Primary Functions
This relay provides 3-pole tripping functions and initiates autoreclosure. The primary purpose of this relay
is 3-zone stepped line phase and ground distance protection, pilot Permissive Overreaching Tripping
scheme. Distance is blocked by VT Fuse Failure, Power Swing Detect and load Enchroachment. Line
Pickup (switch onto the fault) backs up distance on line energization. Autoreclose can be initiated
externally (from L90 relay, for example) and is supervised by synchrocheck. Relay has inputs from breaker
auxiliary contacts, panel pushbuttons, RTU etc, also outputs for trip, alarm, status that are collected by the
HMI and RTU.
Zb Z1, Z0 Zf
~ ~
Minimum Three-phase end of the line fault current flowing in the relay with infeed from both
sources:
VTprim Sf _ min
IF3ph _ min * 885 A
(Sb _ min Z1prim ) * Sf _ min Sb _ min Z1prim Sf _ min
3*
Sb _ min Z1prim Sf _ min
Minimum phase-to-phase end of the line fault current flowing in the relay with infeed from both
sources:
IF3ph _ min* 3
IF 2ph _ min 767A
2
Fault Report
A report is produced when the tripping elements issue a trip signal via assigned virtual output. (VO-1).
Setting name Example setting User setting Comment
Fault Report Source SRC 1 Fault report source
Fault Report Trigger TRIP On (VO1) Fault report trigger
Oscillography
A report is produced when the trip output element issues a trip signal via (VO-1). Three phase voltages, three
phase currents and digital states as noted below are recorded.
Setting name Example setting User setting Comment
Number Of Records 10 Number of records stored
Automatic
Trigger Mode Overwrite Mode (Overwrite or protected)
Trigger Position 30% Pre-fault and post-fault data
Trigger Source TRIP On (VO1) Oscillography Trigger
16
AC Input Waveforms samples/cycle Sampling rate
User-Programmable LEDs
The TRIP LED is illuminated when the protection elements issue a trip signal. This LED is latched.
The ALARM LED is illuminated when ANY MAJOR ERROR is detected. This LED is self-reset.
Setting name Example setting User setting Comment
Trip LED Input TRIP On (VO1)
Alarm LED Input ANY MAJOR ERROR
User-Definable Displays
Screen 1 will display three phase current magnitudes (RMS values)..
Screens 2, 3, 4 will display the three phase-to-ground voltage magnitudes (RMS values).
Screens 5 will display the AB phase-to-phase voltage magnitudes (RMS values).
Installation
SYSTEM SETUP
AC Inputs
Current:
Name Example setting User setting Comment
F1: Phase CT Primary 600 A =CTpri
CT F1: Phase CT Secondary 5A =CTsec
CT F1: Ground CT Primary 600 A =CTpri of parallel line. Ground CT primary nominal (mutual
coupling compensation)
CT F1: Ground CT Secondary 5 A =CTsec of parallel line. Ground CT secondary nominal
(mutual coupling compensation)
Voltage:
Name Example setting User setting Comment
VT F5: Phase VT Connection Wye VT group: delta or wye
VT F5: Phase VT Secondary 66.4 V =VTsec/3
VT F5: Phase VT Ratio 1400.00 :1 =VTpri/VTsec
VT F5: Auxiliary VT Connection Vag 1-phase VT (for synchrocheck)
VT F5: Auxiliary VT Secondary 66.4 V =VTsec/3 (1-phase VT secondary nominal)
VT F5: Auxiliary VT Ratio 1400.00 :1 =VTpri/VTsec
Power System
Power system parameters are defined here
Name Example setting User setting Comment
Nominal Frequency 60 Hz 60Hz or 50 Hz system
Phase Rotation ABC System rotation
Frequency And Phase
Reference SRC 1 Source for frequency tracking
Frequency Tracking Function Enabled Enable is recommended
Signal Sources
2 sources are available per one DSP module. They have to be configured accordingly required functionality
and connections.
Name Example setting User setting Comment
SOURCE 1: Name SRC 1 Name of the 3-phase CT, VT sources for distance,
metering etc
SOURCE 1: Phase CT F1 3-phase line CT circuitry (connected to F1, F2 and F3
channels)
SOURCE 1: Ground CT F1 If used and connected: 1-phase parallel line CT (3I0) for
mutual comp. (F4 channel).
