You are on page 1of 8

engineers newsletter

volume 332 providing insights for todays hvac system designer

Better Part-Load Dehumidification


regardless of the cooling load. The
system therefore must deliver warmer
[its not a pipe dream] supply air at part load to avoid
overcooling the space.

Chilled water vs. DX coils. In a


from the editor heat and moisturelowering the dry-
typical chilled water application, a
While humidity control is apt to bulb temperature to the target (74F in
modulating valve reduces system
imply special applications, such as Figure 1) and maintaining the relative
capacity by throttling the rate of water
museums or printing plants, managing humidity (in this case, at 52% RH). This
flow through the cooling coil. Figure 2
humidity should be a key design full-load dehumidification performance
(p. 2) shows how this affects the
consideration in any HVAC application. certainly seems adequate, but what
supply air leaving the coilthe warmer
This EN outlines the challenge of happens at part load?
coil surface that results from less
dehumidifying at part load and
The basic constant-volume system water flow provides less sensible
describes ways to enhance the
supplies an unchanging amount of air, cooling (raising the supply-air
performance of three commonly used
temperature) and removes less
types of HVAC systems: chilled water
moisture from the passing air stream.
terminal, single-zone direct expansion
(DX), and central VAV. Figure 1. Single-zone, constant-volume, In DX applications, the compressors
mixed-air system
cycle off regularly to avoid overcooling.
Recent research clearly shows how
compressor cycling affects part-load
Why its hard to manage dehumidification (Figure 3, p. 2). When
humidity at part load the compressor starts, the coil surface
quickly becomes cold enough to
The most basic HVAC system supplies provide both sensible cooling (gray
a constant quantity of air to a single region) and latent cooling (also known
zone; common examples include as dehumidification; red region).
packaged terminal air conditioners,
small packaged rooftop units, unit Notice that several minutes elapse
ventilators, and fan-coils. A thermostat after the compressor starts but before
compares the dry-bulb temperature in the moisture that condenses on the
the occupied space to a setpoint and
then modulates the systems cooling
capacity accordingly (Figure 1). Oversized airflow and dehumidification dont mix

Determining the proper relationship between Higher-than-necessary airflow also can result if
At full load, the system mixes outdoor
airflow and cooling capacity is key to designing a you base the design airflow on a rule-of-thumb
air with recirculated return air. The
system with adequate dehumidification capacity rather than a calculation of the space sensible
mixture then passes through a cooling at all load conditions. The flexibility of applied load. The old standbys of 400 cfm/ton, 1 cfm/ft,
coil, where its sensibly cooled and systems, such as chilled water air handlers, and 6 air changes/hr were formulated before the
dehumidified. When the supply air normally lets you select equipment based on a advent of higher ventilation rates, tighter
reaches the space, it absorbs sensible specific airflow rate (cfm) and a specific cooling building envelopes, and high-efficiency lighting.
capacity (tons). By contrast, the prematched
components of packaged DX equipment Of course, excess supply airflow and the
typically limit your selection to a finite cfm/ton increased humidity that accompanies it also
range of application. can result from the addition of safety factors
or a conservative estimate of the space
Selecting a larger unit to provide the required sensible load.
cooling capacity sometimes yields a higher-than-
necessary supply airflow. The result is warmer Selecting equipment based on accurate load
supply air and, in non-arid climates, less calculations is the best way to assure thermal
dehumidification. comfort at all load conditions.

2004 American Standard Inc. All rights reserved 1


Figure 2. Part-load dehumidification with modulated chilled water flow compressor operates for less of each
hour, the system provides little or no
dehumidification. Because of the brief
on periods, the coil doesnt generate
enough condensate to drain into the
pan below; and long off periods allow
more condensate to re-evaporate from
the coil.

