You are on page 1of 2

JOB # Document No.

________________
Customer: Rev. _____
Job Title:
Page _____ of _____
Subject:

Engineer: Travis C. Smith

Date: 8/18/2015 Page 1

Weld Type 9:
FEXX 70 ksi Fallow 0.3 FEXX 21 ksi

d 6 in tweld 1 in
b 10 in
tw 0.36 in

Loads:
Fx 20 k M x 20 in k

Fy 20 k M y 20 in k

Fz 20 k M z 20 in k

Calculations:
2 2 2 2
A1 d tweld 6 in A2 d tweld 6 in A3 b tweld 10 in Aw A1 A2 2 A3 32 in

d d
2
A1
2

A2 0 2 d A3 x bar
b
5 in
y bar 1.125 in 2
Aw
2
2 tw 2
cp max x bar y bar d y bar 5.125 in
2
2
d t
weld
3 2 Ix
d d y bar tweld 2 b y bar tweld 103.5 in
d 2 4 3
Ix 2 Sx 21.231 in
12 2 d y bar
t 2 b 3 t
w weld 4 Iy 3
Iy 2 d tweld 2 167.055 in Sy 33.411 in
2 12 x bar

4
Ip Ix Iy 270.555 in

Fx Fy Fz
fx 0.625 ksi fy 0.625 ksi fz 0.625 ksi
Aw Aw Aw

Mx My M z cp
fmx 0.942 ksi fmy 0.599 ksi fmz 0.379 ksi
Sx Sy Ip

fr
fmx fmy fz
2 2 2 2
fr fx fy fmz 2.37 ksi Weldmin_size in 0.16 in
0.707 Fallow
Weld Type 09_T-Shape_R001.xmcd
JOB # Document No.________________
Customer: Rev. _____
Job Title:
Page _____ of _____
Subject:

Engineer: Travis C. Smith

Date: 8/18/2015 Page 2

Size Weld per TVA Criteria in DS-C1.2.6, General Pipe Support Design Manual:
Fystl 36 ksi

Fy M z cp
fay 1.004 ksi
Aw Ip

Fz M z cp
fbz 1.004 ksi
Aw Ip

Fx Mx My
fcx 2.166 ksi
Aw Sx Sy

2 2 2
frr fay fbz fcx 2.589 ksi

frr
Weldmin_size_TVA min 0.707 F in 0.18 in
allow 0.4 Fystl

Weld Type 09_T-Shape_R001.xmcd