Professional Documents
Culture Documents
Tyco Alarm Valve PDF
Tyco Alarm Valve PDF
Email: techserv@tycofp.com
1
11
11
5
5
10
6
10
7
8 9 13
CLAPPER
ASSEMBLY 6 10
2-1/2 INCH 7 4
VALVE
8
CLAPPER
ASSEMBLY 2
3
4, 6, & 8 INCH
VALVES 12
The 2-1/2 Inch (DN65) Valves with NPT threaded ports have a 1-1/4 inch main drain connection. The 2-1/2 Inch (DN65) Valves with
ISO threaded ports have a DN40 main drain connection.
The 4, 6, and 8 Inch (DN100. DN150, and DN200) Valves with NPT threaded ports have a 2 inch main drain connection. The 4, 6,
and 8 Inch (DN100. DN150, and DN200) Valves with ISO threaded ports have a DN50 inch main drain connection.
FIGURE 1
2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200) MODEL AV-1-300 ALARM CHECK VALVE
ASSEMBLY
TFP910
Page 3 of 22
)
6
100
150
2.0 DN
(DN
(DN
H(
INC
0)
CH
CH
20
0,10
N
4 IN
6 IN
/2
(D
0,09
2-1
H
0,08
NC
0,07
8I
1.0
0.9 0,06
0.8
0.7 0,05
100 200 300 400 500 700 1000 2000 3000 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
The approximate friction loss, based on the Hazen and Williams formula and expressed in equivalent length of pipe
with C=120, is as follows
14 feet of 2-1/2 inch Sch. 40 pipe for the 2-1/2 inch AV-1-300 Valve calculated on a typical flow rate of 250 GPM.
23 feet of 4 inch Sch. 40 pipe for the 4 inch AV-1-300 Valve calculated on a typical flow rate of 600 GPM.
24 feet of 6 inch Sch. 40 pipe for the 6 inch AV-1-300 Valve calculated on a typical flow rate of 1500 GPM.
23 feet of 8 inch Sch. 30 pipe for the 8 inch AV-1-300 Valve calculated on a typical flow rate of 2500 GPM.
GRAPH A
2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200) MODEL AV-1-300 ALARM CHECK VALVE
NOMINAL PRESSURE LOSS VERSUS FLOW
Qty. N
Number of
Bolt Holes
TABLE A
FLANGE DRILLING SPECIFICATIONS
TFP910
Page 4 of 22
Technical WATERFLOW
PRESSURE
Data ALARM SWITCH
ONCE RETARD
CHAMBER OVERFLOWS,
Approvals WATERFLOW PRESSURE
UL and C-UL Listed, as well as FM ALARM SWITCH AND
WATER MOTOR
Approved RETARD
ALARM ACTUATE
CHAMBER UPON SPRINKLER
Working Water Pressure Range WATERFLOW FLOW, WATERWAY
TO WATER CLAPPER OPENS
20 to 300 psi (1,4 to 20,7 bar)
MOTOR ALARM WATERFLOW
TO SYSTEM
Friction Loss 7/32"
Refer to Graph A. (5,6 mm) SYSTEM
ORIFICE PRESSURE
INLET
Physical Characteristics RESTRICTION GAUGE
The body is ductile iron, the hand-hole ASSEMBLY
cover is ductile iron, and the seat ring 1/8"
is bronze. The clapper for the 2-1/2 (3,2 mm)
inch (DN65) valve size is stainless ORIFICE SUPPLY
steel. The clapper for the larger valve OUTLET PRESSURE
sizes is ductile iron. All valve sizes uti- GAUGE
lize an EPDM clapper facing.
WHEN FLOW THROUGH
Flanged connections are available RESTRICTION ASSEMBLY
drilled per ANSI, ISO, AS, and JIS INLET EXCEEDS OUTLET, MAIN ALARM
specifications as detailed in Table A. RETARD CHAMBER DRAIN CHECK
BEGINS TO FILL VALVE WATERFLOW VALVE
Threaded port connections for the AV- THROUGH SEAT
1-300 Valves are available NPT thread- RING GROOVE AND
ed or threaded per ISO 7/1 as detailed ALARM PORT
in the Ordering Procedure section.
