
.41
.37
.34
.31
.28
.25
.23
10%
30%
.62
.55
.48
.43
.39
.34
.31
.27
.24
.21
.19
10%
.62
.53
.47
.41
.36
.32
.28
.25
.22
.19
.16
12
HOLOPHANE