Note: The relationship between


compressor run-time and
dehumidification capacity (Figure 5)
also demonstrates the effect of
oversizing constant-volume DX
equipment. The compressor runs even
less of each hour, resulting in warmer
coil surface actually falls to the drain re-evaporation of moisture from the supply air and less dehumidification.
pan below. Like raindrops on a window, coil surface, the humidity ratio of the
droplets on the coil fins must air is higher when it leaves the coil Figure 6 compares basic, constant-
accumulate enough mass for gravity to than when it entered. Then the leaving- volume dehumidification at two
overcome surface tension. air wet-bulb temperature remains outdoor conditions: full load (design)
relatively constant as the moisture and part load (cooler but more
When the compressor stops, sensible evaporates; if the coil dries completely, humid). 2 Notice that space humidity
cooling drops off dramatically; the leaving and entering air conditions climbs from 52% RH at full load to
meanwhile, latent cooling not only falls match. 67% RH at part load. Thats because
to zero but actually becomes negative the sensible cooling capacity of a
as the condensate on the coils surface Bear in mind that the test data in constant-volume system decreases to
re-evaporates into the supply air Figure 3 and Figure 4 was based on match the smaller sensible cooling
stream. 45-minute on/off cycles. In actual
operation, compressor off-time
Figure 4 shows the psychrometric depends on sensible load and may last 1 To aid coil selections and performance analyses,
effect of compressor cycling on the air only a few minutestoo briefly to the Trane psychrometric chart includes coil
leaving the coil. While the compressor permit the coil to dry completely curves that approximate the part-load
is on, the leaving air is cold and dry. But dehumidification of cooling coils (whether chilled
between compressor starts.
water or refrigerant). These curves can be
when the compressor stops, the
invaluable for analyzing part-load performance.
leaving air quickly warms. Due to Figure 5 shows net dehumidification
capacity as a function of compressor 2 This example, which appeared in a previous
duty cycle or percent run-time. 1 (Net Engineers Newsletter (It may take more than
Figure 3. Part-load dehumidification dehumidification equals all of the you think to dehumidify with constant-volume
(cycling compressor, constant-volume fan) systems, volume 29-4), used an elementary
moisture that condenses on the coil school classroom to demonstrate full-load versus
minus the condensate that re- part-load dehumidification performance of a
evaporates.) Notice that as the basic, constant-volume system.

Figure 4. Effect of compressor cycling on air leaving the cooling coil

2 Trane Engineers Newsletter volume 332 providing insights for todays HVAC system designer
Figure 5. Net dehumidification as a function of compressor run-time Figure 7. Automatic fan-speed adjustment
for chilled-water terminal units

the valve to throttle the rate of chilled


water flow through the coil. At some
point, based on valve position (for
example), the unit controller switches
load. Any latent cooling the fan to low speed. Less airflow
(dehumidification) capacity is purely Chilled water means that colder supply air is needed
coincidental, whether the cooling-coil terminal systems to maintain the target space
medium is chilled water or refrigerant. temperature. The control valve opens,
As the load diminishes, the system In a chilled water terminal system, a chilling the coil surface and allowing
delivers ever warmer supply air. Some central plant distributes cold water to the coil to remove more moisture from
dehumidification may occur but only terminal units (such as unit ventilators, the passing air stream.
if the sensible load is high enough. fan-coils, and blower-coils) located
within or near each conditioned space. Note: When the unit controller
To avoid moisture problems, its Each terminal unit is a single-zone, switches the fan to low speed, it also
important to understand how well the constant-volume, mixed-air system should automatically adjust the
HVAC system will dehumidify at both whose part-load dehumidification can position of the outdoor air damper to
full load and part load, and to know be improved by adding automatic fan- assure proper ventilation.
how to improve its performance. speed adjustment, face-and-bypass
Heres a brief overview of ways to dampers, a subcoolreheat strategy, Face-and-bypass dampers provide
improve the dehumidification and/or a dedicated outdoor-air system. an alternate means of controlling coil
performance of three familiar system capacity. The cooling coil runs wild
typeschilled water terminal, single- Automatic fan-speed adjustment. (constant water flow rate, constant
zone DX, and central VAV. Terminal units with multispeed supply entering water temperature) and the
fans first reduce cooling capacity by zone thermostat modulates the
automatically switching to a slower fan position of the linked dampers.
speed. At full load (Figure 7), the fan
operates at high speed and the control By itself, mixed-air bypass typically
valve is wide open. As the cooling load offers little benefit in non-arid climates
decreases, the thermostat modulates because the diverted air (Figure 8, p. 4)
is relatively humid at many part-load
conditions. However, combining
mixed-air bypass with automatic fan-
Figure 6. Comparison of full- and part-load dehumidification (basic, constant-volume system) speed adjustment can improve
dehumidification significantly.