Valves with NPT threaded ports will FIGURE 2
readily accept the trim arrangements 2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200)
detailed in Figures 4 through 6. MODEL AV-1-300 ALARM CHECK VALVE
OPERATION
Operation
When the fire protection system is in
itially pressurized, water flows into SCREEN
the system until the water supply and
system pressure become equalized,
and the torsion Spring closes the Wa- INLET RESTRICTION
terway Clapper in the Alarm Check WITH 0.219" (5.6 mm)
Valve. Once the pressures stabilize, ORIFICE
the Alarm Check Valve is in service
and the centrally located groove in
the Seat Ring is sealed. Consequent- DRAIN RESTRICTION
ly, with the Alarm Check Valve set for WITH 0.125" (3.2 mm)
service, there is no flow through the ORIFICE
alarm port to the alarm devices (that
is, water motor alarm and/or pressure
alarm switch). FIGURE 3
RESTRICTION ASSEMBLY
When there is a steady flow of wa- (Provided with Alarm Check Valve Trim)
ter into the sprinkler system due to
a sprinkler operation, the Waterway
Clapper opens as shown in Figure 2.
Water is then permitted to flow into way Clapper remains open. Water in A transient surge in supply pressure
the centrally located groove in the the alarm lines will automatically drain that is sufficient only to open the Wa-
Seat Ring and out through the alarm out through the 1/8 inch (3,2 mm) terway Clapper momentarily will not
port towards the Restriction Assembly Drain Orifice in the Restriction As- cause a false alarm, and a portion
(Figure 3). When the flow through the sembly (Figure 3) when the Waterway of the increase in pressure will be
Inlet Restriction of the Restriction As- Clapper closes (due to a discontinua- trapped within the system, thus re-
sembly exceeds the flow through the tion in the flow of water into the sprin- ducing the possibility of another open-
Outlet Restriction, the Retard Cham- kler system). ing. Any water in the alarm line is au-
ber (where provided for systems with tomatically drained, further reducing
For variable pressure systems, slow
variable pressure), begins to fill. the possibility of a false alarm due to
as well as small transient increases in
Subsequently, the Water Motor alarm a successive transient surge in supply
water supply pressure may continue to
and/or the pressure alarm switch will pressure.
build up in the system (via the Bypass
be actuated. The alarms will continue Check Valve) without opening the Wa-
to be actuated as long as the Water- terway Clapper.
TFP910
Page 5 of 22
FIGURE 4 PART 1 OF 3
VERTICAL CLOSED DRAIN TRIM STANDARD ORDER
FOR 2-1/2 INCH (DN65) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-050)
TFP910
Page 7 of 22
SEPARATELY LOCATION 22
20
(FOR VARIABLE FOR OPTIONAL H 11 17 D
PRESSURE ELECTRICALLY 12 13
SYSTEMS) 20
SUPERVISED 3 20
N.O. ALARM
22
A 10
CONTROL 24
20 21
VALVE L B
6 11
7
RESTRICTION 19 29 MODEL AV-1
ASSEMBLY,
C MAIN ALARM VALVE,
M DRAIN VALVE 6 INCH (DN150)
SEE FIGURE 3
(NORMALLY FLANGE x FLANGE
10 N 29 CLOSED) SHOWN
16
11 2 INCH NPT
19 19 3 20 K CONNECTION
TO DRAIN
FIGURE 4 PART 2 OF 3
VERTICAL CLOSED DRAIN TRIM STANDARD ORDER SEMI-PREASSEMBLED
FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-951)
