You are on page 1of 32

Diagnostic Testing Solutions

for Power Transformers


Prevention is better than cure know more about the condition of yo

Manufacturing Commissioning

Mechanical impacts
>> transportation event
>> post fault event
>> seismic activity event etc.

100 %
transformer condition

Keep your transformer in good co

with testing

testing during manufacturing > periodic testing


factory acceptance testing
commissioning acceptance testing > testing after an event relocation, protection trip or

and subsequent preventive actions

Taking the right action at the right time

Maintain OLTC
>> corroded contacts
>> diverter switch
>> motor & brake

2
our transformer

Operation Replacement

Factors causing deterioration

Aging
>> overloading
>> overheating
>> moisture
Protection problems
>> protection underfunction
>> protection failure

ondition

warning, overcurrent, overvoltage, earthquake ...

transformer life expectancy

Replace parts Processing of insulation


>> bushings >> degassing of fluid
>> surge arresters >> retrofilling
>> gaskets >> drying of transformer
>> pumps, fans, etc. >> passivators or inhibitors

3
Transformer parts and their possible faults

Part

Bushings

Bushing CTs

Insulation materials

Leads

OLTC

Windings

Core

Surge arresters

4
Transformer Dielectric response Frequency response Partial discharge Current transformer
diagnostic set: analysis instrument: analysis instrument: analysis system: testing instrument:
see pages 6-21 see pages 22-23 see pages 24-25 see pages 26-29 see CT Analyzer brochure

Variable frequency power factor /

Frequency response of stray losses


Capacitance, dissipation factor /

Power factor / dissipation factor


power factor at 50 Hz or 60 Hz

Frequency response analysis


Dielectric response analysis

Current transformer analysis


Short circuit impedance /

Partial discharge analysis


DC winding resistance

Watt-loss and current


Dynamic resistance
leakage reactance
Transformer ratio

dissipation factor
Exciting current

measurement
Tip up test
Faults detectable Measurement
Partial breakdown between capacitive graded layers,

cracks in resin-bonded insulation
Aging and moisture
Open or compromised measuring tap connection
Partial discharges in insulation
Loss of oil in an oil-filled bushing
Current ratio or phase error considering burden, excessive residual

magnetism, non-compliance to relevant IEEE or IEC standard
Moisture in solid insulation 1 1
Aging, moisture, contamination of insulation fluids
Partial discharges
Contact problems
Mechanical deformation
Contact problems in tap selector and at diverter switch
Open circuit, shorted turns, or high resistance connections in the OLTC

preventative autotransformer, series autotransformer or series transformer
Contact problems in the DETC
Short circuits between windings or between turns
Strand-to-strand short-circuits
Open circuits in parallel strands
Short circuit to ground
Mechanical deformation
Contact problems, open circuits
Mechanical deformation 2 2
Floating core ground
Shorted core laminates
Deterioration and aging
1) Power factor / dissipation factor measurements at 50 Hz or 60 Hz can detect high moisture contents, but have a blind spot for low moisture contents. Measuring power factor /
5 method to determine moisture in solid insulation is dielectric response analysis. 2) If the
dissipation factor at lower frequencies, such as 15 Hz, improves sensitivity. The most sensitive
core ground can be opened.
All in one: the multi-functional transformer test set CPC 100 + CP TD1

DC winding resistance measurement


instrument
winding resistance
I
RHV RLV
V

TR

Leakage reactance/short-circuit
impedance measurement instrument
mechanical?
I

TR

Frequency response of stray losses


measurement instrument
winding strands
I

TR

Further substation diagnostics:


> Ground impedance measurement
> Line impedance and ground factor
measurement
> Resistance measurement
> Primary relay testing

Output Measurement Precision Weight


12 kV V, I, P, Q, S output signal digitally generated CPC 100:
800 A AC Cp: 1 pF ... 3 F Cp measurement: <0.05 % error CP TD1:
400 ADC dissipation factor / power factor independent from mains quality
16 Hz ... 400 Hz resistance: 0,5 ... 20 k in wave form and frequency

6
Transformer ratio measurement
instrument
NP/NS

VP VS

TR

Transformer exciting current


test instrument
core
I

TR

Power factor / dissipation factor


measurement instrument
I
IR IC
V

Insulation

Further substation diagnostics:


> Current transformer testing
> Voltage transformer testing

of units Power supply High voltage cable Trolley


29 kg / 65 lbs 110 V ... 240 V 20 m / 65 feet to conveniently transport:
26 kg / 56 lbs 50 Hz ... 60 Hz double screen CPC 100,
16 A insulation supervision CP TD1,
measurement cable,
high voltage cable

