You are on page 1of 8

May 29, 2002

TECHNICAL BULLETIN 004a


Ferroresonance

Abstract - This paper describes the phenomenon


of ferroresonance, the conditions under which it BACKGROUND ANALYSIS
may appear in electric power systems, and some
techniques for avoiding ferroresonance or In order to understand ferroresonance, a nonlinear
mitigating its effects. phenomenon, it is necessary to distinguish it from
regular and well understood resonance in electrical
INTRODUCTION circuits, what we will refer to as linear resonance.

Ferroresonance is a complex electrical phenomenon Linear Resonance


that, though identified since the early 1920s,
remains little understood today. It is characterized In a linear resonance the impedance values
by the sudden onset of very high sustained represented by the circuit components are
overvoltages concurrent with high levels of predictable; they change predictably with
harmonic distortion. Ferroresonance has been frequency. When operated within its designed
known to be responsible for equipment damage and ranges, a given capacitance will always present a
protection malfunctions capacitive reactance of

Ferroresonance is hard to analyze, in part because it


does not occur regularly or predictably in response
to a particular stimulus. More than one stable steady
state response can result from the same set of initial
circuit parameters. In response to a voltage and a given inductance will always present an
transient, phase to ground fault, circuit breaker inductive reactance of
opening, equipment energization or de-
energization, lightning induced overvoltages, or any
number of other sudden changes, the system can
take a sudden non-linear jump from its normal
steady state response to a steady state condition of where T is the frequency of the sinusoidal voltage
severe harmonic distortion and high (several per- and current.
unit) overvoltages that can severely damage power
system equipment. The relationship between a voltage across an
impedance and a current through it is given by
All is not lost however. Enough is known about Ohms Law:
ferroresonance to enable power system engineers to
design systems that avoid the problem, or to
mitigate its effects should it occur.

P.O. Box 495578 Garland, Texas 75049-5578 Phone 972/240-1594 Fax 972/303-0779 Email info@cadickcorp.com http://www.cadickcorp.com
Figure 2 Series and Parallel Resonance

Resonance, linear or otherwise, occurs when will also be at a maximum.


the inductive and capacitive reactances of a
circuit exactly balance. As shown in the In both series and parallel resonance, the
equations, inductive reactance is proportional to extreme effects of voltage and current are
frequency, rising with rising frequency, while mitigated by the introduction of pure resistance,
capacitive reactance is inversely proportional to because the value of a pure resistance is the
frequency, and so drops with rising frequency. same at all frequencies.
For a given electrical circuit a resonant
frequency can be found in which the inductive Linear resonant circuits as shown above exhibit
reactance and the capacitive reactance exactly regular and predictable responses to the applied
cancel. In a series resonant circuit (Fig. 1a) this voltage. A steady-state sinusoidal voltage will
results in a total impedance Z that is a result in sinusoidal voltages and currents
minimum. And because everywhere in the circuit; and though at
the current is a maximum. In a parallel resonant different magnitudes, they will be at the same
circuit (Fig. 1b) the total impedance is a frequency. Applying twice the voltage will
maximum at the resonant frequency. For a result in doubling the magnitude of voltages and
given current flowing through the circuit, the
voltage across the circuit

P.O. Box 495578 Garland, Texas 75049-5578 Phone 972/240-1594 Fax 972/303-0779 Email info@cadickcorp.com http://www.cadickcorp.com
Figure 3 Magnetic Hysteresis

currents elsewhere in the circuit. Even the


circuits response to transients, though somewhat C the resonant frequency can be
more complicated, is theoretically predictable different for each stable
and repeatable. response.

Ferroresonance Ferroresonance occurs because the inductance


in the circuit is ferromagnetic, meaning that it
With ferroresonance the rules change. has a core made of a ferromagnetic material,
Ferroresonance is distinguished from linear usually iron. A transformer is an excellent
resonance in that: example of a ferromagnetic inductance.