TFP910
Page 8 of 22
FIGURE 4 PART 3 OF 3
VERTICAL CLOSED DRAIN TRIM STANDARD ORDER SEMI-PREASSEMBLED
FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-952)
TFP910
Page 9 of 22
FIGURE 5 PART 1 OF 3
VERTICAL OPEN DRAIN TRIM SPECIAL ORDER
FOR 2-1/2 INCH (DN65) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-053)
TFP910
Page 10 of 22
SEPARATELY LOCATION 24
22
(FOR VARIABLE FOR OPTIONAL H 14 19 D
PRESSURE ELECTRICALLY 15 16
SYSTEMS) 22
SUPERVISED 3 22
18
N.O. ALARM 21 A 13
CONTROL 26
22 21 23
VALVE
6 8 B
7 14
RESTRICTION 10 31 MODEL AV-1
ASSEMBLY,
C MAIN ALARM VALVE,
9 DRAIN VALVE 6 INCH (DN150)
SEE FIGURE 3
K (NORMALLY FLANGE x FLANGE
DRIP CLOSED) SHOWN
FUNNEL
1-1/4 INCH NPT
CONNECTION 2 INCH NPT
TO DRAIN CONNECTION
TO DRAIN
FIGURE 5 PART 2 OF 3
VERTICAL OPEN DRAIN TRIM SPECIAL ORDER SEMI-PREASSEMBLED
FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-954)
TFP910
Page 11 of 22
FIGURE 5 PART 3 OF 3
VERTICAL OPEN DRAIN TRIM SPECIAL ORDER SEMI-PREASSEMBLED
FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-955)
TFP910
Page 12 of 22
FIGURE 6 PART 1 OF 2
HORIZONTAL CLOSED DRAIN TRIM SPECIAL ORDER
FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-057)
TFP910
Page 13 of 22
5
1/2 INCH NPT
CONNECTION 22
FOR WATERFLOW
PRESSURE
ALARM 12
SWITCH ALARM
20 TEST VALVE
(NORMALLY
3/4 INCH NPT 10 CLOSED)
CONNECTION
FOR WATER 22
MOTOR 14
ALARM 31
MODEL AV-1
13 ALARM VALVE,
23
LOCATION 8 INCH (DN200)
FOR OPTIONAL RESTRICTION FLANGE x
ELECTRICALLY ASSEMBLY, MAIN GROOVE
SUPERVISED SEE FIGURE 3 DRAIN VALVE 8 SHOWN
N.O. ALARM (NORMALLY
CONTROL 19 24 CLOSED) 30
VALVE 7 20 21
17
19
10
19 6 19
12 19 2 INCH NPT
3
12 CONNECTION
TO DRAIN
FIGURE 6 PART 2 OF 2
HORIZONTAL CLOSED DRAIN TRIM SPECIAL ORDER
FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES (52-204-2-058)
TFP910
Page 14 of 22
ELEVATION VIEW
ELEVATION VIEW
FIGURE 7 PART 1 OF 3
INSTALLATION DIMENSIONS
FOR 2-1/2 INCH (DN65) MODEL AV-1-300 ALARM CHECK VALVES
TFP910
Page 15 of 22
ELEVATION VIEW
ELEVATION VIEW
FIGURE 7 PART 2 OF 3
INSTALLATION DIMENSIONS
FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES
TFP910
Page 16 of 22
G
ELEVATION VIEW
G
ELEVATION VIEW
RC-1
FIGURE 7 PART 3 OF 3
INSTALLATION DIMENSIONS
FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES
TFP910
Page 17 of 22
Step 5. Slowly open the main control Protection Association (for example,
NO. DESCRIPTION QTY. P/N
valve until the sound of flowing water NFPA 25), in addition to the standards
1 3/4" x 1/4" Hex just begins and then open the valve of any authority having jurisdiction.
Bushing . . . . . . . . . 1 CH one more turn. Contact the installing contractor or
2 3/32" Vent product manufacturer regarding any
Fitting . . . . . . . . . . 1 92-032-1-002 Step 6. Close the remote branch line
questions.
3 1/4" x 5'-0" vent connection after the discharge of
Tubing . . . . . . . . . . 1 CH aerated water ceases, and the outlet Automatic sprinkler systems are rec-
has flowed full for at least 15 seconds. ommended to be inspected, tested,
PRESSURE and maintained by a qualified Inspec-
Step 7. Fully open the main control tion Service in accordance with local
SWITCH valve. requirements and/or national codes.