7
Measuring capacitance & power factor / dissipation factor

Surge arresters Bushings OLTC Leads Insulation materials Windings Core

Capacitance and power factor / dissipation


factor (PF / DF) measurements are performed
to investigate the condition of bushings as well
as the transformer overall insulation. Aging and
decomposition of the insulation, or the ingress of
water, increase the energy that is turned into heat
in the insulation. The level of this dissipation is
measured by the PF / DF.
On surge arresters, currents and watt losses of
identical units can be compared. Deviations may
indicate aging effects, poor contacts or open
circuits between elements.
Damaged TR after bushin

Capacitance values of bushings show if there


have been breakdowns between capacitive Polarization losses Conductive losses
layers. For resin bonded paper bushings, cracks
into which oil has leaked, can also change the
value of the capacitance. Equivalent circuits *)
A rise in capacitance of more than 10 % is
normally considered to be dangerous, since it
indicates that a part of the insulation distance is
already compromised and the dielectric stress to
the remaining insulation is too high.

Preventing bushings from exploding


Typical loss shapes
Increased heat dissipation accelerates the
aging of the insulation. If an aged insulation
can no longer withstand the electrical stress,
bushingsexplode.

Better understanding of losses f f

At line frequency, conductive losses can be


represented with a parallel equivalent circuit. Superposition of both effects
Polarization losses can be represented by a series
equivalent circuit consisting of an ideal capacitor
and a resistor.
Increased losses may pass a test at line frequency
unnoticed, leaving the tester unaware of an
insulation in distress. Measuring the DF / PF
f
over a broad frequency range helps to better
understand both types of losses. Typical loss shapes in 15 Hz ... 400 Hz range

8
How does it work? How can results be confirmed?
High voltage is applied to the insulation to be If values deviate more than indicated by the
tested, i.e. the bushing tip, and a low loss reference standards, then dielectric response analysis can
capacitor (integrated in CPTD1) is connected be performed to check for increased moisture.
in parallel. The currents flowing through the Chemical tests can be performed to verify the
insulation and through the reference capacitor quality of the insulation fluid (DGA, dielectric
are measured and the time difference between breakdown strength, interfacial tension, etc.)
their zero crossings is determined. The loss angle Measuring the power factor / dissipation factor
is then calculated from this time difference. The of the insulation fluid can also be done with a
tangent of this angle is the dissipation factor. The CPC 100 accessory, the CP TC12 oil test cell.
cosine of the angle between voltage and current is
the power factor. Results are compared with values
given in IEEEC57.10.01 and IEC 60137, and can
be compared with a base measurement, another
g explosion phase, or a sister transformer.

Type Insulation Typical new values IEEE C57.10.01 IEC 60137

RIP Resin impregnated paper 0.3 - 0.4 < 0.85 < 0.70

OIP Oil impregnated paper 0.2 - 0.4 < 0.50 < 0.70

RBP Resin bonded paper 0.5 - 0.6 < 2.00 < 1.50
Dissipation factor / power factor in % at 50 / 60 Hz and 20

Capacitive layers in bushings

OIP bushing: PF / DF variable frequency test

center conductor

CI
CJ Grounded layer and tap
electrode on flange

OIP bushing: PF / DF tip up test

9
Measuring capacitance & power factor / dissipation factor

Power factor / dissipation factor (PF / DF) Energize HV to measure CH + CHL | CH | CHL, then energize LV to measure
measurement indicates the condition of the C L + C HL | C L | C HL - thanks to internal switching logic with guard
liquid and solid insulation within a transformer.

Power and accuracy


The CPC 100 / CP TD1 can measure capacitance
and PF / DF (tan) in laboratories, test fields and
on site.
Apowerful test voltage source (12kV, 100mA
continuous, 300mA short-term load current)
with variable frequency (15-400Hz), combined
with high accuracy measuring inputs allows fast,
effective and accurate measurements.
Prepared test procedures can guide the user
through the testing process and offer a basis for
comprehensive reporting.

Modular equipment LV
The modular equipment (CPC100: 29 kg / 65lbs,
CP TD1: 26kg / 56lbs) can be easily transported IN A
thanks to its sturdy cases, which can also be used
to place the instruments onto them for working
at a comfortable height, as shown on page 12.
For convenient transport or mobile use such as CL
in test fields or in substations/power plants, the
instruments can be mounted onto a trolley.
The CPC 100 is used to control the test, i.e.:
>> Entering the voltage and frequency values
>> Where C and cos / tan shall be measured
>> Starting and stopping the test
>> Supervising the measurement progress and
intemediate results
>> Storing results on flash disk and USB memory
stick
The CP TD1 includes
>> A high voltage step-up transformer
>> A reference capacitor (pressurized gas type)
>> The unit to measure and compare currents in
amplitude and phase

