14 Clean-Room Controls and Optimization


B. G. LIPTK (1985, 1995, 2005)

INTRODUCTION

Clean work
Service core

Service core
Clean work

aisle
aisle
Clean-rooms are used for experimental studies of a wide
variety. Testing and analysis laboratories, used in the medical, Process area
military, and processing industries, are all designed to operate (clean room)
as clean-rooms. The control and optimization of clean-rooms,
Rows of work stations
therefore, is an important subject to many industries. (production tools with exhaust hoods)
The traditional method of maintaining air cleanliness is
Corridor (isolates clean-room area from oces)
by ltering. Standard HEPA lters are capable of removing
up to 99.97% of impurities at 0.3 micrometers, while ULPA FIG. 8.14a
lters are efcient up to 99.9995% at 12 micrometers. In this The configuration of a semiconductor manufacturing clean-room
section, besides ltering, other air cleanliness control meth- with rows of workstations and a corridor surrounding the whole
area.
ods will also be discussed.
The production of semiconductors is one of several pro-
cesses that require a clean-room environment. Optimization
of the clean-room control system will drastically reduce both In order to prevent contamination through air inltration
the energy cost of operation and the cost associated with the from the surrounding spaces, the pressure in the clean-room
manufacturing of off-spec products, because plant productiv- must be higher than that of the rest of the building. As shown
ity is maximized if drafts are eliminated in the clean work in Figure 8.14a, the clean-room is surrounded by a perimeter
aisle. This is because drafts can stir up the dust in the work- corridor. In order to protect against the in-leakage of dirty
station area, and if the dust settles on the product, production air from the corridor, the clean-room pressure is controlled
losses result. above it.
The clean-room is made up of rows of workstations.
These rows are also referred to as zones. A typical semicon-
ductor producing plant has approximately 200 workstations,
SEMICONDUCTOR MANUFACTURING which are also called subzones. Each subzone faces the clean
work aisle, and behind it is the service core.
The process, or production area of a typical semiconductor
2
manufacturing laboratory is between 100,000 and 200,000 ft Subzone Optimization
2
(9,290 and 18,580 m ). The market value of the daily pro-
duction from this relatively small area is well over $1 million. As shown in Figure 8.14b, air is supplied to the subzone
Plant productivity is increased if the following conditions are through lters located in the ceiling in front of the worksta-
maintained in the process area: tion. The total ow and the temperature of this air supply are
both controlled. The evacuated exhaust air header is con-
nected to the lower hood section of the workstation. It pulls
1. No drafts (+0.02 in. H2O 0.005 in. H2O, or 5 Pa 1.3 Pa) in all the air and chemical fumes that are generated in the
2. No temperature gradients (72F 1F, or 22C 0.6C) workstation and safely exhausts them into the atmosphere.
3. No humidity gradients (35% RH 3%) In order to make sure that none of the toxic fumes will
4. No airow variations (60 air changes/hr 5%) spill into the work aisle, clean air must enter the workstation
at a velocity of about 75 fpm (0.38 m/s). The air that is not
Therefore, the goal is to continuously maintain these pulled in by the exhaust system enters the service core, where
conditions through the accurate control of these parameters. some of it is recirculated back into the workstation by a local
The secondary goal is to conserve energy. The sensors and fan. The rest of the air is returned from the service core by the
control loop congurations required to meet both of these return air header. A damper in this header (RAR-1) is modu-
goals will be described in this section. lated to control the pressure (DPS-1) in the clean work aisle.

1753

2006 by Bla Liptk


1754 Control and Optimization of Unit Operations

Cold Hot When this airow balance is altered (for example, as a


air air
CAD HAD result of a change in exhaust airow), it will cause a change
2 2
FC FO in the space pressure, and DPS-1 will respond by modifying
the opening of RAR-1.