Step 8. Open the end-of-line Inspec The Tyco Model AV-1-300 Alarm
1 tors Test Connection (or Alarm Test Check Valves do not require any reg-
3 Valve, if acceptable to the authority ularly scheduled maintenance. It is
(ROUTE TO having jurisdiction) and verify that the recommended, however, that proper
DRAIN) system alarms operate. operation of the alarms be periodically
2 Step 9. Close the end-of-line Inspec verified in accordance with a proce-
MODEL RC-1 (GREEN tors Test Connection (or Alarm Test dure that is acceptable to the author-
RETARD TINT) Valve). ity having jurisdiction. Any impairment
CHAMBER must be immediately corrected.
Step 10. Verify that water ceases to
Trim kit is ordered separately when a
flow from the alarm line drain. If water Inspection Procedure
continues to flow, follow the corrective It is recommended that the following
Water Motor Alarm (P/N 52-201-2-012)
procedure described in the Care and inspection procedure be performed at
is not installed. Maintenance section. least quarterly by a qualified Inspec
The Restriction Assembly has a 1/8 tion Service.
FIGURE 8 inch (3,2 mm) diameter drain orifice. Step 1. Notify the proper authorities
ALARM VENT TRIM KIT Sufficient time must be allowed for and all personnel who may be affected
drainage of the Retard Chamber and that an alarm test is to be performed.
the piping to the water motor alarm.
Step 2. Open the end-of-line Inspec
Setting Step 11. After verification that the flow
of water out of the alarm line drain has
tors Test Connection (or Alarm Test
Valve, if acceptable to the authority
Procedure stopped, the alarm valve is set and is
ready for service.
having jurisdiction) and verify that the
system alarms operate in accordance
Steps 1 through 11 are to be per
formed when initially setting the Mod- with the requirements of the authority
el AV-1-300 Alarm Check Valve or af-
ter system operation due to a fire.
Care and having jurisdiction. Verify that the wa-
ter motor alarm and/or the pressure
NOTICE
Maintenance alarm switch properly actuate and
within the elapsed time required by
The following procedures and inspec the authority having jurisdiction.
Filling the system with water will result tions should be performed as indi
in operation of the associated alarms. Step 3. Verify that water is flowing out
cated, in addition to any specific of the alarm line drain at a rate consis-
Consequently, notification must first requirements of the NFPA. Any impair-
be given to the owner and fire depart tent with the 1/8 inch (3,2 mm) diame
ment must be immediately corrected. ter drain orifice in the Restriction As
ment, central station, or other sig-
nal station to which the alarms are sembly.
NOTICE
connected. Step 4. Close the end-of-line Inspec
Performing the care and maintenance tors Test Connection (or Alarm Test
Notify the proper authorities and all procedures will result in operation of
personnel who may be affected that Valve).
the associated alarms. Consequently,
an alarm test is to be performed. notification must first be given to the Step 5. Verify that water ceases to
After placing a fire protection system owner and fire department, central flow from the alarm line drain.
in service, notify the proper authorities station, or other signal station to which Step 6. Clean the 1/2 inch Strainer (lo-
and advise those responsible for mon- the alarms are connected. cated in the valve trim) as well as the
itoring proprietary and/or central sta- Before closing a fire protection system 3/4 inch Strainer (located at the con-
tion alarms. main control valve for maintenance nection to the water motor alarm, as
Step 1. Open the 1/4 inch Gauge Test work on the fire protection system that applicable). Be sure to replace the
Valves for the Supply and System it controls, obtain permission to shut strainer baskets and tighten the caps
Pressure Gauges. down the affected fire protection sys- securely.
tem from the proper authorities and
Step 2. Check to see that the Hand- notify all personnel who may be af- NOTICE
hole Cover bolts are tight. If not, cross- fected by this decision.
tighten them. Cleaning of the Strainers after each
Responsibility lies with the owner for operation of the alarms is especially
Step 3. Close the Alarm Test Valve. the inspection, testing, and mainte- important in the case of water sup-
Step 4. Open the remote cross main nance of their fire protection system plies (such as lakes and rivers) having
or branch line vent connection. (Refer and devices in compliance with this a large quantity of suspended mat-
to Step 7 in the Installation section.) document, as well as with the appli- ter. A clogged alarm line can prevent
cable standards of the National Fire operation of the alarms.