Power factor / dissipation factor tip up results

10
Your Benets
> Perfect digitally generated sine wave
test signal that is independent from
power quality and line frequency
> Laboratory precision for on-site use:
<0.05 % error for capacitance Cp
> Portability (CPC 100: 29 kg / 65 lbs,
CPTD1: 26 kg / 56 lbs)
> Mobility through the use of a
specialized trolley
> Ruggedness and ergonomic design:
transport cases with wheels bring
equipment to appropriate working
CHL height (see page12)
HV > Automatic tests at different voltages
> Automatic tests at different frequencies:
early detection of insulation stress due
to the improved sensitivity provided by
measurements made in the range of
15 - 400 Hz
CH > Optional measurement bandwidth
reduction to 5 Hz and averaging
of up to 20 results for precise
measurements despite strong
electromagnetic interference
> Temperature correction according to
type of insulation and relevant standard
> Internal recalibration of electronic
circuits of the CP TD1 with each
measurement
> Automatic reporting of capacitance
Cp,DF (tan , PF (cos ), power
(active, reactive, apparent), impedance
(absolute value, phase, inductivity,
resistance, Q)
> Automatic assessment if reference
values for capacitance and power
factor / dissipation factor are known
> Less wiring effort through two
measurement inputs (IN A, INB) that
can be used to measure for example
Power factor / dissipation factor variable frequency results the capacitance of a bushing at the
same time as the main insulation

11
Measuring ratio & exciting (no-load) current

Surge arresters Bushings OLTC Leads Insulation materials Windings Core


IP
The measurement is performed for assessing
possible winding damage, such as turn-to-turn
short circuits, comparing the measured ratio and
magnetizing currents to specifications, factory
measurement results, and/or acrossphases. VP

In the factory, this measurement is performed to


verify that ratio and the vector group is correct.

V P / V S = N P / NS
Principal test setup

Ratio measurement with the CPC100


The CPC 100 measures the transformer ratio by
applying a high voltage at the HV winding of
one transformer leg. In amplitude and phase, it
measures the applied voltage and the voltage at
the LV winding, as well as the exciting (no-load)
current. The deviation from rated values is
displayed as a percentage.

Measuring ratio per tap


The CPC 100 measures ratio and excitation
current at each tap position. Each time the user
operates the tap changer, the CPC 100 automati-
cally starts a new measurement and measures
and displays ratio, phase angle, and for each tap,
the deviation from nominal ratio is displayed as
a percentage.
For automatically measuring winding resistance
and ratio of all phases and all taps, see page 16.

Setup for automatically measuring ratio and resistance per tap (see page 16)

12
How does it work? How can results be confirmed?
The winding ratio between primary and second- With the turns-ratio test, shorted turns can
ary windings is measured for each transformer bedetected. If a problem is suspected from
leg, applying high voltage at the HV side and a DGA, a dissipation factor test, or a relay trip,
measuring on the LV side. The ratio of these a turns-ratio test can be performed to rule
voltages, equalling the turns ratio, is calculated. out / verify if turns are shorted.
VS Results are compared with name-plate values If the exciting current test shows deviations,
and across phases. and DC winding resistance and ratio test do not
The exciting current is the corresponding current show errors, then the cause may be a core failure
flowing in the HV winding if the LV winding is or unsymmetrical residualflux.
open. Results are compared with a reference
measurement, or a measurement performed on
TR
a sister transformer; in three phase transformers,
the two outer phases can also be compared.

Your Benets
> Powerful AC voltage source,
controllable from 0 to 2000 V
> A perfect digitally generated sine wave
test signal that is independent from
CPC 100 TRRatio test card the quality of the mains wave form
> Convenient and quick testing by
automatic detection of tap changer
operation as trigger for the next tap
measurement
> Exciting current measurement in
amplitude and phase
> Variable frequency for measurements
outside mains frequency for noise
suppression, if selected by the user
Exciting current [mA] per tap > Accuracy and safety
> Automatic reporting of measured
voltage values and phase angles,
measured ratio and deviation as a
percentage, exciting current in
amplitude and phase
> Tabular and graphical result represen-
tation for every tap

Watt losses [W] per tap

13
Measuring DC winding resistance and OLTC

Surge arresters Bushings OLTC Leads Insulation materials Windings Core

Winding resistance measurements are per-


formed for assessing possible winding damage.
It is also used to check the On-Load Tap Changer
(OLTC) - to know when to clean or replace
OLTC contacts, or to know when to replace or
refurbish the OLTC itself, which has a shorter life
span than the active part of thetransformer.
In the factory, this measurement is performed to
calculate the I2R component of conductor losses
and to calculate winding temperature at the end
of a temperature test.
Burn-off at a diverter switch

Measuring resistance with the CPC 100


The CPC100 injects DC current into the winding,
measures current and voltage and then calculates
and displays the resistance. When the resistance
value is stable, the CPC100 makes the final
measurement, and reduces the test current to
zero to discharge the energy saved in the winding.
When it is safe to remove test leads, the CPC100
illuminates its green safety light.