Return Exhaust
air air
Mixing
box FC
Elimination of Drafts Plant productivity is maximized if
TAD
4 4 drafts are eliminated in the clean work aisle. Drafts would
HBD
6 stir up the dust in this area, which in turn would settle on the
RHT
3
product and cause production losses. In order to eliminate
RAR
1 drafts, the pressure at each workstation must be controlled
Filter at the same value. Doing so eliminates the pressure differen-
DPS Corridor
M
Filter 1 reference
Ceiling tials between stations and therefore prevents drafts. When a
Supply air ZSC
DPS-1 unit is provided to control the pressure at each work-
M
EAD
5 Supply air station, the result is a uniform pressure prole throughout the
Door
5
switch clean-room.
Fan PDS-1 usually controls the pressure in the clean work
Filter aisle on the process side of the workstation. Yet, it is impor-
Operable
sash TC tant to make sure that all points, including the service aisle,
2
Set at
are under positive pressure. Because the local circulating fan
72F 1F within the workstation draws the air in from the service core
(22C 0.6C)
and discharges it into the clean work aisle, the pressure in
the service core will always be lower than that on the process
DPS-1 set at 0.02" H2O 0.005" H2O
(5 Pa 1.5 Pa) side (see Figure 8.14b). On the other hand, it is possible for
FC-4 set to provide the sum of exhaust
plus 60 air changes per hour
localized vacuum zones to evolve in the service core. This
Hood RHT-3 is kept at 35% RH 3% RH could cause contamination by allowing air inltration into
Floor the service core. To prevent this from happening, several
solutions have been proposed.
Service core Work station Clean work aisle
One possibility is to have DPS-1 control the service core
FIG. 8.14b pressure. This is not recommended, because a draft-free pro-
Workstation controls maintain comfort while guaranteeing that all cess area can be guaranteed only if there are no pressure
toxic chemical fumes are removed from the work area. gradients on the work aisle side; this can only be achieved
by locating the DPS-1 units on the work aisle side of the
The lter shown in Figure 8.14b can be a standard HEPA workstations.
lter, which is efcient up to 99.97% at 0.3 micrometers, or Another possibility is to leave the pressure controls on
it can be an ULPA lter, which is efcient up to 99.9995% the work aisle side but raise the set point of DPS-1 until all
at 12 micrometers. the service cores in the plant are also at a positive pressure.
This solution cannot be universally recommended either,
Pressure Controls The pressure in the corridor is the ref- because the quality of building construction might not be
erence for the clean-room pressure controller DPS-1 in high enough to allow operation at elevated space pressures.
Figure 8.14b. This controller is set to maintain a few hun- The pressurization loss in badly sealed buildings can make
dredths of an inch of positive pressure relative to the corridor. it impossible to reach the elevated space pressure.
The better the quality of building construction, the higher Yet another solution is to install a second DPS controller,
this set point can be, but even with the lowest quality build- which would maintain the service core pressure by throttling
ings, a setting of approximately 0.02 in. H2O (5 Pa) can easily the damper HBD-6. This solution will give satisfactory per-
be maintained. formance but will also increase the cost of the control system
At such near-atmospheric pressures, air behaves as if it by the addition of a few hundred control loops (one per
were incompressible, so the pressure control loop shown in workstation).
Figure 8.14b is both fast and stable. When the loop is ener- A more economical solution is shown in Figure 8.14b.
gized, DPS-1 quickly rotates the return air control damper Here, a hand-operated bypass damper (HBD-6) is manually
set during initial balancing. This solution is reasonable for
(RAR-1) until the preset differential is reached. At that point,
most applications, because the effect of the workstation fan
the electric motor stops rotating the damper, and it stays at
is not a variable, and therefore a constant setting of HBD-6
its last opening. This position will remain unaltered as long
should compensate for it.
as the air balance in the area remains the same:
return airow = supply airow (exhaust airow Temperature Controls The temperature at each workstation
+ pressurization loss) 8.14(1) is controlled by a separate thermostat, TC-2 in Figure 8.14b.

2006 by Bla Liptk


8.14 Clean-Room Controls and Optimization 1755

Relative humidity
transducer
2.3"
(58 mm) Temperature
transducer

Threaded probe body


3 Duct-mount
1.0" (18 20 thread)
(25 mm)
Shoulder

O-ring
Wall-mount

FIG. 8.14c
Polystyrene surface conductivity humidity element. (Courtesy of General Eastern.)