TFP910
Page 18 of 22
Step 7. Notify all authorities responsi While holding the Spring down by the NOTICE
ble for monitoring the installation that coils, remove the Hinge Pin. Remove
the fire protection system has been re- the Spring and Waterway Clapper For variable pressure systems, loss of
turned to service. Assembly. excess system pressure will increase
the likelihood of a false alarm.
Sprinkler System Drain-Down Step 7. Using a light, check for and
Follow the procedure indicated be-
Draining the sprinkler system must be remove any debris that may have be
come lodged within the Seat Ring low to correct a loss of excess system
done in accordance with the following
groove. Inspect the Seat Ring seat for pressure condition.
procedure:
any damage. If the Seat Ring has be Step 1. Check for signs of continued
Step 1. Close the main control valve, if come dented across the seat then the leakage from the alarm line drain. If
this has not already been done. Alarm Check Valve will have to be re- rust stains and/or water deposits indi
Step 2. Open the remote cross main placed. It is impractical to re-face a cate that continued leakage has been
or branch line vent connection. (Refer Seat Ring in the field. taking place, take corrective action
to Step 7 in the Installation section.) Step 8. Check for and remove any de- according to the procedure described
Step 3. Open the Main Drain Valve. bris that may have become lodged in in the sub-section entitled Leakage
Check first to see that the drainage the Clapper Facing. If a minor imper from Alarm Line Drain.
water discharge will not cause dam- fection remains in the Clapper Fac- Step 2. If there are no signs of contin
age or result in dangerous conditions. ing, then turn it over after thoroughly ued leakage from the alarm line drain,
cleaning both surfaces with a clean close the main control valve, slowly
Step 4. Wait until the Supply Pressure cloth. Replace the Clapper Facing if
Gauge reads zero pressure and the remove the plug from the supply pres
necessary. Be sure to securely re- sure gauge test valve to relieve the
sound of draining water has stopped tighten the retaining fastener for the
before performing any maintenance supply pressure, and then slowly open
Clapper Washer. the union in the externally mounted
work on the fire protection system.
Step 9. Replace the Spring and Wa- bypass.
Leakage from Alarm Line terway Clapper Assembly as shown in Check for leakage past the Bypass
Drain Figure 1. While holding the coils of the Check Valve. If there is leakage, debris
Follow the steps indicated below un- Spring down, re-insert the Hinge Pin. may have become lodged between its
til water ceases to flow from the alarm Be sure that the Hinge Pin is pushed clapper and seat. Drain the system in
line drain. Check for the discontinua- all the way to the rear of the valve. accordance with the prescribed pro-
tion of the leakage after each step is cedure and then clean or replace the
complete. Step 10. Replace the Handhole Cover.
Return the Alarm Valve to operation in Bypass Check Valve as required.
Step 1. Open the Main Drain Valve. accordance with the steps described Re-assemble the externally mount-
Let the water flow for about 5 sec- in the Setting Procedure section. ed bypass, replace the plug into the
onds and then close the Main Drain Gauge Test Valve, and return the fire
Valve. This should flush any loose de- Clogged Alarm Line Drain protection system to operation in ac
bris that may have become trapped If water either does not flow or only
cordance with the steps described in
between the Clapper Facing and the dribbles out of the alarm line drain
the Operation section.
Seat Ring or in the seating area of the during an alarm test, then it is likely
Drain Valve. that the screen protecting the Restric Step 3. If there are no signs of leak-
tion Assembly drain orifice (Ref. Fig age past either the Alarm Check Valve
Step 2. Repeat Step 1 if the rate of ure 3) has become clogged. Clapper per Step 1 or the Bypass
continued flow out of the drain was Check Valve per Step 2, inspect the
noticeably reduced. NOTICE sprinkler system for leakage.