C there exist several stable steady In ordinary, non-ferromagnetic inductance, as in


state responses to any given a simple coil of wire, the value of inductance is
change of parameters. determined by geometry; the dimensions of the
C Which particular response coil, the number of turns, the cross sectional
occurs is very dependant on the area, etc. When a ferromagnetic material such
initial conditions. as iron is introduced into the core of such a coil,
C resonance at a given frequency the inductance value is changed. This is
can occur over a wide range of because ferromagnetic materials have the
parameter values. property of causing an increase the magnetic

P.O. Box 495578 Garland, Texas 75049-5578 Phone 972/240-1594 Fax 972/303-0779 Email info@cadickcorp.com http://www.cadickcorp.com
flux density, and therefore the magnetic positive current. This is a characteristic of
induction.* The amount of magnetic induction ferromagnetic materials, and also very
attributable to the iron in the center of the important to understanding ferroresonance. The
solenoid can be much larger than the induction magnitude of current that causes the iron to go
associated with the current in the coil by itself. into saturation is not the same as the magnitude
at which the iron comes out of saturation. The
There are two additional properties of boundary between linear operation and
ferromagnetic materials that are important in saturated operation is not a fixed value of
understanding the phenomenon of current, but is dependant on the previous values
ferroresonance. Ferromagnetic materials can of that current. This is called hysteresis, and is
saturate, and they exhibit hysteresis. due to residual flux density stored in the iron,
and which must be overcome when the current
A typical magnetization curve of an iron core changes direction.
coil is shown in Figure 2. As the current
increases, the magnetic flux density increases. As with any resonance, the resonant frequency
A point is reached, however, where further is that at which the capacitive and inductive
increases in current yield smaller and smaller reactances exactly cancel. At resonance
increases in flux density. This is called the extreme values of voltage and current can occur.
saturation point, and is characterized by a With ferroresonance however, the inductance is
dramatic change in the slope of the current - not fixed. It changes due to saturation, and this
flux density curve. The slope of this curve is changes the inductive reactance, so that the
proportional to the inductance of the coil, which resonant frequency is a moving target. As the
indicates that the inductance value itself is iron goes into saturation, the sudden change in
different for current magnitudes above the inductance brings about a sudden change the
saturation point. This is key to understanding frequency at which resonance will occur.
ferroresonance. As the current in a
ferromagnetic coil increases beyond the Another way of looking at this is to focus on the
saturation point, the inductance of the coil value of capacitance required to bring about a
changes rather suddenly. resonance. In a linear resonance this value can
be (theoretically) identified precisely. With
Figure 2 further shows two current-flux density ferroresonance however, sudden and
characteristics. The bottom curve indicates the unpredictable changes in inductance will mean
the flux that occurs when increasing from a that a wide range of capacitances can potentially
negative current. The top curve indicates the lead to resonance at a given frequency.
flux that occurs when decreasing from a
Once the ferromagnetic inductance pops into
saturation, it remains saturated until the current
*
In nonmagnetic materials the magnetic effect magnitude decreases. If the inductance when
of electron spin in one direction is completely offset by saturated causes a resonance (i.e. results in an
equal electron spin in the opposite direction. In ferro- inductive reactance that matches the capacitive
magnetic materials, compensation is not complete, and reactance in the circuit), the current magnitude
tiny, completely magnetized domains exist in the
can increase dramatically, further driving the
crystals of such materials. The application of a
magnetic field (as when in the presence of an electrical iron into saturation, and thus making the
current) causes an orientation of the domains in the resonant point stable.
direction of the applied field. [5]