This temperature control adjusts the ratio of cold air to hot offset error. This can be most economically accomplished
air within the supply air mixing box to maintain the space through the use of microprocessor-based shared controllers
temperature. that communicate with the sensors over a pair of telephone
Unfortunately, conventional thermostats cannot be used wires that serve as a data highway.
if the temperature gradients within the clean-room are to be
kept within 1F of 72F (0.6C of 22C). Conventional Humidity Controls The relative humidity sensors are located
thermostats cannot meet this requirement for either measure- in the return air stream (RHT-3). In order to keep the relative
ment accuracy or control quality. Even after individual cali- humidity in the clean-room within 35% RH 3% RH, it is
bration, it is unreasonable to expect an error of less than 2 important to select a sensor with an error lower than 3% RH.
or 3F (1 or 1.7C) in the overall loop performance if The repeatability of most relative humidity sensors (see Sec-
HVAC-quality thermostats are used. Part of the reason for tion 8.32 in the rst volume of this handbook) is approxi-
this is the fact that the offset cannot be eliminated in plain mately 1% RH.
proportional controllers such as thermostats (Section 7.9). Figure 8.14c illustrates the polystyrene surface conduc-
Thus, in order for the thermostat to move its output from tivity-type humidity element. These units are available for
the mid-scale value (5050% mixing of cold and hot air), an duct mounting and can be used for clean-room control appli-
error in room temperature must rst develop. This error is cations if they are individually calibrated for operation at or
the permanent offset. The size of this offset error for TC-2 around 35% RH. Without such individual calibration, they
in Figure 8.14b for the condition of maximum cooling can will not perform satisfactorily, because their off-the-shelf
be determined as follows: inaccuracy, or error, is approximately 5% RH.
The controller associated with RHT-3 is not shown in
spring range of CAD Figure 8.14b, because relative humidity is not controlled at
offset error = 8.14(2) the workstation (subzone) level but at the zone level (as
2(thermostat gain)
mentioned earlier, a zone is a row of workstations). The
Assuming that CAD-2 has an 813 PSIG (5590 kPa) control action is based on the relative humidity reading in
spring (a spring range of 5 PSI, or 34.5 kPa) and that TC-2 the combined return air stream from all workstations within
is provided with a maximum gain of 2.5 psi/F (31 kPa/C), that zone.
the offset error is 1F (0.6C). Under these conditions, the
space temperature must permanently rise to 73F (22.8C) Flow Controls The proper selection of the mixing box serv-
before CAD-2 can be fully opened. The offset error will ing each workstation is of critical importance. Each mixing
increase as the spring range increases or as the thermostat box serves the dual purpose of providing accurate control of
gain is reduced. Sensor and set-point dial error are always the total air supply to the subzone and of modulating the ratio
additional to the offset error. of cold and hot air to satisfy requirements of the space
Therefore, in order to control the clean-room temperature thermostat TC-2.
within 1F (0.6C), it is necessary to use an RTD-type or The total air supply ow to the subzone should equal 60
a semiconductor transistor-type temperature sensor and a air changes per hour plus the exhaust rate from subzone. This
proportional-plus-integral controller, which will eliminate the total air supply rate must be controlled within 5% of actual

2006 by Bla Liptk


1756 Control and Optimization of Unit Operations

ow by FC-4, over a ow range of 3:1. The rangeability of RA CD


HD
nger nger
3:1 is required because as processes change, their associated A nger
RHT FC Control
exhaust requirements will also change substantially. 3 HWS signal to
FC-4 in Figure 8.14b can be set manually, but this setting RHC RHCV Figure
8.14 f
must change every time a new tool is added to or removed FB B

from the subzone. The setting of FC-4 must be done by FB RHIC SP = TIC
individual in-place calibration against a portable hot wire 3 35% RH
Note # 5 SP
6
Note # 3
anemometer reference (Sections 2.2 and 2.13 in Volume 1). L HIC
H 8
Settings based on the adjustments of the mixing box alone >
(without an anemometer reference) will not provide the All other sub-zones
within zone
required accuracy. to mixing box

Some of the mixing box designs available on the market TC


2
are not acceptable for this application. Such unacceptable
FB
designs include the following: Note
INT
R/A
Int Note
R/A DPC #1 # 2 DPC
FB
5 4
Pressure-dependent designs, in which the total ow
TC To
will change with air supply pressure. Only pressure- D/A SP = 100%
2 mixing SP = 100%
NL box
independent designs can be considered, because both PIC Typical sub-zone
7 Note Cold deck (CD) (see gue 8.14b)
the cold and the hot air supply pressures to the mixing #4 nger
box will vary over some controlled minimum. FB Return air (RA)
Hot deck (HD)
nger
Low rangeability designs. A 3:1 rangeability with an nger
> : High selector > : High limit < : Low selector < : Low limit
accuracy of 5% of actual ow is required. NL : Nonlinear controller DPC : Damper position controller
FB : External feedback signal to D/A : Direct acting controller
Selector or override designs. In these designs either eliminate reset windup R/A : Reverse acting controller
ow or temperature is controlling on a selective basis. INT: intergral only controller, set for ten times the integral time in PIC-7 or RHIC-3