Tapped windings and OLTC


In semi-automatic mode, the CPC100 measures
the resistance of each subsequent tap position.
Each time the user operates the OLTC, the CPC100
Table in CPC 100 TRTapCheck test card Switching process
waits until the values stabilize, and then measures
and displays the winding resistance at this tap
position. When all taps have been measured, the
CPC100 discharges the inductive energy stored
in the winding and indicates when this process is
completed. For automatically measuring static and
dynamic winding resistance and ratio of all phases
and all taps, see page16.

Dynamic resistance measurement


The OLTC has to switch from one tap position to
another without interrupting the load current.
When switching the tap changer during winding
resistance measurement, the DC current
temporarily decreases. This current decrease Winding resistance per tap
should be measured and compared across
taps, as recommeded in the Cigr Transformer
Maintenance Guide445.
14
How does it work? How can results be confirmed?
To measure the winding resistance, the winding Results should not differ more than 1%
under test must first be loaded with energy compared to the reference measurement.
(E=1/2*L*I2) until the inductance of the winding Differences between phases are usually less
is saturated. Then the resistance can be deter- than 2 - 3 %.
mined by measuring DC current and DCvoltage. Transformer turns ratio or frequency response
For tapped windings, this should be done for analysis can be used to confirm contact prob-
every tap position, hence testing the OLTC lems. In both cases, hot spots in the transformer
and the winding together. Results should be will result in a DGA indicating increased heat.
compared to a reference measurement, across However, gas signatures are not unique and thus
phases, or with a sister transformer. In order to do not allow for the identification of the root
compare measurements, the resistance values cause.
have to be re-calculated, to reflect different
temperatures during themeasurements.

Your Benets
> Convenient and quick testing by using
OLTC operation as a trigger for the next
tap measurement
> Additional condition assessment of the
individual OLTC taps through dynamic
resistance measurement, recorded
as a part of classical resistance
measurement, without extra effort
> High accuracy and safe testing through
the use of a 4-wire connection. The
Ripple per tap CPC 100 visually indicates when it is
safe to remove test leads, even if its
power supply is interrupted during
testing. If the test leads are removed
or interrupted accidentally, the test
current will flow through the voltage
path, preventing dangerous over-
voltages. If the CP SA1 accessory is in
use during such an accidental
interruption of test leads, damage to
the CPC 100 will be prevented.
> Automatically created report showing
the test duration, the resistance
value at measurement and reference
temperature, etc.
> Tabular and graphical results are
Slope per tap
produced for every tap for easy
visualcomparison

15
Automatically measuring ratio & winding resistance of all taps and all

Using the CPSB1 accessory, the CPC100 can automatically


>> measure ratio and the exciting current of all of the
Faster Safer
taps and all phases
>> confirm the vector group
>> measure static and dynamic winding resistance of
all of the taps and all phases
This accessory helps to save a lot of time as wiring is only
necessary once. With the same cabling, both ratio and
resistance measurements can be performed.
Through the CPSB1, the CPC100 is connected to all phases
of a transformer. The up and down command inputs of the
OLTC are also connected and controlled by the CPC100 and
the CPSB1.

Ratio measurement
The CPC100 only requires the user to enter ratio and the
vector group to measure the ratio and the exciting current
for each tap of each phase automatically. For each tap,
results are compared to the specified ratio and the
deviations are displayed.

Winding resistance measurement


With the CPSB1, the CPC100 injects DC current into each
tap of each winding. The CPC100 then waits for the current
to stabilize and measures the resistance value, as well as the LV
data describing the switching process (dynamic resistance
measurement).
The tap changer is then operated automatically until
the measurement on one transformer phase is finished.
Between measuring the different phases, the energy stored
in the windings is quickly discharged. When the windings
are fully discharged, the CPC 100 / CPSB1 automatically
switches to the next phase.
At the end of the measurement, the last winding is
discharged and the operator is notified visually that it is
safe to remove the wiring.

AC, DC, OLTC

16
phases

Measurement with witchbox

Switchbox connected to CPC 100 / CP TD1

OLTC HV
Your Benets
> Several times faster than conventional
wiring technique:
- minimum wiring, only once for
all connections
- automatic discharging of the wind-
ings between measurements
- automatic tap changer operation
> Increased safety: no repeated climbing
up and down the transformer
> Simple workflow: a single, automatic
measurement for determining ratio
and exciting current, as well as static
and dynamic winding resistance
> Prevention of wiring errors: prior to
the measurement, wiring plausibility is
automatically checked
> Comprehensive automatic reporting
control for all phases and taps

17
Measuring short circuit impedance / leakage reactance & frequency

Surge arresters Bushings OLTC Leads Insulation materials Windings Core

The measurement is performed for assessing


possible damage/displacement of windings.
Measurements are compared over time or by
comparing phases.
In case of a short-circuit, forces work towards the
core for the inner winding and away from the core
for the outer winding. If these forces affect the
placement of windings, the leakage flux will change.
In particular, short circuits between parallel strands
of Continuously Transposed Conductors (CTCs), and
local overheating due to excessive eddy current
losses linked by the stray flux can be detected.
Regional overheating