Step 3. Open the Alarm Test Valve For variable pressure systems, a Excess Pressure Due To
and allow water to flow for about 5 clogged alarm line drain will increase
seconds before re-closing the valve. Thermal Expansion
the likelihood of a false alarm. Wet pipe sprinkler systems subject
This should flush any loose debris that
may have become trapped in the seat First break the union downstream of to ambient temperatures in excess of
ing area of the Alarm Test Valve. the Drain Restriction and remove the 100F/38C can experience significant
Drain Restriction for cleaning by back- increases in system pressure due to
Step 4. Repeat Step 3 if the rate of flushing the screen. Re-install the the thermal expansion of the water. In
continued flow out of the drain was Drain Restriction and re-assemble the particular, a gridded wet-pipe system
noticeably reduced. drain line. with a relatively small air pocket and
Step 5. Determine whether the water no relief valve can be subjected to an
Loss of Excess System increase of more than 100 psi (6,9 bar),
is flowing from the Alarm Port (Figure
1) or past the Alarm Test Valve. If the Pressure due to an increase in ambient temper-
leakage is past the Alarm Test Valve, For variable pressure systems, the ature of approximately 50F/28C.
close the main control valve, and then System Pressure Gauge normally in-
dicates a pressure greater than that As necessary, install a pressure relief
repair or replace the Alarm Test Valve valve, in accordance with the require-
as necessary. shown by the Supply Pressure Gauge.
Also, the value should be close to that ments of the authority having jurisdic-
Step 6. If it appears that the leakage of the peak supply pressure that has tion, to automatically relieve the ex-
noted in Step 5 is from the Alarm Port, occurred after the system was placed cess pressure that could otherwise be
drain the system in accordance with in service. created in wet-pipe systems exposed
the prescribed procedure. After the to significant increases in ambient
system has been drained, remove the temperature.
Handhole Cover.
TFP910
Page 19 of 22
False Alarms
Follow the step below when repeated Limited
false alarms occur in a variable pres-
sure system. Warranty
Products manufactured by Tyco Fire
Step 1. Check for and correct the
Suppression & Building Products
cause of continued leakage out the
(TFSBP) are warranted solely to the
alarm line drain.
original Buyer for ten (10) years against
Step 2. Check for and clean a clogged defects in material and workmanship
alarm line drain. when paid for and properly installed
Step 3. Check for and correct the and maintained under normal use and
cause of a loss in excess system pres service. This warranty will expire ten
sure. (10) years from date of shipment by
TFSBP. No warranty is given for prod-
Step 4. Drain the sprinkler system and ucts or components manufactured by
re-fill it using the steps described in companies not affiliated by ownership
the Setting Procedure section. with TFSBP or for products and com-
ponents which have been subject to
Intermittent Alarms misuse, improper installation, corro-
If the pressure alarm switch gives a sion, or which have not been installed,
steady signal, but the water motor maintained, modified or repaired in
generates an intermittent alarm, check accordance with applicable Standards
for binding in the water motor alarm of the National Fire Protection Associ-
drive shaft. ation, and/or the standards of any oth-
If the water motor alarm and/or the er Authorities Having Jurisdiction. Ma-
pressure alarm switch provide an in terials found by TFSBP to be defective
termittent alarm, it is likely the conse shall be either repaired or replaced, at
quence of an excessive amount of air TFSBPs sole option. TFSBP neither
being trapped within the sprinkler sys assumes, nor authorizes any person
tem. Drain down the sprinkler system to assume for it, any other obligation
and refill it using the steps described in connection with the sale of prod-
in the Setting Procedure section. ucts or parts of products. TFSBP shall
not be responsible for sprinkler system
A discontinuance of an alarm may also
design errors or inaccurate or incom-
be caused by the Clapper closing due
plete information supplied by Buyer or
to a sudden drop in supply pressure
Buyers representatives.
or the shut-off of a pump in the supply
line. These types of problems can only In no event shall TFSBP be liable, in
be corrected by maintaining a steady contract, tort, strict liability or under
supply pressure. any other legal theory, for inciden-
tal, indirect, special or consequential
damages, including but not limited to
labor charges, regardless of whether
TFSBP was informed about the possi
bility of such damages, and in no
event shall TFSBPs liability exceed an
amount equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex
press or implied, including warranties
of merchantability and fitness for a
particular purpose.