Such override designs will periodically disregard the


FIG. 8.14d
requirements of TC-2 and will thus induce upsets,
Typical zone control system that is under envelope control. Note 1:
cycling, or both.
This is the opening of the most-open hot air damper. HAD-2 (shown
in Figure 8.14b) which is fully open when the TC-2 output is min-
If the mixing box is selected to meet the aforementioned imum. Note 2: This is the opening of the most-open cold air damper.
criteria, both airow and space temperature can be accurately CAD-2 (shown in Figure 8.14b) is fully open when the TC-2 output
controlled. is maximum. Note 3: HIC-8 sets the maximum limit for the CD
temperature at approximately 70F (21C). Note 4: As vacuum
Optimization of the Zones increases (and pressure decreases), the output of PIC-7 also
increases. Note 5: The controller action is D/A in summer, R/A in
Each row of workstations shown in Figure 8.14a is called a winter.
zone, and each zone is served by a cold deck (CD), a hot
deck (HD), and a return air (RA) subheader. These subhead-
ers are frequently referred to as fingers. The control devices
serving the individual workstation (subzones) will be able to damper is fully open, the associated control loop is out of
perform their assigned control tasks only if the zone nger control. Therefore, the purpose of the damper position con-
conditions make it possible for them to do so. trollers (DPCs) in Figure 8.14d is to prevent the correspond-
For example, RAR-1 in Figure 8.14b will be able to ing dampers from having to open fully.
control the subzone pressure as long as the P across the Lastly, the relative humidity in the return air must also
damper is high enough to remove all the return air without be controlled within acceptable limits. Therefore, at the zone
requiring the damper to open fully. As long as the dampers level there are ve controlled, or limit variables but only one
are throttling (neither fully open nor completely closed), manipulated variable:
DPS-1 in Figure 8.14b is in control.
PIC-7 in Figure 8.14d is provided to control the vacuum
in the RA nger and thereby to maintain the required P
across RAR-1. PIC-7 is a nonlinear controller with a fairly Limit or Controlled Variables Manipulated Variable
wide neutral band. This protects the CD nger temperature RA pressure TIC-6 set point
(TIC-6 set point) from being changed until a sustained and RA relative humidity
substantial change takes place in the detected RA pressure.
Max. CAD opening
Similarly, the mixing box in Figure 8.14b will be able to
Max. HAD opening
control subzone supply ow and temperature as long as its
dampers are not forced to take up extreme positions. Once a Max. TIC-6 set point

2006 by Bla Liptk


8.14 Clean-Room Controls and Optimization 1757

Constraint #1 increased, more CD air will be needed to accomplish the


Cold deck nger temperature Constraint # 3 required cooling. Increasing the ratio of humidity-controlled
is at its maximum limit of Return air excess is
signaled by PIC-7 CD air in the zone supply (HD humidity is uncontrolled) also
about 70F (21C)
(RA nger pressure high) brings the zone closer to the desired 35% RH set point.
Constraint # 2 In this envelope control system, the following conditions
Most open cold air damper
(CAD-2) of all mixing boxes will cause an increase in the TIC-6 set point:
within this zone is fully open
Return air shortage detected by a drop in the RA nger
pressure (increase in the detected vacuum) measured
by PIC-7. An increase in the TIC-6 set point will
Response is to decrease increase the CD demand (opens all CAD-2 dampers
cold deck ow by
decreasing TIC-6 set point
in Figure 8.14b), which in turn lowers the HD and,
therefore, the RA demand.
Control envelope Controlled
for determining variable TIC-6 Hot air damper in mixing box (HAD-2 in
cold deck supply set point Figure 8.14b) is near to being fully open. This, too,
temperature necessitates the aforementioned action to reduce HD
Response is to increase demand.
cold deck ow by RA humidity does not match the RHIC-3 set point.
increasing TIC-6 set point
This condition also necessitates an increase in the
proportion of the CD air in the zone supply. Because
the moisture content of the CD air is controlled, an
increase in its proportion in the total supply will help
control the RH in the zone.
Constraint #5
Most open hot air damper
(HAD-2) of all mixing boxes On the other hand, the following conditions will require
within this zone is fully open
Constraint #6 Constraint #4
a decrease in the TIC-6 set point:
Return air shortage is Return air humidity error
being signaled by PIC-7 in RA nger is too high
(RA nger pressure low)
Return air excess detected by a rise in RA nger
pressure (drop in the detected vacuum) measured by
FIG. 8.14e PIC-7.
For optimized control of the cold deck temperature, a constraint Cold air damper in mixing box (CAD-2 in Figure 8.14b)
envelope-based control system can be used. is fully open.
CD nger temperature exceeds 70F (21C). This limit
is needed to keep the CD always cooler than the HD.
Figure 8.14d shows the control loop conguration
required to accomplish the aforementioned goals. It should Plantwide Optimization
be noted that dynamic lead/lag elements are not shown and
that this loop can be implemented in either hardware or In conventionally controlled semiconductor plants, both the
software. temperature and the humidity of the main CD supply air are
xed. This can severely restrict the performance of such
Envelope Optimization Whenever the number of control systems, because as soon as a damper or a valve is fully open
variables exceeds the number of available manipulated vari- (or closed), the conventional system is out of control.
ables, it is necessary to apply multivariable envelope control. The optimized control system described here does not
This means that the available manipulated variable (TIC-6 suffer from such limitations, because it automatically adjusts
set point) is not assigned to serve a single task but is selec- both the main CD supply temperature and the humidity so
tively controlled to keep many variables within acceptable as to follow the load smoothly and continuously, never allow-
limitswithin the control envelope shown in Figure 8.14e. ing the valves or dampers to lose control by fully opening or
By adjusting the set point of TIC-6, it is possible to closing. The net result is not only increased productivity but
change the cooling capacity represented by each unit of CD also reduced operating costs.
air. Because the same cooling can be accomplished by using A semiconductor production plant might consist of two
less air at lower temperatures or by using more air at higher dozen zones. Each of the zones can be controlled as shown
temperatures, the overall material balance can be maintained in Figure 8.14d. The total load represented by all the zones
by manipulating the set point of the heat balance controls. is followed by the controls shown in Figure 8.14f. The overall
Return air humidity can similarly be affected by modu- control system is hierarchical in its structure: The subzone
lating the TIC-6 set point, because when this set point is controls in Figure 8.14b are assisted by the zone controls in