Ideal return-air bypass (full coil face


available as the face damper closes)
directs all incoming outdoor air through
the cooling coil. Consequently, its a
better choice in situations where the
humidity ratio of the outdoor air is
higher than that of the return air.

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 332 3
Figure 8. Mixed-air and return-air bypass arrangements the dehumidification burden on the
terminal units; and,
cold enough, whenever possible,
to offset part of the sensible load in the
space. Neutral conditioned air
requires not only more capacity from
the terminal units but also reheat at the
dedicated outdoor-air unit.

Specify the dedicated outdoor-air unit


to limit relative humidity to some
maximum level (typically 6065% RH)
at worst-case conditions. Designing for
drier indoor air requires larger
Note: The design of terminal units, boiler; reduce system operating costs equipment and increases operating
such as unit ventilators, affords little by avoiding the use of new energy costs. Also consider communicating
space for return-air bypass. Often, face for reheat; and enable compliance with controls to optimize energy use,
dampers in this arrangement block part local codes and energy standards, such improve comfort (two-pipe systems),
of the cooling coil as they close. Less as ASHRAE Standard 90.1. 3 and independently limit humidity
face area at part load severely limits during unoccupied periods. 4
the coils ability to dehumidify. Dedicated outdoor-air system.
Directing all outdoor air through a
Subcoolreheat. Adding a heat dedicated air handler can eliminate the
source downstream of the cooling coil sensible and latent cooling loads Single-zone DX systems
and a humidity sensor in the space associated with ventilation. The
Equipment in this category is installed
makes it possible to directly control conditioned air then passes from the
in or near the space and includes
both temperature and humidity. air handler directly to the space or to
packaged rooftop units, split systems,
Heres how local terminal units (Figure 9). Each
packaged terminal air conditioners, and
local terminal unit conditions only the
If the detected humidity in the space water-source heat pumps. Each of
recirculated return air to maintain the
exceeds a preset limit, cooling-coil these units is a single-zone, mixed-air
target temperature in the space.
capacity increases to dehumidify the device that contains a constant-volume
supply air. The downstream heating For most efficient performance, make supply fan and a compressor that
coil then warms (reheats) the supply air sure that the conditioned outdoor air is: cycles on and off.
to avoid overcooling.
drier than the space, which offsets Single-zone DX systems are notorious
A boiler can serve the reheat coilbut the latent load in the space and eases for losing humidity control at part load
only if its available to operate during due to the natural cycling operation of
the cooling season. Recovering heat DX equipment and the need for
from the chilled water system for this constant ventilation with outdoor air.
3 Schwedler, M. and D. Brunsvold. 2003.
purpose offers several benefits. It may Oversizing often compounds the
Waterside Heat Recovery in HVAC Systems
permit seasonal shutdown of the (SYS-APM005-EN). La Crosse, WI: Trane. problem (see inset, p. 1.) In
applications that require an unusually
high percentage of outdoor air, the
cfm/ton limitations of packaged units
often make it necessary to select a unit
Figure 9. Dedicated outdoor-air arrangements for chilled water terminal systems
that delivers more airflow than the
cooling load requires at design. But
dont forgetmore airflow means

