Hvac Interview Questions and Answers
Hvac Interview Questions and Answers
Hvac Interview Questions and Answers
ANSWERS
Q1) What is the Unit of Heat?(1M)
ANS) Units: BTU (British Thermal Units)
1BTU: It is the amount of energy required to raise 1 Degree
Fahrenheit
temperature of 1 Pound of water
(OR)
It is the amount of heat when added to 1 Pound of water
increases the temperature of water to 1 Degree Fahrenheit
1 Lb = 0.45 Kgs (or) 1kg = 2.2 Lbs.
Types of Heat:Sensible Heat: It can be sensed or measured by an ordinary dry
bulb thermometer.
Eg: Human body temperature can be measured using thermometer
Latent Heat: It cant be sensed or measured by an ordinary dry
bulb thermometer. It is a hidden heat. Latent heat
is
absorbed or released when ever there is a change
in
phase.
Eg: When the water becomes vapor and vice versa
(1M)
ANS) 24 Degree Celcius or 76 Degree Fahreinheit
Q6) How much Fresh Air do you provide in a Bedroom?(2M)
Q11) Calculate Hood Size,Exhaust Air CFM,Exhaust Air Duct Size, Fresh Air CFM & Fresh Air
Duct Size(25M)?
ANS) EXAMPLE PROBLEM ON KITCHEN VENTILATION SYSTEM:Q) Length of the stove = 750mm
Width of the stove = 500mm
Height between stove and Hood = 800mm
Find (a):Hood Size (b): Exhaust Air CFM
(c): Exhaust Air Duct Size (d): Fresh Air CFM
(e): Fresh Air Duct Size
For a wall Type hood and medium cooking?
Solution:- (a): Hood Size:
L = l + 0.8H
= 0.75 + 0.8(0.8)
= 1.39M
M x 3.28 = FT
1.39 x 3.28 = 4.55FT
W = w + 0.8H
= 0.5 + 0.8(0.8)
= 1.14M
M x 3.28 = FT
1.14 x 3.28 = 3.73FT
Therefore Hood Size: L = 4.55Ft and W = 3.73Ft
(b):- Exhaust Air CFM:
CFM = P x 150
Where P = 2L + W for wall type of Hood
Therefore P = 2(4.55) + 3.73
= 12.83
Exhaust Air CFM = P x 150
= 12.83 x 150
= 1925CFM
(c): Exhaust Air Duct Size: Q = A x V
1925 = A x 1800
A = 1925/1800
= 1.06 Sq.Ft (Area of the Duct)
Sqft x 0.093 = Sq.M
1.06 x 0.093 = 0.098Sq.M
(1):- Round Duct: Area = Pi x D2/4
0.098 = 3.14 x D2/4
Therefore Diameter D = Under Root of (0.098 x 4)/3.14
= 0.35M
= 350mm
(2):- Square Duct: Area = 0.098
Therefore Under Root of Area = Under Root of 0.098
= 0.30M
= 300mm
Hence the Width and Height of Square duct is 300 x 300mm
(3):- Rectangular Duct: Area = W x H
0.098 = W x 0.3
W = 0.098/0.3
= 0.32M
~ 350mm
Hence the Width and Height of Rectangular duct is 350 x 300mm
(d): Fresh Air CFM = Exhaust Air CFM x 0.8
= 1925 x 0.8
= 1540CFM
(e): Fresh Air Duct Size: Q = A x V
1540 = A x 1800
A = 1540/1800
= 0.855 Sq.Ft (Area of the Duct)
Sqft x 0.093 = Sq.M
0.855 x 0.093 = 0.08Sq.M
(1):- Round Duct: Area = Pi x D2/4
0.08 = 3.14 x D2/4
Therefore Diameter D = Under Root of (0.08 x 4)/3.14
= 0.319M
= 350mm
(2):- Square Duct: Area = 0.08
Therefore Under Root of Area = Under Root of 0.08
= 0.28M
= 300mm
Hence the Width and Height of Square duct is 300 x 300mm
(3):- Rectangular Duct: Area = W x H
0.08 = W x 0.25
W = 0.08/0.25
= 0.32M
~ 350mm
Hence the Width and Height of Rectangular duct is 350 x 300mm
Q12) How do you calculate CFM for Toilets?(2M)
ANS) CFM = M3 x A.C.H/ 1.7
Q13) To select a fan in Commercial Toilets, what are the things that
are required?(2M)
ANS) 1) Volume of Air and 2) Static Pressure
Q14) Difference between Axial and Centrifugal Fans
ANS) Axial Fan: Has the Parallel Movement of Air. Centrifugal Fan: Has the Perpendicular
Movement of Air
Q15) Explain Vapour Compression Cycle?
Q23) What are the things we have in Indoor unit & Outdoor Unit
ANS) Indoor Unit: Evaporator Coils and Blower Fan
OutDoor Unit: Compressor, Condensor, Expansion Valve and Axial Fan
Q24) Which units consume power
ANS) COMPRESSOR, AXIAL FAN & BLOWER FAN
Q25) What is the advantage if I use VAC instead of VCC?
ANS) Power Consumption on the daily basis will be lowered down
Q26) What are the ASHRAE Recommendations for Pipe Designing?
ANS) Maximum Velocity is 4 FPS & Maximum Head Loss is 4 FT/100FT
Q27) Formula for GPM
ANS) GPM = Ton x 12000/ 500 x Delta T
Q33) Name the types of insulation used for ducting & why do we use
insulation.
ANS) Fibre Glass Insulation, Rubber Insulation and Canvas Type Insulation.
Insulation for the ducts is used to protect the Duct from the Outside Conditions so that the Outsid
Q34) Name the different types of material used for duct fabrication.
ANS) GI Duct, Aluminium Sheet Metal, Fibre Glass Duct, Thick Black Mild Steel, Galvanized
Steel Sheet & PUF