New NSM

Air cooled chiller with


screw compressors
and micro-channel coil
NSM – Main features

• Cooling capacity from 300 up to 2000 kW (28 sizes)


[EN14511:2013]

• EER up to 3,3 and ESEER up to 4,15

• Screw compressor (R134a)

• Micro-channel condenser coil

• Shell & tube evaporator

• Fans Erp ready

• Re-designed frame: lighter and more robust


NSM – Main features

NEW V-BLOCK CONFIGURATION


NSM – Competitors
NSM – Competitors
MTA
AXIMA

AIREDALE

CARRIER
CLIMAVENETA
NSM – 6 versions available

NOT SILENCED
• °: standard (EER = 2,7)
SILENCED
° EER 2.7

• L: low noise A EER 3.1


L EER 2.7

• E: high efficiency low noise U EER 3.3 E EER 3.1

• N: very high efficiency low noise N EER 3.3

High efficiency versions (E/N/A/U) have a bigger


• A: high efficiency (EER = 3,1) exchanger compared to the standard versions (°/L)

Low noise versions (L/E/N) have a lower fan speed


• U: very high efficiency (EER = 3,3) compared to the not silenced versions (°/A/U)
NSM – Operating (working) limits
NOT SILENCED
• Working limits based on the size and the
configuration (efficiency version);
• For the silenced versionsv“L” “E” “N” the fans
42°C
work with a lower speed rotation up to a ° EER 2.7 AVERAGE SILENCED
specific outdoor air temperature (table below)
and in this range the noise profile is silenced
type; over this temperature the fans increase
the speed rotation and consequently also the
A EER 3.1 AVERAGE 46°C L EER 2.7

noise level, in order to achieve the working


limit;
• The units 3002 e 3202 have lower limits due to U EER 3.3 AVERAGE 48°C E EER 3.1
the economizer
• All the units can work up to 50°C outdoor air
temperature but at partial cooling load.
AVERAGE 50°C N EER 3.3
NSM – Low noise versions

• In the low noise version are available the same efficiency levels. In this case we will
have greater dimensions as we have a lower air flow rate (+1/+3 V-block)
– At the moment for the NRL exist only the «L» and «E» version with not so high efficiency
(EER=2.0 e EER=2.5)

• Average noise reduction of -8 dB(A) compared to the not silenced version

• Low noise only cooling version (“ L “, “ E “, “ N “)


– Fan speed reducing
– More V-block to maintain a good efficiency level
NSM – Options

XLA (Extra Low Ambient) option


• NSM: It is possible to achieve up to -20°C through switching off one or more V-block;
in this case it is needed:

• J option (EC fans);


• Double insulation for the evaporator
• Anti freeze electric heaters for the hydraulic circuit
• Electric heaters for the wiring box
• (recommended windbreak)

OFF ON ON ON ON OFF
NSM – Options

NSM produces water temperature up to +30°C.

HWT option includes:


• Boosted compressors
• Special electronic expansion valve
NSM – Options

• High water temperature: leaving water temperature up to +30°C


(boosted compressors and electronic expansion valve)

• «Q» option (Tropical):


Full load working with outdoor air temperatures
up to 55°C; availability only with the “N” versions.

o Wiring box with integrated external cooler


o Compressors with boosted motor
o AC fans with working limits up to 70°C outdoor
air temperature
NSM - frame

DCPX Fans wiring


box

Auxiliary Input power


Compressors
wiring box wiring box
NSM – V-block

• The V-Block is composed by 2 coils and 2 fans with a


frame to support them. In the frame there are two
delta sheet to close the structure

• Each V-block rougly provides 130 kW

• Better and easier coil maintenance/replacement

• Air filter for the coil (standard equipment only for


free cooling version and like accessory for the
others)

m
1190 m
NSM – Compressor

• The whole range has been designed using Bitzer compressors CSH
series, from 70 HP size, motor 2 with working limit of 65°C
condensing temperature

• New antivibration devices to reduce the vibrations through the


frame

NS NSM
NSM – Evaporator
• Single evaporator double circuit up to 1400
kW and three circuits at 1850 kW with
standard efficiency (“°”). Compared to the
old NS series we have a benefit in terms of
efficiency and installation.
• Purposes:
• Better seasonal efficiency
• Lowe installation costs
(without hydraulic parallel for a lot of sizes)

430kW 540kW 1.0MW 1.23MW 1.40MW 1.85MW

610kW 1.33kW
NSM – Fans

• EBM fans (D=800 mm)

• Oversized fans (accessory) to get an available static pressure

• EC fan (EBM axitop): +3% ESEER

• The noise level remains the same when the external air temperature grows, so
throughout the operating range!!
(this achievement has been carried out thanks to the greater surface area)