Numerous incidents exist of asset managers


investigating the reason why their transformer is
gassing even though all standard electrical tests
show acceptable results. This illustrates that
their tools do not cover all trouble and failure
possibilities.
The Frequency Response of Stray Losses of each
phase will be nearly identical if all phases are in
good condition. An increase in frequency will
result in an increase in impedance as the skin
effect becomes more pronounced.
Just like measuring leakage reactance or short
circuit impedance at power system frequency,
the CPC 100 measures leakage reactance, or
short circuit impedance, across a frequency
range of 15 Hz ... 400Hz, as defined by the user.
It applies AC voltage to the high voltage
winding, with the low voltage winding short-
circuited. It then measures the load current
in amplitude and phase and calculates the
impedance. The measurement is performed for
each transformer phase. The user then compares
results across phases and / or over time.

Measuring frequency response of stray losses

18
response of stray losses

How does it work? How can results be confirmed?


An AC source is connected to each phase of the Leakage reactance: deviations of more than 1 %
HV winding with the corresponding LV winding ought to be investigated with other tests such
shorted. The current and the voltage across the as FRA. Differences between phases are usually
HV winding are measured in amplitude and phase, less than 2 %. Deviations of more than 3 % are
and the short circuit impedance is calculated. considered significant. Frequency response of
Short-circuit impedance measurements should stray losses (FRSL) results can be cross-checked with
ideally be performed over a range of frequencies, PD measurement, FRA, and DGA. If parallel strands
commonly known as Frequency Response of are shorted, higher losses in the stray channel
Stray Losses. Here, the AC source features variable will cause high internal temperatures, normally
frequency. After source current and voltage have indicated by a DGA. The gas signature is not
been measured across the HV winding, the stray unique and does not provide the identification
losses are represented by the inductive part of the of the root cause, however. FRSL is unique in this
short circuit impedance at higher frequencies. respect.

Leakage flux

Your Benets
> A perfect digitally generated sine wave
test signal that is independent from
power quality
> Additional diagnostic information
HV LV LV HV
through the measurement of the
leakage reactance or short circuit
impedance at several frequencies
Leakage flux force direction
> Variable frequency for measurements
outside mains frequency for noise
suppression,
if selected by the user
> Accuracy and safety
> Automatic reporting of all measured
values
> Display of result as Z and , RandX,
or R and L
> Graphical results representation

FRSL test results with faulty phase C

19
Execution of diagnostic tests

1 Detailed nameplate data 2 Customized test plans

In order to assist you during testing, Based on the nameplate values,


PTM helps you in defining your PTM generates a customized
The Primary Test ManagerTM
asset with specific nameplate test plan according to current
(PTM) supports you in views. It indicates mandatory and standards and guidelines for each
performing measurements and recommended parameters, making asset. Thereby, PTM provides you
guides you step by step through data entry fast and easy. with a comprehensive test plan to
the entire test procedure. thoroughly assess the condition of
You can enter information about
your asset.
the location as well as nameplate
parameters, such as serial number, By selecting or de-selecting
vector group, or voltage and current individual tests, you can tailor the
ratings. test procedure to your specific needs
with minimum effort. At the same
Once the data is entered, it can be
time, test plans can be configured in
re-used for all tests in the future.
advance to enable fast and effective
measurements onsite.

20
3 Easy connection due to 4 Fully PC operated 5 Automatic assessment of
wiring diagrams measurement results

Pre-configured wiring diagrams, PTM enables you to control and Limit values can be set according to
depending on the selected asset operate the connected test set current international standards and
and connected test set, assist you directly from a computer. guidelines. They are based on many
with setting up the test equipment Results are automatically stored and years of OMICRON expertise.
in the correct way. organized in the database on your An automatic assessment of the test
In doing so, you minimize the PC and are available for analysis and results is displayed based on the
likelihood of measurement errors, reporting. Therefore, there is no specified limit values. This allows a
speed up your testing process and need to retrieve test results or files fast, first assessment of your assets
obtain accurate test results even from the test equipment after condition.
faster. performing measurements.

Software-guided workow with PTM

21
Dielectric response analysis of power transformers and bushings

Surge arresters Bushings OLTC Leads Insulation materials Windings Core

Dielectric response analysis is used to assess the Dissipation Factor


1
water content of the solid insulation (cellulose)
and thus periodically monitor its condition.
Knowing the water content is important for the 0,1

condition assessment of transformer bushings


and the transformer in its entirety.
0,01
In the factory, this measurement is used at the
end of production to control the drying procress
and to assure low moisture after drying.
0,001