SOURCE 1: Phase VT F5 3-phase VT for distance, metering etc (F5, F6, F7
channels)
SOURCE 1: Auxiliary VT None Auxiliary VT not used for this source
SOURCE 2: Name SRC 2 Name of source #2 (used for synchrocheck function)
SOURCE 2: Phase CT None
SOURCE 2: Ground CT None
SOURCE 2: Phase VT None
SOURCE 2: Auxiliary VT F5 Synchronizing 1-phase voltage (F8)
Line
Line positive and zero-sequence impedance in secondary ohms, used for fault locator
Name Example setting User setting Comment
Pos Seq Impedance Magnitude 3.00 ohms =Z1sec Mag
Pos Seq Impedance Angle 85 =Z1sec Ang
Zero Seq Impedance 9.00 ohms =Z0sec Mag
Magnitude
Zero Seq Impedance Angle 80 =Z0sec Ang
Line Length Units km
Line Length 100
Breaker 1 Control
This element is used for tracking 52a bus CB poles state and passing this data to other elements. It is also
used for driving the faceplate open and closed indicators.
Name Example setting User setting Comment
BREAKER 1: Function Enabled Enabling the function
BREAKER 1: Push Button Control Disabled Faceplate pushbuttons
BREAKER 1: Name Bkr 1 Name of the breaker
BREAKER 1: Mode 3-Pole Mode 1-pole or 3-pole
BREAKER 1: Open OFF Operand driving open coil
BREAKER 1: Close OFF Operand driving close coil
BUS CB 52A Breaker auxiliary contact Ph. A or 3-
BREAKER 1: Phase A/3-Pole On(H7c) pole
BREAKER 1: Phase B OFF Breaker auxiliary contact Ph. B
BREAKER 1: Phase C OFF Breaker auxiliary contact Ph. C
BREAKER 1: External Alarm OFF Alarm like Low pressure
BREAKER 1: Alarm Delay 0.000 s Alarm delay
BREAKER 1: Manual Close Recal Limits the duration of manual close
Time 0.000 s cmd
Breaker 2 Control
This element is used for tracking 52a tie CB poles state and passing this data to other elements. It is also used
for driving the faceplate open and closed indicators. Settings are identical to breaker 1.
FLEXLOGIC
PH DIST Z1 OP
PH DIST Z2 OP
PH DIST Z3 OP
1
GND DIST Z1 OP
OR
OR
TRIP (VO1)
GND DIST Z2 OP
GND DIST Z3 OP
POTT OP
LINE PICKUP OP
GND DIST Z1 OP
2
GND DIST Z2 OP OR
OR GR TRIP (VO2)
GND DIST Z3 OP
PH DIST Z1 OP
3
PH DIST Z2 OP OR
OR PH TRIP (VO3)
PH DIST Z3 OP
PH DIST Z1 OP
GND DIST Z1 OP
4
OR
OR
POTT OP
5
RECLOSE INIT ON(H7A) AND
AND RECLOSE INIT (VO4)
LATCH 1 ON
AR CLOSE BKR 1
6
SYNC 1 SYNC OP AND
AND CLOSE BRK (VO5)
7 0 min
CLOSE BRK ON (VO5)
Timer 4
4 min
8 2 min
AND
AND Timer 5 RECL SUCCESS (VO6)
1 min
POTT OP
9
AND
AND PILOT PH TR (VO8)
PH DIST Z2 OP
POTT OP
10
AND
AND PILOT GR TR (VO9)
GND DIST Z2 OP
11
POWER SWING BLOCK OR
OR BLOCK 21P (VO10)
LOAD ENCHR OP
BREAKER 1 CLOSED
12
OR
OR ANY BRK CLD (VO11)
BREAKER 2 CLOSED
BREAKER 1 OPEN
13
AND
AND ALL BRK OPEN (VO12)
BREAKER 2 OPEN
BREAKER 1 CLOSED
14 300 min
AND
AND Timer 6 TRIPCIRALARM (VO19)
200 min
TRIP BUS CB VOFF (H1)
TRIPCIRALARM ON (VO19)
Flexlogic Timers
Timer Exmaple setting User setting Comment
# units PKP DPO
1 second 0 1 Spare
2 second 0 1 Spare
3 second 0 1 Spare
4 second 0 4 Delay to identify successful autorelosure
5 second 2 1 Delay to identify successful autorelosure
6 millisecond 300 200 Delay to set Trip Circuit Supervivon alarm
Flexelements
Can be used to create user-required protection elements.