2006 by Bla Liptk


1758 Control and Optimization of Unit Operations

Setpoint to HWS temperature


(TIC-11) FB2 D/A
Least-open RHCV
VPC < Fingers serving
5 one typical zone
%x Y = SP
VPA All
100 other
<> 80 5
zones
60
40 Y Set at 95%
20 x
SP f(x) <
5 0 5 10 15 %Y Most-open RHCV
FB2 RHCV
SP FB1 opening
D/A PID
AMC TIC TT B signal
1 1 D/A from
PID
SP Figure 8.14 d
DPtTC <> RHIC
OA
High DPtT
2 R/A 3 Highest
accuracy FB1 Y = SP RH
2
CD
Humidity and SF
temperature Y Set at 8% RH
PC Note
controls 9 #1 f(x)
RHA
Y (% RH) X 3
Relief damper Lowest
RH
< 38
FC
FC Make-up
damper 35 All
Note other
R/A #2 D/A X < zones <
PC PC
1" 6 7 3" 30 32 34 36 % RH
(0.25 kPa) (0.75 kPa) HD
RF RH in each
PC Note D/A RA nger from
10 #1 TC 72F
RA 8 (22C) A Figure 8.14 d

FIG. 8.14f
The plantwide control system handles the total load, the sum of the loads of all the zones in an optimized manner. Symbols: AMC =
Controller with positions for automatic-manual-cascade modes of operation. DPtIC = Dew point controller. INT = Controller with integral
control action only. Its setting is to be 10 times the integral time setting of the associated process controller(s). PID = Controller with
proportional, integral, and derivative control modes. VPC = Valve position controller. Note 1: This pressure controller keeps the lowest of
all finger pressures at a value above some minimum. It modulates the fan volume or speed and starts extra fan units to meet the load. When
the load drops, the unnecessary fans are stopped by flow (not pressure) control. Note 2: If the pressure rises above 1 in. H2O (0.25 kPa),
the relief damper starts to open, and if the pressure drops below 3 in. H2O (0.75 kPa), the makeup damper opens. This opening is limited
by TC-8, which prevents the HD temperature from dropping below 72 (22C). Between the settings of PC-6 and PC-7, both dampers are
tightly closed and the suction pressure floats.

Figure 8.14d, and the plantwide controls in Figure 8.14f Material Balance Controls The plantwide material balance
guarantee that the zone controllers can perform their tasks. is based on pressure control. PC-9 and PC-10 modulate the
The interconnection among the levels of the hierarchy is variable-volume fans so as to maintain a minimum supply
established through the various valve and damper position pressure in each of the CD and HD ngers. The suction side
controllers (VPCs and DPCs). These guarantee that no throt-
tling device, such as mixing boxes or RHC valves, anywhere The manipulated variables are the
in this plant will ever be allowed to reach an extreme position. setpoints of TIC-1 and TIC-11 which
determine the plantwide air and
Whenever a control valve or a damper is approaching the water supply temperatures
point of losing control (nearing full opening), the load- Plantwide
following control system at the next higher level modies controls The controlled variables are the
(see Figure .14f ) VPC
the air or water supply conditions so that the valve or damper openings of the reheat coil
in question will not need to open fully. The hierarchical control valves (RHCV)
Couple of dozen
control scheme is depicted in Figure 8.14g. zone level control systems Manipulated variable is the
The overall plantwide control system shown in Figure 8.14f (see Figure 8.14d) setpoint of TIC-6, which sets
can be viewed as a exible combination of material balance the CD supply temperature
to that zone DPC
and heat/humidity balance controls. Through the load-follow-
Couple of hundred subzone
ing optimization of the set points of TIC-1 and TIC-11, the level control systems
The controlled variables
heat balance controls are used to assist in maintaining the (see Figure 8.14b)
are the damper openings
material balance around the plant. For example, if the mate- within the mixing boxes
rial balance requires an increase in airow and the heat bal-
ance requires a reduction in the heat input to the space, both FIG. 8.14g
requirements will be met by admitting more air at a lower The overall control architecture in a semiconductor manufacturing
temperature. plant is hierarchical in structure.