4 See Trane Engineers Newsletter 30-3 (2001),


Design Tips for Effective, Efficient Dedicated
Ventilation Systems.
conditioned air to
local terminal units

4 Trane Engineers Newsletter volume 332 providing insights for todays HVAC system designer
warmer supply air and less suction temperature from becoming Figure 10. Dedicated outdoor air system
dehumidification at all loads. Such too cold, and perhaps frosting the coil, with single-zone water-source heat pumps
situations demand particular design during low-airflow operation.
care to assure that the DX system will
dehumidify effectively over a wide Note: A variation of this concept is
range of conditions. the single-zone VAV system, which
modulates fan capacity (supply airflow)
to maintain the desired space
Automatic fan-speed adjustment.
temperature and cooling capacity to
In a traditional DX unit with a constant-
maintain the supply-air temperature at
speed supply fan, the fan operates
setpoint.
whenever the space is occupied. By
contrast, in a unit with a multiple-speed
fan, the fan operates at low speed Subcoolreheat. Adding a space-
whenever possible and only switches humidity sensor and a reheat coil
permits direct control of both space compressor and the condenser.
to high speed when the load is large.
temperature and space humidity. Whenever its necessary to avoid
Less supply airflow at part load results
When humidity becomes excessive, overcooling the space, the heat
in a lower supply-air temperature and
cooling capacity increases to exchanger transfers sensible heat from
improves dehumidification. (For proper
adequately dehumidify the air. The the hot refrigerant vapor to the supply
ventilation at low airflow, the unit
reheat coil then warms the supply air air downstream of the cooling coil.
controller should appropriately and
automatically adjust the position of the to avoid overcooling.
outdoor-air damper.) Dedicated treatment of outdoor air.
Reheating the supply air with As in chilled water systems, you can
Combining a multispeed supply fan recovered heat from the refrigeration improve the single-zone DX systems
with multiple compressors (or with a cycle can reduce operating costs by ability to control humidity by adding a
compressor that unloads) further avoiding the use of new energy. It also dedicated outdoor-air handler but
improves dehumidification because it allows the system to meet local energy with an important difference. Its
lengthens the compressor on cycle codes and ASHRAE Standard 90.1. usually preferable to deliver cold air to
when supply airflow (and temperature) Typically, hot gas reheat is the local units, but not when the local
are low. It also helps prevent the accomplished by adding a refrigerant- units are plenum-mounted water-
to-air heat exchanger to the source heat pumps. Most WSHPs do
refrigeration circuit, between the not include mixing boxes, so the
conditioned outdoor air must be
delivered in proximity to the inlet of
each heat pump (Figure 10). To avoid
Make use of ASHRAEs design dew-point condition unwanted condensation, especially
during unoccupied periods, dehumidify
With publication of the 1997 Fundamentals the sensible load in the space at each outdoor
handbook, ASHRAE expanded outdoor design design condition may be quite different.
the outdoor air so that its drier than the
conditions to include peak dew point. Unlike space and reheat it to assure that the
the traditionally used peak dry bulb condition, For HVAC systems that are controlled based on dry-bulb temperature is well above the
which represents hot, mostly sunny days, peak space temperature, it is the space sensible load worst-case dew point in the plenum.
dew point conditions occur when the outdoor that dictates how the system will dehumidify at
air is cooler but loaded with moisture. part load.

Peak dew point can be valuable when


designing a dedicated dehumidification system. Central VAV systems
It can be equally useful for analyzing coincidental
VAV systems typically dehumidify
dehumidification at part load, as provided by an
effectively over a wide range of indoor
HVAC system thats controlled on the basis of
space dry-bulb temperature alone.
loads. As long as any space needs
cooling, the VAV air handler will provide
Realize, however, that the peak dew point supply air at a dew point thats low
seldom occurs during the same month, nor at enough (sufficiently cool and dry) to
the same time of day, as the peak dry bulb. offset the latent load.
Because the month and/or time of occurrence
(which affect solar and roof loads) may be A basic system consists of an
differentas is the outdoor dry-bulb indoor or outdoor central air handler
temperature (which affects conduction loads)