P.O. Box 495578 Garland, Texas 75049-5578 Phone 972/240-1594 Fax 972/303-0779 Email info@cadickcorp.com http://www.cadickcorp.com
If the current is able to drop below the which ferroresonance is likely to occur.
saturation point, the inductance pops out of
saturation, and again the inductance value ! A sinusoidal voltage source - A power
changes. As previously described, magnetic system generator will do quite nicely.
hysteresis causes the precise points where the ! Ferromagnetic inductances - these can
inductor goes into and out of saturation to be be power transformers or instrument
different, as shown in Figure 2. transformers.
! Capacitance - this can come from
These dramatic changes in inductance account installed power system capacitors, the
for the multiple stable responses characteristic capacitance to ground of transmission
of ferroresonance. Hysteresis explains how the lines, the large capacitance of
particular response that occurs is very underground cable, or the capacitance to
dependant on the initial conditions. ground of an ungrounded system.
! Low resistance - this can be lightly
As with linear resonance, the introduction of loaded power system equipment,
significant resistance in the circuit will tend to (unloaded transformer for example), low
mitigate the extreme values of voltage and short circuit power source, or low circuit
current. losses.

POWER SYSTEM FERRORESONANCE A further requirement [1] is the existence of at


least one point in the system whose potential is
Ferroresonance in a power system can result in not fixed. This can be an isolated neutral, or
any of the following, alone or in combination: can be created by a blown fuse or during single
phase switching. This one degree of freedom
C high sustained overvoltages, can allow the system to reposition itself into
both phase to phase and phase to a ferroresonant condition.
ground, (a maximum of 4.5 per
unit in one typical example [2].)
C high sustained overcurrents,
C high sustained levels of
distortion to the current and
voltage waveforms,
C transformer heating and
excessively loud noise,
C electrical equipment damage
(thermal or due to insulation
breakdown)
C Apparent mis-operation of
protective devices.

If this occurred randomly without warning it


would be quite disconcerting. Armed with our
circuit level understanding of ferroresonance,
however, we can identify the conditions under

P.O. Box 495578 Garland, Texas 75049-5578 Phone 972/240-1594 Fax 972/303-0779 Email info@cadickcorp.com http://www.cadickcorp.com
Figure 4 Typical Power System Configuration Favorable to Ferroresonance

The research [1] on ferroresonance indicates through a wye grounded to delta generator step
that if any one of these conditions does not up (GSU) transformer. The GSU transformer
exist, ferroresonance is highly unlikely. provides no ground to the 34.5 kV system, and
isolates it from what ever ground connection is
The number of power circuit configurations provided by the generator itself. The utility
which meet the conditions described above and source feeds the other side of the circuit, and
therefore could conceivably support even assuming it is grounded, may become
ferroresonance are endless. Through experience, ungrounded during some switching
however, several typical circuit configurations contingencies. A recloser or the gang operated
can be identified that have been known to give switch can isolate the cogenerator from the
rise to ferroresonance. [1] utility source, and if the plant is running with
this switch open, the 34.5 kV section of line will
TYPICAL NON-UTILITY POWER PLANT be entirely ungrounded.

This paper now concentrates on the circuit Ferroresonance is a possibility during the time
presented by an actual industrial cogeneration the 34.5 kV line section is not adequately
project. The connection of this generator into grounded. Each of the necessary pre-conditions
the utility distribution system typifies one of the described will be met:
configurations known to give rise to
ferroresonance: a grounded voltage transformer ! A sinusoidal voltage source - in this
connected to an isolated neutral system. case the normal utility source or the
power plant generator.
As shown in Figure 3, the scenario features a ! Saturable ferromagnetic inductance - the
voltage transformer whose wye grounded voltage transformer
primary is connected to a 34.5 kV system that ! Capacitance - capacitance to ground of
could become ungrounded. the 34.5 kV lines.