2006 by Bla Liptk


8.14 Clean-Room Controls and Optimization 1759

of the CD supply fan station is open to the outside and will These purposes are accomplished by f(x), which keeps
draw as much outside air as the load demands (Figure 8.14f). the least-open valve at approximately 12% opening as long
The suction pressure of the HD supply fan station is an as the most-open valve is less than 90% open. If this 90%
indication of the balance between RA availability and HD opening is exceeded, f(x) prevents the most-open valve from
demand. This balance is maintained by PIC-7 in Figure 8.14d, fully opening. It does so by lowering the set point of VPC-
at the zone level. Because this controller manipulates a heat 5, which in turn will increase the set points of the TICs.
transfer system (RHCV), it must be tuned for slow, gradual Increasing the set point of TIC-1 reduces the load on the
action. This being the case, it will not be capable of respond- most-open RHCV, whereas increasing the TIC-11 set point
ing to sudden upsets or to emergency conditions, such as the increases the heating capacity at the reheat coil. Through this
need to purge smoke or chemicals. method of load-following and through the modulation of
Such sudden upsets in material balance are corrected by main supply air and water temperatures, all zones in the plant
PC-6 and PC-7 in Figure 8.14f. PC-6 will open a relief will be kept under stable control if the loads are similar in
damper if the suction pressure is high (vacuum is low), and each zone.
PC-7 will open a makeup damper if it is low (vacuum is
high). In between these limits, both dampers will remain Mechanical Design Limitations All control systems in-
closed and the suction pressure will be allowed to oat. cluding this onewill lose control when the design limits of
the associated mechanical equipment are reached or if the
Heat Balance Controls Heat balance also requires a multi- dissimilarity in load distribution is greater than that which was
variable envelope control system (similar to that shown in anticipated by the mechanical design. Therefore, if a condition
Figure 8.14e), because the number of controlled variables ever arises in which one zone requires large amounts of cooling
exceeds the number of available manipulated variables. (associated RHCV closed) while at the same time some other
Therefore, the plantwide air and water supply temperature zone requires its nger reheat coil valve to be fully open, then
set points (TIC-1 and TIC-11) are not adjusted as a function the control system cannot control both.
of a single consideration but are selectively modulated to In such a case, the control system must decide which
keep several variables within acceptable limits inside the condition it is to correct. The control system in Figure 8.14f
control envelope (Figure 8.14e). is so congured that it will give rst priority to preventing
By adjusting the set points of TIC-1 and TIC-11, it is the RHCV valve from fully opening. Therefore, if as a result
possible to adjust the cooling capacity represented by each of mechanical design errors or because of the misoperation
unit of CD supply air and the heating capacity of each unit of the plant there is no CD supply temperature that can keep
of hot water. This then provides not only for load-following all valves from fully closing or from fully opening, then the
control but also for minimization of the operating costs. Cost control system will allow some RHCV valves to close while
reductions are accomplished by minimizing the HWS tem- preventing all of them from fully opening.
perature and by minimizing the amount of simultaneous cool- Whenever such a condition is approaching (that is, when
ing and reheating of the CD air. the difference between the opening of the most-open and the
This control envelope is so congured that the following least-open valves reaches 95%), a valve position alarm (VPA-
conditions will decrease the TIC set points (both TIC-1 and 5) is actuated. This allows the operator to check the causes
TIC-11): of such excessively dissimilar loads between the zones and
to take corrective action by revising processes, relocating
1. The least-open RHCV is approaching full closure. tools, modifying air supply ducts, or adding or removing
2. CD supply temperature is at its maximum limit. mixing boxes.
By keeping all RHCV valves from being nearly closed,
On the other hand, the following conditions will require this control system simultaneously accomplishes the follow-
an increase in the TIC set points: ing goals:

1. The most-open RHCV is approaching full opening. 1. Eliminates unstable (cycling) valve operation by not
2. The CD supply temperature is at its minimum limit. allowing valves to operate nearly closed
2. Minimizes pumping costs by minimizing pressure
The set point of VPC-5 in Figure 8.14f is produced by a losses through throttling valves
function generator, f(x). The dual purposes of this loop are 3. Minimizes heat pump operating costs by minimizing
1) to prevent any of the reheat coil control valves (RHCVs) the required hot water temperature
from fully opening and thereby losing control, and 2) to force 4. Provides a means of detecting and thereby smoothly
the least-open RHCV toward a minimum opening, so as to following the variations in the plantwide load
minimize wasteful overlap between cooling and reheat. All
this is done while keeping any of the RHCVs from fully Humidity Controls At the zone level, the RA humidity is
closing as long as possible. controlled by RHIC-3 in Figure 8.14d. In addition, the dew