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 332 5
Figure 11. VAV versus CV dehumidification at part load

Investigate the practicality of


delivering colder supply air. Lowering
the supply-air temperature reduces
supply airflow and ultimately lowers
the humidity in the space because
more moisture condenses on the coil.

and a VAV box for each zone. A humidity in the space. It also increases
Closing thoughts
thermostat maintains the target space the supply fans energy consumption
temperature by modulating the volume perhaps enough to negate the cooling Dehumidification performance varies
of supply air through the VAV box. energy savings. with the type of HVAC system. A basic,
Meanwhile, the central supply fan single-zone, constant-volume system
For applications that include SAT reset,
delivers only the necessary amount of may suffice for some applications in
provide one or more humidity sensors
constant-temperature air. certain climates. But more demanding
to override the reset function if space
applicationsparticularly densely
As the sensible cooling load in the humidity exceeds the desired limit.
occupied spaces and humid climates
space decreases, the basic VAV Provide a tempering heat source may require enhanced designs (or a
system delivers less supply air. at the VAV boxes. Each VAV box has a different system type) to adequately
Because the supply air is cool and dry, minimum airflow setting thats based manage or limit indoor humidity.
the relative humidity in our classroom on the performance limits of the
example only rises to 57% at the part- If properly designed, controlled, and
diffusers or terminal, or on the required
load condition, compared to 67% RH operated, the HVAC system can
ventilation in the space. Densely
with the basic constant-volume system effectively dehumidify over a wide
occupied spaces may require relatively
(Figure 11). range of conditions. The key to
high minimum airflow settings to
success is careful analysis of full-load
assure proper ventilation.
To improve the dehumidification of a and part-load performance.
central VAV system: Eventually, the sensible cooling load
becomes small enough that the space Note: The dehumidification
Avoid using SAT reset during the requires less supply airflow than the enhancements mentioned here are
cooling season. Its tempting to raise VAV terminal can deliver. Without discussed in greater detail in Trane
the supply-air temperature (SAT) at tempering (reheat), the system will application manual SYS-APM004-EN,
part-load conditions in an attempt to overcool the space, causing the Dehumidification in HVAC Systems. To
save cooling or reheat energy. But relative humidity to rise and the space obtain a copy, contact your local Trane
warmer supply air means less to feel cold and damp. office or visit www.trane.com/
dehumidification at the coil and higher bookstore.
If using a boiler as the heat source for
tempering, make sure that its available By John Murphy, applications engineer, and
for cooling season operation. Brenda Bradley, information designer, Trane. You
can find this and previous issues of the Engineers
Alternatively, use recovered heat from
Newsletter at http://www.trane.com/commercial/
another part of the system; this option newsletters.asp. To comment, e-mail us at
allows the boiler to be shut down and comfort@trane.com.
avoids using new energy for reheat.

Trane
A business of American Standard Companies Trane believes the facts and suggestions presented here to be accurate. However, final design and
www.trane.com application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
the material presented.
For more information, contact your local Trane
office or e-mail us at comfort@trane.com

6 Trane Engineers Newsletter volume 332 ADM-APN011-EN


get smart. stay current.

educational materials from Trane can help.

application manuals are comprehensive


Applications
reference guides that can increase your
Engineering
Manual Dehumidifying with
working knowledge of commercial HVAC
Dehumidification in
Dedicated Outdoor Air
systems. Topics range from component
HVAC Systems Implications of ASHRAE Standard 90.1. Section 6.3.1 in the 2001 version
of the standard defines requirements for HVAC systems with economizers. In
the case of airside economizers, the section specifies damper characteristics,
how to control the economizer dampers, and how to relieve air from the
building to prevent overpressurization. It also prescribes how and when to shut
off the economizer cycle when the weather is no longer suitable for free
combinations and innovative design concepts
e

to system control strategies, industry issues,


cooling; high-limit shutoff requirements vary by climate and control method.