Non-volatile latches
Latch #1 used to memorize Autoreclose Enable/Disable command from either pushbuttons or RTU
Name Example setting User setting Comment
LATCH 1: Function Enabled
LATCH 1: Type Reset Dominant Reset or Set dominant
LATCH 1: Set 79 SET On(H8c) Operand causing Set position
LATCH 1: Reset 79 RESET On(M8c) Operand causing Reset position
LATCH 1: Target Disabled
LATCH 1: Events Enabled
Distance (Group 1)
Specifies common for all distance elements settings.
Setting Name Example setting User setting Comment
Source for 3-phase voltage and current for
Source SRC 1 distance
Memory Duration 10 cycles Duration of the memory
Operand to reset memory if needed in
Force Self-Polar OFF special cases
Phase Distance Z1
Setting Name Example setting User setting Comment
PH DIST Z1: Function Enabled
PH DIST Z1: Direction Forward Direction: Forward or Reverse
PH DIST Z1: Shape Mho Shape MHO or QUAD
PH DIST Z1: Xfmr Vol Connection None Needed if VTs are located after transform.
PH DIST Z1: Xfmr Curr Connection None Needed if CTs are located after transform.
PH DIST Z1: Reach 2.55 ohms =Z1sec*0.85=3*0.85=2.55 (reach is set to
85% of the line length)
PH DIST Z1: RCA 85 Line positive sequence impedance angle.
PH DIST Z1: Comp Limit 90 This produces a circular Mho
characteristic
PH DIST Z1: DIR RCA 85 Line positive sequence impedance angle for
direct. checks
PH DIST Z1: DIR Comp Limit 90 Blinders for directional lines
PH DIST Z1: Quad Right Blinder 10.00 ohms Used for QUAD only
PH DIST Z1: Quad Right Blinder 85 Used for QUAD only
RCA
PH DIST Z1: Quad Left Blinder 10.00 ohms Used for QUAD only
PH DIST Z1: Quad Left Blinder RCA 85 Used for QUAD only
PH DIST Z1: Supervision 1.00 pu <0.8*IF2ph_min/CTpri<0.8*767/600<1.02pu
setting 1.0pu is chosen
PH DIST Z1: Volt Level 0.000 pu Settings used with series capacitors
PH DIST Z1: Delay 0.000 s Element delay
PH DIST Z1: Block BLOCK 21P On Blocking for defined conditions
(VO10)
PH DIST Z1: Target Latched Target mode
Phase Distance Z2
Setting Name Example setting User setting Comment
PH DIST Z2: Function Enabled
PH DIST Z2: Direction Forward
PH DIST Z2: Shape Mho
PH DIST Z2: Xfmr Vol Connection None
PH DIST Z2: Xfmr Curr Connection None
PH DIST Z2: Reach 3.75 ohms =Z1sec*1.25=3*1.25=3.75 (reach is set to
125% of the line length)
PH DIST Z2: RCA 85 Line positive sequence impedance angle.
PH DIST Z2: Comp Limit 90 This produces a circular Mho
characteristic
PH DIST Z2: DIR RCA 85 Line positive sequence impedance angle for
direct. checks
PH DIST Z2: DIR Comp Limit 90 Blinders for directional lines
PH DIST Z2: Quad Right Blinder 10.00 ohms Used for QUAD only
PH DIST Z2: Quad Right Blinder 85 Used for QUAD only
RCA
PH DIST Z2: Quad Left Blinder 10.00 ohms Used for QUAD only
PH DIST Z2: Quad Left Blinder RCA 85 Used for QUAD only
PH DIST Z2: Supervision 0.680 pu =Z1supervis*Z1reach/Z2reach=1*2.55/3.75=
0.68pu
PH DIST Z2: Volt Level 0.000 pu Settings used with series capacitors
PH DIST Z2: Delay 0.300 s Element delay
PH DIST Z2: Block BLOCK 21P On Blocking for defined conditions
(VO10)
PH DIST Z2: Target Latched Target mode
Phase Distance Z3
Setting Name Example setting User setting Comment
PH DIST Z3: Function Enabled
PH DIST Z3: Direction Forward
PH DIST Z3: Shape Mho
PH DIST Z3: Xfmr Vol Connection None
PH DIST Z3: Xfmr Curr Connection None
PH DIST Z3: Reach 6.00 ohms 2 conditions:
>1.25*Z2reach>1.25*3.75>4.69
< ZLsec /2<13.3/2<6.65 (allowing for 200%
emergency line overload)
Zone reach is chosen 6 secondary Ohms
PH DIST Z3: RCA 85 Line impedance angle for distance
PH DIST Z3: Comp Limit 90 This produces a circular Mho
characteristic
PH DIST Z3: DIR RCA 85 Line impedance angle for direct. checks
PH DIST Z3: DIR Comp Limit 90 Blinders for directional lines
PH DIST Z3: Quad Right Blinder 10.00 ohms Used for QUAD only
PH DIST Z3: Quad Right Blinder 85 Used for QUAD only
RCA
PH DIST Z3: Quad Left Blinder 10.00 ohms Used for QUAD only
PH DIST Z3: Quad Left Blinder RCA 85 Used for QUAD only
PH DIST Z3: Supervision 0.430 pu =Z1supervis*Z1reach/Z3reach=1*2.55/6=0.43
pu
PH DIST Z3: Volt Level 0.000 pu Settings used with series capacitors
PH DIST Z3: Delay 1.000 s Element delay
PH DIST Z3: Block BLOCK 21P On Blocking for defined conditions
(VO10)
PH DIST Z3: Target Latched Target mode
GROUND DISTANCE
The two settings above are provided in all zone elements to provide precision in the event of tapped, non-
homogenous or series compensated lines.