0,001 Hz 1 Hz

Typical shape of dielectric

Displaying the dissipation factor over a wide


frequency range provides insight into the
specific properties of the oil, the geometry of
the solid insulation in the form of spacers and
barriers, and the condition of the solid insulation
itself. This is the only method that can - non-
invasively - directly measure the actual moisture
content in the solid insulation.
The method is scientifically approved by CIGR.
Aging threshold values as defined in IEC 60422
allow for an automatic insulation condition as-
sessment and corresponding recommendations
for further actions such as transformer drying.
OMICRONs DIRANA can measure dielectric
response over an extremely wide frequency
range (10 Hz - 5 kHz). It minimizes testing time
by combining frequency domain spectroscopy
(FDS) at high frequencies and polarization and
depolarization current measurement (PDC)
at low frequencies. DIRANA also displays the
polarization index (PI) based on FDS/PDC
measurement. It thus replaces measuring
insulation resistance, delivering the same
information, but being more accurate for
moisture determination. Testing time is further
minimized by simulaneously measuring through
two channels, and the application of an intel-
ligent curve recognition. Measurements are
ended automatically as soon as the typical shape
of the curve, including the hump, indicates that
all relevant points have been measured.
Verifying the insulation condition with DIRANA

22
How does it work? How can results be confirmed?
If the dissipation factor of a transformer is There are no other non-invasive ways to assess
plotted against a wide frequency range, the moisture in a transformer; dielectric response
Moisture and aging
resulting dielectric response curve contains analysis is unique in this respect.
of cellulose
Insulation Geometry
information on the insulation condition. The Karl Fischer titration method can determine
Oil conductivity
The very low and the high sections contain moisture content in oil or in paper, but has
information on moisture and aging in the solid several disadvantages.
insulation, while the position of the slope in the For instance, to determine moisture in paper,
mid range frequencies indicates the conductivity the method requires opening the transformer
of the liquid insulation. and taking a paper sample. During the process,
This curve is compared to model curves to the insulation itself is being damaged and the
Frequency evaluate aging, particularly for assessing the sample takes up new moisture.
1000 Hz
moisture content in the insulation.
response

Your Benets
f range duration
> Insulation condition assessment
concerning moisture / aging of
cellulose and oil conductivity
DIRANA comprehensive ~ 2.9 h
> Automatic result evaluation according
to IEC60422 (dry, moderately wet, wet,
extremely wet), indicating if further
actions are required
FDS comprehensive ~ 6.0 h
> Completely non-invasive measurement
> Minimum down-time: a measurement
can be performed directly after the
transformer has been shut down, as
PDC limited ~ 5.5 h equilibrium is not required
> Fast measurement through an
intelligent combination of methods
FDS and PDC, simultaneous
measurement with two input
channels and forecast algorithm
> Automatic compensation of the
influence of conductive aging by-
products avoiding overestimation
of moisture content
> Predefined tests for all transformer
types and bushings
> Step-by-step software guidance
> Also measure the insulation condition
of cables, generators, motors and
instrument transformers
DIRANA and accessories in sturdy case

23
Sweep frequency response analysis

Surge arresters Bushings OLTC Leads Insulation materials Windings Core

Frequency response analysis (FRA) is used to Element forming


verify the electrical and mechanical integrity a unique
of the active part of the transformer (core, fingerprint C

leads, windings). FRA is also ideal for further C


diagnosis, if periodic testing or monitoring C
identifiesirregularities.
C

A growing number of utilities also use FRA C

during routine testing, since the method can C


detect a wide range of faults while being C
completely non-invasive.
FRA is the most sensitive method for detecting
mechanical deformations.

Frequency response analysis (FRA) is based


on the comparison of a reference test with an
actual test, where the reference test is usually a
fingerprint that has been previously measured.
When such a fingerprint is not available, another
phase or a sister transformer can also be used for
comparison.
For on site use, FRANEO 800 comes in a rugged
case which all necessary accessories fit into,
including a battery with sucient power
to complete the comprehensive testing of
anytransformer.
FRANEO 800 uses braids for its connections
which allow a high level of reproducibility due to
their tight connection close to the bushing using
clamps and screws.
This technique is recommended in the CIGR
brochure 342 on FRA:
> connection close to the bushing
> broad braids minimize test setup interference

For large bushings, the


influence of the measurement

setup can be reduced even


more by using two braids

24
How does it work? How can results be confirmed?
A low voltage sinusoidal signal with variable Frequency response analysis can detect a wide
frequency is applied to one terminal of a range of faults. Some of these faults can be
C
winding and at the other end of the winding confirmed by other measurements, such as DC
C
R L C
the response signal is measured. The voltage winding resistance, frequency response of stray
C
R L C transfer function of the winding is determined losses, short-circuit impedance / leakage
C
R L C as the output / input ratio. reactance, exciting current, or ratio measurement.
C
R L C
The transfer function of a winding depends on However, no other method can give as clear
C
R L
C the resistive, inductive and capacitive elements an indication as frequency response analysis
C
R L C of the transformer. Changes in these elements can to determine whether windings have been
C
R L C as a consequence of a failure lead to changes in deformed, for example by the mechanical forces
R L the transfer function. Results are represented in resulting from a fault.
magnitude and phase as in a Bode diagram.