2006 by Bla Liptk


1760 Control and Optimization of Unit Operations

point of the main CD air supply must be modulated. The Exhaust Air Controls The exhaust air controls at the sub-
main CD supply temperature is already being modulated to zone level are shown in Figure 8.14b. At this level, the control
follow the load. This is accomplished by measuring the rel- element is a two-position damper, EAD-5. When the work-
ative humidity in all RA ngers (RHT-3 in Figure 8.14d) and station is functioning, its operable sash is open. This condi-
selecting the one nger that is farthest away from the control tion is detected by the door position limit switch, ZSC-5,
target of 35% RH. which in that case fully opens the two-position damper. When
The control system is similar to the TIC set point opti- the workstation is out of service, its operable sash is closed,
mization loop discussed earlier. The rst elements in the loop and therefore the door switch closes EAD-5 to its minimum
are the selectors shown in Figure 8.14f. They pick out the position.
return air ngers with the highest and the lowest relative This minimum damper position still provides sufcient
humidity readings. The purpose of the loop is to herd all air exhaust ow from the workstation to guarantee the face
RH transmitter readings in such a direction that both the velocity needed for operator safety. In other words, when the
highest and the lowest readings will fall within the acceptable sash is closed, the air will enter the workstation over a smaller
control gap limits of 35% 3% RH. This is accomplished by area; therefore, less exhaust airow is required to provide the
sending the highest reading to RHIC-3 in Figure 8.14f as its air inow velocity that is needed to keep the chemical fumes
measurement and also sending the lowest reading to this from leaking out. Through this technique, the safety of oper-
RHIC-3 as its modied set point. ation is unaffected, and operating costs are lowered because
A humidity change in either direction can be recognized less outside air needs to be conditioned if the exhaust airow
and corrected through this herding technique. The set point is lowered.
of RHIC-3 is produced by the function generator, f(x). Its In order for EAD-5 to maintain the required exhaust air
dual purposes are to prevent the most humid RA nger from ow accurately, it is necessary to keep the vacuum in the
exceeding 38% RH and to keep the driest RA nger humidity exhaust air collection ductwork at a constant value. This
from dropping below 32% RH, as long as this can be accom- pressure control loop is depicted in Figure 8.14h. In each
plished without violating the rst goal. zone exhaust nger, the PC-1 shown in Figure 8.14h keeps
These purposes are accomplished by keeping the set the vacuum constant by throttling the EAD-1 damper as
point of RHC-3 at 35% as long as the driest nger reads 34% required.
RH or more. If it drops below that value, the set point is In order for these dampers to stay in control while the
raised to the limit of 38% RH in order to overcome this low- exhaust airow varies, it is important to keep them from fully
humidity condition, without allowing excessive humidity in opening. This is accomplished rst by identifying the most-
the return air of some other zone. open nger damper (low selector) and then by comparing its
This control strategy and the RHIC-3 controller in opening with the set point of the damper position controller,
Figure 8.14d will automatically respond to seasonal changes DPC-2.
and will give good RH control as long as the loads in the The task of this controller is to limit the opening of the
various zones are similar. If the humidity loads are substan- most-open EAD-1 to 80% and to increase the vacuum in the
tially dissimilar, this control system is also subject to mechan- main EA header if this opening would otherwise exceed 80%.
ical equipment limitations. In other words, the mechanical Therefore, if the measurement of DPC-2 exceeds 80%, the
equipment is so congured that addition or removal of mois- vacuum set point of PC-3 is increased (pressure setting
ture is possible only at the main air supply to the CD. Con- lowered). This in turn will increase the operating level of the
sequently, if some zones are moisture-generating and others exhaust fan station (EAF).
require humidication, this control system can respond to The limits on the set point of DPC-2 will prevent mechan-
only one of these needs. ical damage, such as collapsing of the ducts as a result of
Therefore, if the lowest RH reading is below 32% while excessive vacuum or manual misoperation. The reasons for
the highest is already at 38%, the low-humidity condition integral action and external feedback are the same as in the
will be left uncontrolled, and the high-humidity zone will be case of all other damper and valve position controllers dis-
controlled to prevent it from exceeding the 38% RH upper cussed earlier.
limit. Allowing the minimum limit to be temporarily violated Figure 8.14h also shows a glycol-circulating heat recov-
while maintaining control on the upper limit is a logical and ery loop that can be used as shown to preheat the entering
safe response to humidity load dissimilarities between zones. outside air or that can be used as a heat source to a heat pump
It is safe because the intermixing of the return airs will allow in the winter (not shown). In either case, the operating cost
self-control of the building by transferring moisture from of the plant in the winter is lowered by recovering the heat
zones with excess humidity to ones with humidity deciency. content of the air before it is exhausted.
Whenever the difference between minimum and maxi- The discharging of chemical vapors into the atmosphere
mum humidity readings reaches 8% RH, the RHA-3 alarm is regulated by pollution considerations. The usual approach
is actuated. This will alert operators that substantial moisture is to remove most of the chemicals by adsorption and scrub-
load dissimilarities exist so that they can seek out and elim- bing prior to exhaustion of the air. An added measure of
inate the causes. safety is provided by exhausting the air at high velocity, so

2006 by Bla Liptk


8.14 Clean-Room Controls and Optimization 1761

CD S C H H
C R OA AVC
C C
C C

Pump-around loop (glycol)