Ground Distance Z1
Setting Name Example setting User setting Comment
GR DISTANCE Z1: Function Enabled
GR DISTANCE Z1: Direction Forward
GR DISTANCE Z1: Shape Quad Shape of the element
GR DISTANCE Z1: Z0/Z1 Mag 3.0 See calculations above, zero- sequence
compensation Magnitude
GR DISTANCE Z1: Z0/Z1 Ang -5 See calculations above, zero- sequence
compensation Angle
GR DISTANCE Z1: Z0M Z1 Mag 0 Zero sequence mutual compens. magnitude.
ZOMmag=abs(ZM)/abs(Z1), where ZM is
mutual impedance.
GR DISTANCE Z1: Z0M Z1 Ang 0 Zero sequence mutual compens. Angle
ZOMang=ang(ZM/Z1)
GR DISTANCE Z1: Reach 2.55 ohms Reach is equal to Phase Dist.Z1 reach
GR DISTANCE Z1: RCA 85 Line positive sequence impedance angle.
GR DISTANCE Z1: Comp Limit 90 Reactance line tilt, 90 -straight line
GR DISTANCE Z1: DIR RCA 85 Line positive sequence impedance angel for
direct. checks
GR DISTANCE Z1: DIR Comp Limit 90 Used for base directional lines, 90 -straight
line
GR DISTANCE Z1: Quad Right 3.5 ohms 2 conditions:
Blinder >1.25*(25+2.6)*CTR/VTR>2.96 (where
25 is desired primary fault resistance to
detect and 2.6 is line primary resistance at
the zone end)
<4*Z1Reach<4*2.55<10.2
3.5 setting is chosen
GR DISTANCE Z1: Quad Right 85 Set equal to line RCA angle
Blinder RCA
GR DISTANCE Z1: Quad Left 1.70 ohms 2 conditions:
Blinder <IL/2<13.3/2<6.85 (to allow 200% overload)
<Zright_blinder/2=3.5/2<1.75
1.7 setting is chosen
GR DISTANCE Z1: Quad Left 85 Set equal to line RCA angle
Blinder RCA
GR DISTANCE Z1: Supervision 0.34 pu <0.8*IFgr_min2/CTpri<0.8*255/600<0.34pu
setting 0.34pu is chosen
GR DISTANCE Z1: Volt Level 0.000 pu Settings used with series capacitors
GR DISTANCE Z1: Delay 0.000 s Element delay
GR DISTANCE Z1: Block SRC1 VT FUSE Blocking for defined conditions
FAIL OP
GR DISTANCE Z1: Target Latched Target mode
Ground Distance Z2
Setting Name Example setting User setting Comment
GR DISTANCE Z2: Function Enabled
GR DISTANCE Z2: Direction Forward
GR DISTANCE Z2: Shape Quad Shape of the element
GR DISTANCE Z2: Z0/Z1 Mag 3.0 See calculations above, zero- sequence
compensation Magnitude
GR DISTANCE Z2: Z0/Z1 Ang -5 See calculations above, zero- sequence
compensation Angle
GR DISTANCE Z2: Z0M Z1 Mag 0 Zero sequence mutual compens. magnitude.