Although compliance with these requirements minimizes energy use, it may


not provide acceptable humidity control at all operating conditions or in all
climates. For instance, Standard 90.1 permits the use of the fixed-dry-bulb-
g with
temperature high limit in any climate. When applied in a humid locale, the high

and fundamentals.
limit can only disable economizer cooling when the outdoor temperature is
olume Mixed
65F DB (18.4C Air
D B) or higher. A previous example (p. 31) demonstrated what
can happen in a constant-volume system when the shutoff setting is too high; in
that case, the indoor humidity reached 75 percent!

Understand that Standard 90.1 does not mandate an economizer if the cooling
capacity ofWhen
stipulation: each used
local in
HVAC unit is
a humid less than
climate, theeither 65,000 Btu/hr (19 kW) or
e when135,000 Btu/hrdry-bulb
the outdoor (38 kW),temperature
depending on climatewhich is typically true of
is less
esystems with
preceding dedicated
example showsoutdoor-air
what canhandlers
happen and local HVAC terminals. If you
include
conomizer an economizer
setpoint is too high.)anyway, the control
Of course, the requirements in Section 6.3.1 will
not apply.insta
or a particular There fore, you
llation can devise
will depend on a control strategy that more effectively
the
controls in
humidity.
perforation (1/4 inch from right edge of page)

tem operates the economizer mode.

Dehumidifying with
When using fixed dry-bulb temperature for economizer control in a constant-
idental Dehumidification
Dehumidification in HVAC Systems uses basic psychrometric analyses
volume system, choose a shutoff setting that is low enough to avoid bringing
Variable-Volume Mixed Air
mild-but-humid outdoor air into the building. For better dehumidification,
however, consider a more sophisticated control method that uses an indoor
nt-volume HVAC
humidity system
sensor to can be altered
disable to improve
the economizer whenever the relative humidity in
the spacewithout
performance exceedsdirectly controlling space

to review the dehumidification provided by cold coil commercial


60 percent.
the effect of these modifications (described on
In64.
constant-volume
example
Figure classroom
Dual-duct inapplications
Jacksonville,for
VAV terminal which
Florida. Standard
VAV terminal 90.1 does
(Figure require
64). The an air streams mix inside the VAV terminal
primary
economizer, investigate control methods and aresuch as fixed
then enthalpy
delivered to theorspace
electronic
(Figure 65).
hybrid enthalpy.
ntal (indirect) dehumidification 1
Waterside economizing
Resulting relative
Peak dry bulb
humidity, %
As the cooling load in the space decreases, the modulation device that controls
the cool primary air modulates toward its minimum-open position. When the
cooling
Peak dew point Mild, rainy day load drops to the point where the required amount of cool primary air is
comfort-cooling HVAC systems. It also identifies ways to improve
Waterside economizers can satisfy many of the economizer requirements
December 2002 SYS-APM004-EN 52 67 less
73 than the VAV terminals minimum airflow setting, the second modulation

34)
. 32)
defined in Section 6.3.1 of ASHRAE Standard

One way52
52

to provide free
60
65
device
68
90.1 2001 and in local codes.
begins to open. This allows warm primary air to mix with and temper the
cool primary air before it is supplied to the space.
cooling in68a chilled water system is to install a plate
dehumidification, particularly at part-load conditions.
and-frame
adjustable 52 heat exchanger 58 between the
Withchilled
65
furtherwater and condenser-water
decreases in the cooling load, the space will eventually require
loops, upstream of the chillers. When the leaving-tower
heating. To offset anwater is coldheating
increasing enough, load, the VAV terminal mixes the
full circulating 52 it through the 55 heat exchanger60 will satisfy at of
least part of the air
cooling
minimum amount cool primary with ever-increasing amounts of warm
. 37)
reduced
. 39)
load and reduce or eliminate the need
52 64
to operate
primary
66
the chillers.
air. When the heating load becomes large enough, the recirculated
return air is heated before it is delivered to the VAV terminals as warm
primary air.
Chapter topics: sources and effects of indoor moisture; a
ce is based on a classroom in Jacksonville, Florida. See Analysis of
a description of the room and the constant-volume HVAC system serving it.