Your Benets
> Non-invasive detection of:
- Axial and radial winding deformation
- Displacements between high- and
low-voltage windings
- Partial winding collapse
- Shorted or open turns
- Faulty grounding of core or screens
Automatic comparison / evaluation of results
- Core movement
- Broken clamping structures
- Problematic internal connections
> Wide dynamic measuring range
(> 145 dB)
> Reproducible results thanks to
innovative connection technique,
based on IEC 0076-18, method 1
> Guided workflow for test set-up,
execution and assessment or easy
analysis without expert knowledge
> Fast measurement times due to
intelligent sweep algorithm
> Small and light-weight equipment
guarantees optimum usability

Small and lightweight FRANEO 800

25
Partial discharge analysis

Surge arresters Bushings OLTC Leads Insulation materials Windings Core

Once initiated, partial discharge (PD) causes a conductor


progressive breakdown of insulating materials C2
by electrical tree formation. C3 C3
PD measurements are performed on the C1
insulation of transformers to determine the
insulations condition and to safely prevent it void
oid
insu
from breaking down. C2

PD measurement is also part of the factory


acceptance test. conductor

Partial discharge measurem

The OMICRON MPD PD system offers quick and


precise recording of pulses on the three phases
of a transformer using data acquisition from
three or more channels.

Digital lter
In the MPD 600 the classical analog bandpass
filter has been replaced by a digital filter using a
mathematical algorithm. Digital system design
eliminates aging effects and temperature drift
making measurements comparable and
reproducible by perfectly reproducing settings:
> the digital filter can be easily adapted
to the conditions on site by tuning its
center frequency and bandwith to minimize
disturbances with fixed frequency bands
> calibration values for charge and voltage
can be set directly on the laptop controlling
the test, fully reproducible during the next
measurement

Optical Isolation
Between individual PD acquisition units and be-
tween the acquisition units and the PC / laptop,
fiber-optics are used for the communication.
Communication with fiber-optics ensures a
continuous, disturbance-free transmission of
PD events and test voltage. The units are
supplied using a battery power supply. This
design provides complete galvanic isolation
between the individual components, minimizing
ground loops and so reducing interference. PD analysis on a three phase transformer

26
How does it work? How can results be confirmed?
A coupling capacitor is connected in parallel A chemical dissolved gas analysis (DGA) can
to the capacitances of the measured insulation also indicate partial discharges. It is impossible,
distance. Any charge movements within the however, to locate partial discharges with DGA.
connected insulation distance will be reflected
in the charge of the coupling capacitor. The
Ccoupling
resulting circulating current of the paralleled
capacitances is measured and interpreted.
ulation Analyzing PD means detecting and evaluating
very small discharges, while dealing with very
high test voltages, often complicated by external
disturbances.

ment

Battery powered acquisition units


The acquisition units are supplied from
rechargeable batteries, which can supply the
units for more than 20 hours. Another advantage
of battery power supply is that it eliminates
disturbances which would result from a mains
power supply.

Noise suppression through gating


Additionally, noise can be eliminated by
amplitude / phase gating, dynamic noise gating
or antenna gating. Here, one measurement
Signals acquired simultaneously by 3 units channel, which is not connected to the equipment
under test, is used as a detector for external
disturbances. Any pulse picked up by this unit is
considered to be an external disturbance and is
therefore eliminated on all other units because
internal PD cannot be detected by this antenna
channel due to the shielding effect of tank and
graded bushings.

Multi-channel measurement
Measuring simultaneously with several channels
with synchronization accuracy in the range of
nanoseconds has several advantages:
> it minimizes the time for which high voltage
has to be applied to a suspect transformer
and speeds up testing
> it allows for real-time de-noising of the data
to minimize the influence of disturbances,
and helps separating different sources of PD
PD acquisition unit and identifying the type of PD sources
27
Partial discharge analysis

Tuning to partial discharges (PD)


When you are listening to the radio, the audio
filter of your receiver filters out all other radio
stations, and only plays the one that you are
listening to. The MPD can use two methods for
tuning to PD sources to display only what you
want to take a closer look on.

3-Phase Amplitude Relation Diagram


Through cross-coupling, a PD pulse on one
Measurements related to each other in 3PARD or 3CFRD
phase in a transformer will usually appear on
all phases - with different amplitudes. Noise,
however, is external and thus produces
amplitudes that are similar on all phases.
By synchronously measuring on all phases the
tester can separate pulses by plotting them in the pd cluster
3-Phase Amplitude Relation Diagram (3PARD).
Noise will create a separate cluster in this diagram,
usually in the center of the 3PARD. PD,however,
the pulses of which are often smaller than those of
noise, typically form a cluster outside the center. If
more than one PD source exists, each of them will
form a separate cluster.
When a cluster is selected, the phase-resolved
PD pattern will be shown specifically for this
cluster, facilitating pattern recognition, i.e.
determining the possible cause of a single PD
source.