GR DISTANCE Z2: Z0M Z1 Ang 0 Zero sequence mutual compens. angle
GR DISTANCE Z2: Reach 3.75 ohms Reach is equal to Phase Dist.Z2 reach
GR DISTANCE Z2: RCA 85 Line positive sequence impedance angle
GR DISTANCE Z2: Comp Limit 90 Reactance line tilt, 90 -straight line
GR DISTANCE Z2: DIR RCA 85 Line positive sequence impedance angle for
direct. checks
GR DISTANCE Z2: DIR Comp Limit 90 Used for base directional line, 90 -straight
line
GR DISTANCE Z2: Quad Right 5.13 ohms =GRZ1right_blind*Z2reach/Z1reach=3.5*3.75
Blinder /2.55=5.13
GR DISTANCE Z2: Quad Right 85 Set equal to line RCA angle
Blinder RCA
GR DISTANCE Z2: Quad Left Blinder 2.50 ohms =GRZ1left_blind*Z2reach/Z1reach=1.7*3.75/
2.55=2.5
GR DISTANCE Z2: Quad Left Blinder 85 Set equal to line RCA angle
RCA
GR DISTANCE Z2: Supervision 0.23 pu Overcurrent supervision
=Z1supervis*Z1reach/Z2reach=0.34*2.55/3.7
5=0.23pu
GR DISTANCE Z2: Volt Level 0.000 pu Settings used with series capacitors
GR DISTANCE Z2: Delay 0.300 s Element delay
GR DISTANCE Z2: Block SRC1 VT FUSE Blocking for defined conditions
FAIL OP
GR DISTANCE Z2: Target Latched Target mode
Ground Distance Z3
Setting Name Example setting User setting Comment
GR DISTANCE Z3: Function Enabled
GR DISTANCE Z3: Direction Forward
GR DISTANCE Z3: Shape Quad Shape of the element
GR DISTANCE Z3: Z0/Z1 Mag 3.0 See calculations above, zero- sequence
compensation Magnitude
GR DISTANCE Z3: Z0/Z1 Ang -5 See calculations above, zero- sequence
compensation Angle
GR DISTANCE Z3: Z0M Z1 Mag 0 Zero sequence mutual compens. magnitude.
GR DISTANCE Z3: Z0M Z1 Ang 0 Zero sequence mutual compens. angle
GR DISTANCE Z3: Reach 6.00 ohms Reach is equal to Phase Dist.Z3 reach
GR DISTANCE Z3: RCA 85 Line positive sequence impedance angle
GR DISTANCE Z3: Comp Limit 90 Reactance line tilt, 90 -straight line
GR DISTANCE Z3: DIR RCA 85 Line positive sequence impedance angle for
direct. checks
GR DISTANCE Z3: DIR Comp Limit 90 Used for base directional line, 90 -straight line
GR DISTANCE Z3: Quad Right 8.20 ohms =GRZ2right_blind*Z3reach/Z2reach=5.13*6.0/
Blinder 3.75=8.2
GR DISTANCE Z3: Quad Right 85 Set equal to line RCA angle
Blinder RCA
GR DISTANCE Z3: Quad Left Blinder 4.00 ohms =GRZ2left_blind*Z3reach/Z2reach=2.5*6.0/3.
75=4.0
GR DISTANCE Z3: Quad Left Blinder 85 Set equal to line RCA angle
RCA
GR DISTANCE Z3: Supervision 0.15 pu Overcurrent supervision
=Z1supervis*Z1reach/Z2reach=0.34*2.55/6=0
.15pu
GR DISTANCE Z3: Volt Level 0.000 pu Settings used with series capacitors
GR DISTANCE Z3: Delay 1.000 s Element delay
GR DISTANCE Z3: Block SRC1 VT FUSE Blocking for defined conditions
FAIL OP
GR DISTANCE Z3: Target Latched Target mode
X
POWER SWING DETECT [GROUP 1]
Power Swing is used to block phase distance
5. Outer Limit Impedance from point 1 to point 4 is determined by maximum load, assumed exporting load at 30
;
Z14 0.8 ZLsec cos( RCA 30) 0.8 13.3 cos(8530 ) 6.1
CONTROL ELEMENTS
Setting Groups 2 through 6-Not Used.
Synchrocheck
VT Fuse Failure
This element is used for blocking the distance elements and issuing a critical alarm.
Setting Name Example setting User setting Comment
VT FUSE FAILURE 1: Function Enabled VT Fuse Fail has to be enabled
Autoreclose
Setting Name Example setting User setting Comment
Function Enabled
Mode 3 Pole - B Mode: single-pole, 3-pole etc
Max Number Of Shots 1 Number of shots
Block BKR1 OFF General Block is used
Close Time BKR1 0.10 s Duration of the close command, should
be greater than maximum breaker
close time including aux. Contact
BKR Man Close OFF Blocking of AR when breaker closed by
operator from switch or SCADA.