Figure 65. VAV system with dual-duct air distribution


89 dehumidification primer; dehumidifying with constant-volume mixed
d
Many room terminals, such as fancoils and classroom unit ventilators
air, variable-volume mixed air, and dedicated outdoor air
(Figure 24), include fans that can run at different speeds. Depending on the
equipment, fan speed is controlled manually by a switch or automatically by a
unit controller.

Slowing the fan speed improves the coincidental dehumidification provided by


constant-volume room terminals; it is also the first step to reduce cooling
How to appendices for psychrometrically analyzing dehumidification
capacity. Lets use the example classroom to demonstrate the effect of less
airflow. Assume that the HVAC system provides 1,500 cfm (0.7 m/s) of supply
airflow when the fan operates at its highest speed. As the sensible-cooling load
in the space decreases (Figure 25), the system initially responds by switching to
performance and designing a dedicated outdoor-air system
32 SYS-APM004-EN

Humidity Control during Unoccupied Periods


140 pages; indexed for easy reference
Buildings that are served by VAV systems may require an after-hours source of
reheat energy for example, heating coils at the VAV terminals or warm
plenum air if the VAV terminals are fan-powered. If the VAV system includes an
air handler that exclusively conditions the outdoor air, then the dedicated
Published December 2002
outdoor-air handler also can provide after-hours dehumidification. (The next
chapter discusses dedicated outdoor-air systems in detail.)

68 SYS-APM004-EN

air conditioning clinics are a series of educational presentations that


educate readers about HVAC fundamentals, equipment, and systems.
The recently revamped series now includes full-color student engineers newsletter providing insights for todays
hvac system designer

workbooks, which can purchased individually. a new standard for


Acoustics in the Classroom
from the editor
Education presently ranks high on the
wise to understand how the new
standard will affect school design and
learning spaces, and defines
requirements and guidelines for noise
list of domestic issues, and for good classroom functionality. isolation. It divides learning spaces
reason. Overcrowding, disrepair, and into several categories and sets
obsolescence are widespread and maximum limits for each. The
severe enough to earn schools a D in maximum permissible background-
an assessment of the nations ANSI/ASA S12.602002 sound level for typical classrooms is
infrastructure [1]. Scholastic As the result of a petition by the parent 35 dBA, with a maximum reverberation

engineers newsletters are published as a free service to building


performance is suffering, too. of a hearing-impaired child, the time of 0.6 to 0.7 second (depending
According to the U.S. Chamber of Architectural and Transportation on room volume) [2].
Commerce, more than one-third of the Barriers Compliance Board (Access
people who sought jobs in 1998 lacked Board) enlisted the American National This benchmark differs considerably
the reading and math skills necessary Standards Institute (ANSI) and the from the acoustical environments
for employment. Acoustical Society of America (ASA) to existing in many classrooms (Figure 1,
develop a standard for classroom p. 2). Although there is no exhaustive
The current education reform acoustical design. The culmination of database of measured sound levels in

professionals and are archived at www.trane.com/commercial/library/


movement seeks to close the gap that effortANSI/ASA S12.60, classrooms, there is considerable
between business needs and Acoustical Performance Criteria, Design evidence that background noise varies
scholastic performance by making Requirements, and Guidelines for widely from classroom to classroom

Air Conditioning
states responsible for developing
strong academic standards and then
holding schools accountable for
Schools was completed and
approved in 2002. *
and from school to school, regardless

Clinic
* To obtain a copy, visit http://webstore.ansi.org/
meeting those standards. But more ANSI/ASA S12.602002 details ansidocstore/ and search for S12.60. The

archived_newsletters.asp. Each 4-to-8-page issue tackles a timely topic


classrooms, lower studentteacher acoustical performance criteria for single-copy purchase price is $35 USD.
ratios, and modern equipment may not
be enough. Studies indicate that poor
acoustics interfere with learning and
pose a particular barrier for students Gauging the education market
with special needs. So compelling is Improving the academic performance of than 40 years old) to proper standards.

