You are on page 1of 2

Panel MCC (motor control center) Common

Data;

1. Rate power ; 0,4kv


2. Rate curent ; 630A
3. Capacity ; 204KW
4. Power 1 dari L103
5. Power 2 dari L202
6. Type panel ; MNS
7. Kode Panel ; G 1-4

No Feeder Code kapasitas Code


Panel cable
1 Panel incoming 1 G101 204 kw GMCCA-
01
2 Panel incoming 2 204 KW GMCCB-
01
3 No 2 power for coal conveying floor G102 32 KW 2YDLX-
power supply box 01
4 No 4 bottom ash cooler 3 KW 4LZQ-01
5 No 2 power for chemical dosing room 24 KW 2JDLX-01
power supply box
6 Belt conveyor PD-3B (EL 34) 37 KW PD3B-01
7 Belt conveyor PD-3A (EL 34) 37 KW PD3A-01
8 No 1 bottom ash cooler G103 3 KW 1LZQ-01
9 No 2 bottom ash cooler 3 KW 2LZQ-01
10 No 3 bottom ash cooler 3 KW 3LZQ-01
11 Power for 20 KV distribution room power 17 KW SDLX-01
supply box
12 Power for comprehensive building for 38 KW 1CCDLX-
ESP no 1 power supply box 01
13 No 1 power for coal conveying floor 32 KW 1YDLX-
power supply box 01
14 No 1 power chemical dosing room power 24 KW 1JDLX-01
supply box
15 Power for comprehensive building for G104 29 KW 2CCDLX-
ESP no 2 power supply box 01
16 Belt conveyor PD-4A (EL 28,5) 15 KW PD4A-01
17 Belt conveyor PD-4B (EL 28,5) 15 KW PD4B-01
18 Circulating water system DCS remote IO 2XDCS-
cabinet 01
19 Belt conveyor ZD-1 (Ash silo EL -2,9) 4 KW 1ZDD-01
20 Belt conveyor ZD-2 (Ash silo EL 14) 4 KW 2ZDD-01
Sec wiring diagram Belt conveyor ZD-1 (Ash silo EL -2,9)

Sec wiring diagram Belt conveyor PD-3A/B (EL 34)

You might also like