Blk Time Upon Man Cls 10.00 s Duration of the AR blocking upon
manual close
1-P Init OFF Used in single-pole tripping
3-P Init RECLOSE INIT On Initiation of the 3-pole autoreclose from
(VO4) TPC specified functions
3-P TD Init OFF Time delayed initiation (not used for
this application)
Multi P Fault OFF Used in single-pole tripping
BKR 1 Pole Open OFF Used in single-pole tripping
BKR 3 Pole Open OFF Breaker status is brought from Breaker
Control automatically
st
3-P Dead Time 1 1.00 s 3-pole dead time for 1 shot
nd
3-P Dead Time 2 1.20 s 2 shot is not used
Extend Dead T1 OFF Extension of the Dead Time 1(not used
for this application)
Dead T1 Extension 0.50 s Extension of the Dead Time 1(not used
for this application)
Reset OFF Custom reset if needed
Reset Time 10.00 s Reset time after successful reclose
BKR Closed OFF Breaker status is brought from Breaker
Control automatically
Block LATCH 1 OFF Blocking AR from Reset pushbutton
Pause OFF Allows freezing of the recluse cycle,
not used
Inc Seq Time 15.00 s Incomplete sequence time to lockout
Block BKR2 OFF Not needed for single-breaker
application
Close Time BKR2 0.10 s Not needed for single-breaker
application
Transfer 1 to 2 No Not needed for single-breaker
application
Transfer 2 to 1 No Not needed for single-breaker
application
BKR1 Fail Option Continue Not needed for single-breaker
application
BKR2 Fail Option Continue Not needed for single-breaker
application
1-P Dead Time 1.00 s 1-pole tripping
BKR Sequence 1&2 Both breakers (if used) reclose
simultaneously
Transfer Time 4.00 s Transfer time from one breaker to
another
Event Enabled
Contact Inputs
Example setting User setting Comment
ID Name Debounce Events
Time
H7A RECLOSE INIT 2.0 ms Enabled
H7C BUS CB 52A 2.0 ms Enabled Bus CB auxiliary contact
H8A SPARE 2.0 ms Disabled
H8C 79 SET 2.0 ms Enabled Input from Set pushbutton
M7A TIE CB 52A 2.0 ms Enabled Tie CB auxiliary contact
M7C BUS CB PRESS 2.0 ms Enabled
M8A SPARE 2.0 ms Enabled
M8C 79 RESET 2.0 ms Enabled Input from Reset pushbutton
Contact Outputs
The critical failure output is used in parallel with VT Fuse Fail and Trip Circuit supervision alarms.
ID Example setting User setting Comment
Name Operate Seal-In Events
H1 TRIP BUS CB TRIP On (VO1) OFF Enabled
H2 TRIP BUS SPR TRIP On (VO1) OFF Disabled
H3 CLOSE CB CLOSE BRK On OFF Enabled
(VO5)
Virtual Outputs
ID Example setting User setting Comment
Name Events
VIRTUAL OUTPUT 1 TRIP Enabled Trip command
VIRTUAL OUTPUT 2 GR TRIP Disabled Ground distance operation
VIRTUAL OUTPUT 3 PH TRIP Disabled Phase distance operation
VIRTUAL OUTPUT 4 RECLOSE INIT Enabled Initiation of reclosure
VIRTUAL OUTPUT 5 CLOSE BRK Enabled Close breaker(s) command
VIRTUAL OUTPUT 6 RECL SUCCESS Disabled Reclosure is successful
VIRTUAL OUTPUT 7 SPARE Disabled SPARE
VIRTUAL OUTPUT 8 PILOT PH TR. Disabled Phase pilot scheme operation
VIRTUAL OUTPUT 9 PILOT GR TR. Disabled Ground pilot scheme oper.
VIRTUAL OUTPUT 10 BLOCK 21P Enabled Block phase distance
VIRTUAL OUTPUT 11 ANY BRK CLD Disabled At least one breaker closed
VIRTUAL OUTPUT 12 ALL BRK OPEN Disabled Both breakers open
VIRTUAL OUTPUT 19 TripCirALARM Enabled Trip Circuit Supervision oper.
VIRTUAL OUTPUT 20 Crit. Alarm Disabled Critical alarm operation
Color-coding
Cell color Remark
Critical setting, need to be revised specifically to protected line
Set per project specification
Non critical, default setting