Note #1
EAF Pollution
H control
Exhaust air header
R equipment
C
PT Actuator

EAD
1 Int R/A FB
SP = 80%

< DPC < < PC


FO
2 3
0100%
R/A Wafer
All other FB increasing vacuum valve
ngers decreases ouput, body
D/A which lowers
PC output fan volume
1 increases
if vacuum Adjustable
increases orice
EA
nger
(typical)

FIG. 8.14h
Exhaust air optimization controls are used to keep the vacuum in the exhaust air collection ductwork at a constant value and to maximize
heat recovery. Note 1: When the need for dehumidification in the summer results in excessive overcooling of the CD air supply, and therefore
in increased demand for reheat at the CD fingers, the pump-around economizer loop is started to lower operating cost. It also increases
efficiency by reducing the degree of overcooling, thereby lowering the need for reheat.

as to obtain good dispersion in the atmosphere. Because the Therefore, the benet of increased productivity is a result not
volume of air being exhausted varies, an air velocity control- of higher initial investment but of better control system
ler (AVC in Figure 8.14h) is used to maintain the velocity of design.
discharge constant. This is accomplished by modulation of a It should be emphasized that the described load-following
variable orice iris damper, also illustrated in Figure 8.14h. optimization envelope control strategy is far from being typ-
ical of todays practices in the semiconductor manufacturing
industry. In fact, it has never been fully implemented, and
CONCLUSIONS many plants are still operated under conventional HVAC
controls.
The productivity of semiconductor manufacturing plants can Therefore, the conclusion that yields will increase and
be greatly increased and the operating costs can be lowered operating costs will drop when such improved control sys-
through the control and optimization methods described in tems are installed is an assumption. This appears to be sup-
this section and by such added control system features as: ported by the results of partial system implementations that
the author implemented at IBM plants and by the experiences
Low leakage dampers (0.5 CFM/ft at 4 in. H2O P,
2
in other industries but will remain an assumption until a
or 2.5 1/s/m at 1 kPa P)
2
semiconductor manufacturing plant that includes all the fea-
Accurate airow metering for material balance and tures of such modern controls is in operation.
pressurization loss control
Pump-around economizers (see Figure 8.14h)
Bibliography
The initial cost of the previously described control system
is not higher than the cost of conventional systems, because ACHIH, Air Sampling Instrumentation of Atmospheric Contaminants, 9th
the added expense of more accurate sensors is balanced by ed., Cincinnati, OH: American Conference of Governmental Industrial
the reduced installation cost of distributed shared controls. Hygienists (ACHIH), 2001.

2006 by Bla Liptk


1762 Control and Optimization of Unit Operations

AIHA, Workplace Environmental Exposure Level Guide Series on Toxic Liptk, B. G., Savings through CO2-Based Ventilation, ASHRAE Journal,
Chemicals, American Industrial Hygiene Association (AIHA), 2002. July 1979.
Carlson, D. R., Temperature Measurement in Process Control, InTech, Liptk, B. G., Save Energy by Optimizing Your Boilers, Chillers, and
October 1990. Pumps, Instrumentation Technology, March 1981.
Cooper, F. G., Low Pressure Sensing and Control, InTech, September Nordeen, H., Control of Ventilation Air in Energy Efcient Systems,
1992. ASHRAE Symposium #20, Paper #3.
Daryanani, S., Design Engineers Guide to Variable Air-Volume Systems, Shih, J. Y., Energy Conservation and Building Automation, ASHRAE
Actual Specifying Engineer, July 1974. Paper #2354.
DHO/Atlanta Corp., Conserving Energy, Powered Induction Unit, Data Spielvogel, L. G., Exploding Some Myths about Building Energy Use,
Sheet #1, May 1, 1974. Architectural Record, February 1976.
Kerin, T. W., and Katz., E. M., Temperature Measurement in the 1990s, Stillman, R. B., Systems Simulation Engineering Report, prepared for IBM-
InTech, August 1990. RECD, December 10, 1971.
Kusuda, T., Intermittent Ventilation for Energy Conservation, ASHRAE Warmoth, D., Temperature Measurement and Control, Measurements and
Symposium #20, Paper #4. Control, February 1986.
Liptk, B. G. (Ed.), Carbon Dioxide Sensors, in Environmental Engineers Woods, J. E., Impact of ASHRAE Ventilation Standards 6273 on Energy
Handbook, Vol. II, Section 4.6, Radnor, PA: Chilton Books, 1975. Use, ASHRAE Symposium #20, Paper #1.
Liptk, B. G., Reducing the Operating Costs of Buildings by the Use of Yan, W. B., and Mallon, T., "Breakthrough Technology Measures Parts-per-
Computers, ASHRAE Transactions, Vol. 83, Part 1, 1977. Trillion Moisture in Gases," Chem. Res., March 2002.

2006 by Bla Liptk

You might also like