3-Center Frequency Relation Diagram


Another way to separate pulses is 3-Center
Frequency Relation, which requires only one
measurement channel, for example when the
test object is a single phase transformer.
This method measures with three filters at
different measurement frequencies at the same
time. Using spectral differences, distinct internal
pulses can be separated from each other and PD
can be discriminated from external noise.
The result of the three measurements is plotted
in the 3-Center Frequency Relation Diagram
(3CFRD). The unfolding clusters in this diagram
can then be analyzed separately.

Advantages of 3PARD and 3CFRD


> allows the separation of PD activity from noise
> enables the separation of different PD sources Separated partial discharge Separated noise
> facilitates pattern recognition
28
Ultra high frequency PD detection
Within liquid-insulated transformers, PD can also
be measured using ultra high frequency (UHF)
sensors. PD is directly measured from within
the tank, by flanging UVS 610 sensors directly
onto it, using its natural screening effect. The
UHF620 accessory converts the signals for the
MPD. UHF measurement can also be used to
trigger an acoustic PD measurement, or as an
additional gating mechanism - then pulses from
an electrical measurement are only accepted if a
UHF pulse is also present.

UVS 610 UHF sensor (MPD accessory)

noise cluster

Your Benets
> Lightweight, scalable and
modular system
> High speed for the most
comprehensive testing
> Measuring all phases of a transformer
simultaneously with nanosecond
synchronicity
> High operator safety through optical
fibers galvanically isolated from the
PD acquisition units
> High sensitivity down to pico or even
femto Coulombs through effective
gating technology
> Separating PD sources and noise
through 3PARD / 3CFRD
> Improving the locating of PD and thus
assisting the user to make the right
follow-up decisions (e.g. if a
transformer can be repaired on-site)

29
Power transformer services, training and support

Expertise in transformer diagnostics


OMICRON employs some of the worlds most
renowned experts in transformer diagnosis.
Among them are members of working groups
concerned with transformer maintenance
and diagnosis in international standardization
bodies, such as CIGR, the IEEE, or the IEC.
They have performed numerous diagnostic
measurements on power transformers, often
as a result of customer requests.
Moreover, they have published many papers
on power transformer diagnosis, which are
available in the customer area on the OMICRON
website, together with dedicated expert forums,
moderated by OMICRON.

Result assessment support OMICRON experts evaluating a customers results

OMICRON experts support customers in


interpreting and assessing results - such as
partial discharge patterns, or FRA fingerprints.

Technical support
High quality technical support teams also
provide answers to questions on the use of the
equipment, and are the first point of contact
should a functional problem occur. If a repair is
necessary, repair times are short - typically in the
range of less than one or two weeks.

Dedicated events
OMICRON hosts the regular Diagnostic
Measurements on Power Transformers
Workshop. There, typically over a hundred
delegates from all over the world share and
discuss case studies and recent developments
in transformer diagnosis.
Themes include best practice experiences and
solutions in transformer testing presented by
customers and new technological developments
reported by OMICRON. Informal get togethers
aid peer exchange.
Several smaller events on related subjects
targeted on the particularities of specific
geographical regions are also offered
throughout the year.
Demonstration booth at dedicated event

30
Training courses
OMICRON training courses provide a solid
theoretical and practical background and
answer a clients individual questions. Training
courses are held at either the customers site,
online through a webinar, or in one of the
OMICRON training centers wordwide.

Power transformer training topics


> Design, testing and maintenance
> Chemical diagnostic methods
> Diagnostic measurements and
residual life assessment
> Condition assessment of HV bushings
> Moisture determination and dielectric
diagnostics
Customer theoretical training
> Frequency response analysis and
interpretation
> Partial discharge measurement
> Training courses using OMICRON
technology

Your Benets
> Assistance in interpretation and
assessment of results
> Access to relevant training modules
> Dedicated conventions/conferences
> Technical assistance in equipment
usage from our technical support
teams
> Access to scientific papers on
transformer diagnosis through the
Customer practical training customer area on our website

31
OMICRON is an international company serving the electrical power industry with
innovative testing and diagnostic solutions. The application of OMICRON products
allows users to assess the condition of the primary and secondary equipment on
their systems with complete confidence. Services offered in the area of consulting,
commissioning, testing, diagnosis and training make the product range complete.

Customers in more than 140 countries rely on the companys ability to supply leading-
edge technology of excellent quality. Service centers on all continents provide a broad
base of knowledge and extraordinary customer support. All of this together with our
strong network of sales partners is what has made our company a market leader in the
electrical power industry.

For more information, additional literature,


and detailed contact information of our
worldwide offices please visit our website.

OMICRON L2528, October 2015


www.omicronenergy.com Subject to change without notice.

You might also like