Psychrometry
the evidence that it led to the recent
approval of an industry standard, which
U.S. students depends, in part, on our
ability to create learning-friendly
With the student population expected to
increase from 53 million to 54.4 million by

related to the design, application and/or operation of commercial,


establishes an ambitious acoustical environments. Unfortunately, our nations 2008, another $73 billion is needed to add
schools are seriously challenged by new facilities.
One of the Fundamental Series
target for learning environments.
overcrowding and disrepair, substandard
plumbing and HVAC systems, inadequate Industry watchers forecast that schools
With school construction projected at technology, and health- and safety-related will continue to lead the nonresidential
more than $31 billion for 2003 (with concerns. market for new construction (particularly
another $42 billion likely by 2008), it is in the Southwest), with investments for
How big is the problem? The U.S. General 2003 estimated at $31.6 billion. Another
Accounting Office estimates that it will $16.4 billion is anticipated to modernize

applied HVAC systems.


cost $112 billion to bring existing K12 existing facilities (primarily in the
public schools (many of which are more Northeast and Midwest) [14], [15].

2003 American Standard Inc. All rights reserved Volume 32, No. 1

engineers newsletter live is a series of 90-minute recordings that


presents technical and educational information on specific aspects of
HVAC design and control. Past topics include: specifying quality sound, TRG-TRC001-EN

high-performance schools, building pressurization, and dedicated


outdoor-air systems.

visit www.trane.com/bookstore for a complete listing of Trane educational materials


use the order form on the back of this page to place your order
publication order form

Get smart. Stay current. Trane publications can help.

unit
Placing your order title order number quantity price a total
Phone 608-787-4153 or 608-787-3684 Dehumidification in HVAC systems SYS-APM004-EN $15 =
Fax 608-783-4705 Air-to-air energy recovery SYS-APM003-EN $15 =
Mail to: Trane Multiple chiller system design and SYS-APM001-EN $15 =
c/o Inland Marketing Services control
3030 Airport Road
Waterside heat recovery SYS-APM005-EN $15 =
La Crosse, WI 54603 USA

perforation (1/2 inch from right edge of page)


Managing building moisture SYS-AM-15 $15 =

Refrigeration system equipment room REF-AM-3 $10 =


design
Billing/ship-to information Water-source heat pump system design SYS-AM-7 $10 =

name =

=
company
=
ship-to address
=
ship-to address (continued)
=
city Shipping and handling b =

state Subtotal =

postal code Taxc =

Grand total d =
country

a All prices are in U.S. dollars ($usd) and are subject to change without notice.
phone number
b Add $10 for order shipped within the United States. For orders shipped outside the U.S., add $ 30 USD. Orders shipped
e-mail address within the U.S. are sent via FedEx Ground and typically are delivered within 3 to 6 business days. Orders shipped outside
the U.S. are sent via DHL and typically are delivered within 4 to 7 business days.
c Apply all applicable taxes to the subtotal. If your company is exempt from paying sales tax, submit your order via fax or mail
and include a copy of the tax exemption certificate.
d Minimum order is $25 USD; orders totalling less than that amount will be billed at $25 USD.
Payment method Return policy
Literature may be returned within 90 days of shipment; call 608-787-4153 or 608-787-3684 for prior authorization. A
VISA 15 percent restocking charge will be charged on all returned material.

MasterCard

American Express

card number

expiration date Visit www.trane.com/bookstore to view the latest listing


name on card
of Trane educational materials

signature

2004 American Standard Inc. All rights reserved

You might also like