• Low noise versions: -25% air flow rate

• In order to reduce the noise level it is possible to add the acoustic kit for the
compressors. The noise level can be reduced more or less up to 5 dB(A) (option
available only for the silenced versions)
NSM – V-block

The module V-Block is composed by:


• 2 off microchannel heat exchangers
• 2 off fans
• The main frame

MICRO-CHANNEL HEAT EXCHANGERS

• 30% Weight reduction if compared with traditional CU/AL

• 30% - 35% reduction of refrigerant charge if compared with


similar units with CU/AL
NSM – V-block

• In line pumps Erp 2015


• Available 10 pump
models
NSM – Dimensions

• The length has been reduced to face: MAX 13500

o Competitors
o Available spaces in job site
o Shipment: over 13.5 m, it is mandatory to split the
machine in more modules

• Solutions to reduce the length:


o Improvements in the refrigerant circuit (more kW keeping the same dimension)
o Position of the electrical box (for big frames)
o The increase in capacity is reached using more V-blocks
o MAX 11 V-blocks: 1190*11= 13090 mm

m m
1190
NSM – Overall dimensions compared to NS

• NS and NSM space comparison:


o 900 kW cooling capacity
o EER = 2,68 for the NS unit
o EER = 2,86 for the NSM unit
NSM – Dimensions over 13,5 meters
• Over a specific size (based on the version)
the lenght can be > 13,5 m
• 5 configuration single circuit from 450 kW
(4 V-block) to 650 kW (8 V-block), to
combine at other sizes bi-compressor, in 90 m m
ck =130
order to satisfy requests for bigger units 11 V-Blo

with split to ship and to lift;

m
c k = 7140 m
6 V-Blo

1.0MW 1.23MW 1.40MW


NSM – Environmental impact

R134a Charge= 60 kg + 60 kg R134a charge = 38 kg + 38 kg

R134a = charge reduction > 30-40%


NSM – Regulation pCO3

• pCO3 regulation (within 2015 will be improved to pCO5+)

• Regulation on the supply water


NSM – Regulation pCO3

• Night Silent Mode for the not low noise version


– Possibility to reduce the fans speed from external contact or from hourly program
– Logic regulation with set end pression band

Cooling load required during


day
> Cooling load required at
night

NIGHT SILENT MODE


Specify a time during which the unit can
operate by reducing the fan speed

Versions standard (“ ° “, “ A “, “ U “) This low noise version is compact and


+ accessory DCPX less expensive unit .. good compromise
price/noise
NSM – Regulation pCO3

• Continuous capacity stepless regulation 40-100%


(25÷100% if NSM equips the electronic expansion valve)

• “Always Working”
If there are critical working conditions (for example a very high outside air temperature) NSM doesn’t stop but it is
capable to work automatically at reduced load.
NSM – Regulation pCO3

• AFFP system “Anti Freezing Fan Protection”


It turns on the fans periodically in case of very low outside temperatures (in order to prevent ice forming or snow
deposition on the blades).

• PDC system “Pull Down Control”


to prevent the capacity grow when the water temperature is quickly approaching set point.
This function optimizes energy consumption at each working condition.
NSM – Regulation pCO3

• Double set-point (second set-point through an external input)



• “Set-point compensation”
according to an external analog signal (4-20 mA or 0-10V).

• “Demand Limit”
It allows to limit the input power. It is possible to limit the input power and consequently the cooling capacity to a
specified value (through an external analog input 4÷20 mA or 0÷10V ). It is useful in the case of reducted power avaible.
NSM – Accessories

MULTICHILLER

Up to 9 chillers linked together (modbus interface


AER485P1 is always required for each chiller)

AER485P1

RS-485 interface card allows NSM to communicate


with MODBUS RS-485 RTU protocol
NSM – Accessories

AVX
Kit of antivibrating supports in rubber or springs in order to dampen the
vibrations of the machine

PRV3
Remote control panel

AK (Acoustic Kit)
It consists in a jacket for compressor and a sound suppressant
material under the base (more or less -5 dB(A) compared to the low
noise version).
NSM – Unit configurator
Performance – NSM «°»
Performance – NSM «A»
Performance – NSM «U»
NSM – Some pictures
NSM free-cooling

• Refrigerant coil: microchannel

• Water coil: Copper/Alluminium

• Air filter provided as standard


NSM free-cooling – Competitors
NSM free-cooling – 4 versions
2 efficiency levels
High efficiency versions “A” - “E” EER 2.88
Ultra high efficiency versions “U” - “N” EER 3.06; New!

NOT SILENCED +13% NS FE


SILENCED
+1% NS FA
EER 2.88
A

EER 3.06 U E EER 2.88 +20% NS FE


+7% NS FA
N EER 3.06

• Same efficiency also for the silenced versions, using more V-block.
– New compared to the NS serie;
– For the not silenced versions is available the Night silent working mode;