One side of the circuit is fed by a generator,

P.O. Box 495578 Garland, Texas 75049-5578 Phone 972/240-1594 Fax 972/303-0779 Email info@cadickcorp.com http://www.cadickcorp.com
Figure 5 Parallel Ferroresonant Circuit

! Low resistance - the voltage transformer provides an inductive reactance exactly


only is probably very lightly loaded, as canceling the capacitive reactance, and
it feeds voltage sensing devices. The ferroresonance results. Overvoltages, caused by
generator may also be very lightly the parallel resonance, will sustain the
loaded. saturation, and thus stabilize the ferroresonant
! The existence of at least one point in the condition. Steady state overvoltages can exceed
system whose potential is not fixed - normal phase to phase voltage and destroy
the neutral point of the ungrounded or electrical equipment. Extreme harmonic
inadequately grounded section of the distortion may confuse protective relays and
system. prevent tripping.

The ferroresonant inductance of the voltage PREVENTION OR MITIGATION


transformer is in parallel with the system
capacitance, as shown in Figure 4. An initiating Ferroresonance is prevented by eliminating one
event, such as a transient overvoltage due to of the pre-conditions. Several alternatives, of
switching or fault clearing on the utility system, various practicality, present themselves:
or a phase to ground fault on the inadequately
grounded system, can drive one or several C avoid by design: use a delta
phases of the VT into saturation. The saturation connected primary VT. (This
of the iron core results in a sudden change in the may not be practical in this case
inductance presented to the system by the because one of the purposes of
voltage transformer. The ferromagnetic circuit the VT is to detect ground faults
can lock onto a level of saturation that using an open corner delta

P.O. Box 495578 Garland, Texas 75049-5578 Phone 972/240-1594 Fax 972/303-0779 Email info@cadickcorp.com http://www.cadickcorp.com
secondary.) transformer turns ratio. [3]
C prevent the system from
becoming ungrounded under any
conditions. (This may not be
entirely possible.) CONCLUSIONS
C purchase a VT designed to
operate at much lower induction Though ferroresonance may be complex and
values, so that the saturation hard to analyze, it need not be mysterious.
point is at least twice the system Ferroresonance has been shown to be the result
voltage. (This may an expensive of specific circuit conditions, and can be
alternative.) induced predictably in the laboratory. Power
C Introduce losses by means of system ferroresonance can lead to very
load resistances. (This is the dangerous and damaging overvoltages, but the
alternative chosen.) condition can be mitigated or avoided by careful
system design.
In wye-wye connected VTs three resistors can
be connected, one in each secondary circuit. It REFERENCES
is important to pick resistor values carefully, as
the resistors connected this way will [1] Ferracci,P., Ferroresonance Cahier
continuously absorb power and can affect the Technique No. 190, Group Shneider
accuracy of connected metering. [2] Fink,D.G., and Beaty,H.W., eds.,
Standard Handbook for Electrical
Where an open corner delta secondary exists, a Engineers, 13th ed., Meliopoulos,
single resistor across the open delta is advisable. A.P.S., Sec. 27, New York, McGraw-
This has the advantage that it does not affect the Hill Book Company, 1993.
measurement accuracy of the VT or introduce [3] Elmore,W.A., ed., Protective Relaying
losses during normal operating conditions. Theory and Applications, ABB Power
Only during an unbalanced condition (such as T&D Company, Blackburn, J.L.,
may initiate ferroresonance in the first place) Kresseler,J.V., Chp. 7., New York,
does the resistor provide damping. Marcel Dekker, Inc., 1994.
[4] Protective Relays, GEC Alsthom
The appropriate value of resistance is given by Measurements, Stafford England, 1990
Karlicek and Taylor in Ferroresonance of [5] Masch,L.W., Electromagnetic &
Grounded Potential Transformers on Electromechanical Machines, 2nd ed.,
Ungrounded Power Systems (AIEE Power New York, Harper & Roe, 1972
Apparatus & Systems, August 1959) as

where La is the voltage transformer primary


inductance in millihenries and N is the

P.O. Box 495578 Garland, Texas 75049-5578 Phone 972/240-1594 Fax 972/303-0779 Email info@cadickcorp.com http://www.cadickcorp.com

You might also like