This limited warranty sets forth the ex
clusive remedy for claims based on
failure of or defect in products, materi
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
TFP910
Page 20 of 22
4 Inch Valves with NPT Ports 6 Inch Valves with NPT Ports 8 Inch Valves with NPT Ports
ISO (PN16) Flange x ANSI Flange x ISO (PN10) Flange x
4.50 inch (114,3 mm) 6.50 inch (165,1 mm) 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-1-493 Groove O.D. . . . . . . . . . . P/N 52-203-1-625 Groove O.D. . . . . . . . . . . P/N 52-203-1-896
ISO (PN16) Flange x ISO (PN16) Flange x ISO (PN16) Flange x
ISO (PN16) Flange. . . . . P/N 52-203-4-013 6.62 inch (168,3 mm) 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-1-695 Groove O.D. . . . . . . . . . . P/N 52-203-4-266
AS Flange x
AS Flange. . . . . . . . . . . . P/N 52-203-4-313 ISO (PN16) Flange x ISO (PN10) Flange x
6.50 inch (165,1 mm) ISO (PN10) Flange . . . . . P/N 52-203-4-016
AS Flange x Groove O.D. . . . . . . . . . . P/N 52-203-5-215
4.50 inch (114,3 mm) ISO (PN16) Flange x
Groove O.D. . . . . . . . . . . P/N 52-203-4-413 ISO (PN16) Flange x ISO (PN16) Flange. . . . . .P/N 52-203-4-118
ISO (PN16) Flange. . . . . P/N 52-203-4-015
JIS Flange x AS Flange x
JIS Flange. . . . . . . . . . . . P/N 52-203-4-713 AS Flange x AS Flange. . . . . . . . . . . . P/N 52-203-4-316
AS Flange. . . . . . . . . . . . P/N 52-203-4-315
JIS Flange x AS Flange x
4.50 inch (114,3 mm) AS Flange x 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-813 6.62 inch (168,3 mm) Groove O.D. . . . . . . . . . . P/N 52-203-4-416
Groove O.D. . . . . . . . . . . P/N 52-203-4-415
4 Inch Valves with ISO Ports JIS Flange x
AS Flange x JIS Flange. . . . . . . . . . . . P/N 52-203-1-716
ISO (PN16) Flange x 6.50 inch (165,1 mm)
ISO Flange . . . . . . . . . . . P/N 52-203-4-113 Groove O.D. . . . . . . . . . . P/N 52-203-4-425 JS Flange x 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-816
ISO (PN16) Flange x JIS Flange x
4.50 inch (114,3 mm) JIS Flange. . . . . . . . . . . . P/N 52-203-4-715 8 Inch Valves with ISO Ports
Groove O.D. . . . . . . . . . . P/N 52-203-4-213
JIS Flange x ISO (PN10) Flange x
4.50 inch (114,3 mm) Groove O.D x 6.62 inch (168,3 mm) ISO (PN10) Flange . . . . . P/N 52-203-4-116
4.50 inch (114,3 mm) Groove O.D. . . . . . . . . . . P/N 52-203-4-815
Groove O.D. . . . . . . . . . . P/N 52-203-1-923 ISO (PN16) Flange x
JIS Flange x ISO (PN16) Flange. . . . . .P/N 52-203-4-117
6.50 inch (165,1 mm) ISO (PN10) Flange x
Groove O.D. . . . . . . . . . . P/N 52-203-5-815 8.62 inch (219,1 mm)
6.50 inch (165,1 mm) Groove O.D x Groove O.D. . . . . . . . . . . P/N 52-203-4-216
6.50 inch (165,1 mm) ISO (PN16) Flange x
Groove O.D. . . . . . . . . . . P/N 52-203-1-124 8.62 inch (219,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-226
6 Inch Valves with ISO Ports
8.62 inch (219,1 mm) Groove O.D. x
ISO (PN16) Flange x
8.62 inch (219,1 mm)
ISO (PN16) Flange. . . . . P/N 52-203-4-115
Groove O.D. . . . . . . . . . . P/N 52-203-1-926
ISO (PN16) Flange x
6.62 inch (168,3 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-215
ISO (PN16) Flange x
6.50 inch (165,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-4-225
6.62 inch (168,3 mm) Groove O.D. x
6.62 inch (168,3 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-1-925
6.50 inch (165,1 mm) Groove O.D. x
6.50 inch (165,1 mm)
Groove O.D. . . . . . . . . . . P/N 52-203-1-125
TFP910
Page 22 of 22
2009 TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446