Design Parameters are taken from 2014-01-17.DAF.rpt.

Catuiran Hydro Electric Power Project - Design Report V2R0

I. PARAMETER
Soil Unit Weight gsoil = 19.00 kN/m3
Angle of Backfill Slope b = 0.00 deg
Angle of Internal Friction f = 35.00 deg
Wall Slope from Horizontal a = 90.00 deg
Angle of Friction (wall & soil) d = 0.00 deg
Inclination of interface to vertical = 0.00 deg
Peak Ground Acceleration PGA = 0.38

II. STATIC (Coulomb Earth-Pressure)


a. Active Coefficient
sin2(a+f)
Ka =
sin2asin(a-d)[1+sqrt((sin(f+d)sin(f+b))/(sin(a+d)sin(a+b))]2

Ka = 0.2710

b. Passive Cofficient
sin2(a-f)
Kp =
sin2asin(a+d)[1-sqrt((sin(f+d)sin(f+b))/(sin(a+d)sin(a+b))]2

Kp = 3.6902

c. Static Coefficient
Ko = 1-sinf
Ko = 0.4264

III. OBE DYNAMIC (Seismic Mononobe-Okabe)


Ground Acceleration = 0.25
Horizontal Coefficient kh = 0.17
Vertical Coefficient kv = 0.11
Seismic Inertia Angle q = 10.620 deg

a. Dynamic - Active Coefficient


sin2(a+q-f)
Kae =
cosqsin2asin(a+q+d)[1+sqrt((sin(f+d)sin(f-b-q))/(sin(a+q+d)sin(a-b))]2

Kae = 0.3864

Dkae = Kae - Ka
Dkae = 0.1154

b. Dynamic - Passive Coefficient


sin2(a-q+f)
Kae =
Kae =
cosqsin2asin(a-q-d)[1-sqrt((sin(f+d)sin(f+b-q))/(sin(a-q-d)sin(a-b))]2

Kpe = 3.3122

Dkpe = Kp - Kpe
Dkpe = 0.3780

IV. MDE DYNAMIC (Seismic Mononobe-Okabe)

Horizontal Coefficient kh = 0.25


Vertical Coefficient kv = 0.17
Seismic Inertia Angle q = 16.699 deg

a. Dynamic - Active Coefficient


sin2(a+q-f)
Kae =
cosqsin2asin(a+q+d)[1+sqrt((sin(f+d)sin(f-b-q))/(sin(a+q+d)sin(a-b))]2

Kae = 0.4780

Dkae = Kae - Ka
Dkae = 0.2071

b. Dynamic - Passive Coefficient


sin2(a-q+f)
Kae =
cosqsin2asin(a-q-d)[1-sqrt((sin(f+d)sin(f+b-q))/(sin(a-q-d)sin(a-b))]2

Kpe = 3.0630

Dkpe = Kp - Kpe
Dkpe = 0.6272
ect - Design Report V2R0

-taken from Table 6.1: Design Peak Ground Accelerations


PARAMETERS
Unit weight of water Gw = 9.81 kN/m3
Unit weight of concrete Gc = 24 kN/m3
Seismic Ground Acceleration Kh = 0.17
Concrete compressive strength f'c = 24 MPa
Yield strength of Steel fy = 414 MPa

Pressure Distribution at Base

Net Moment Mnet = 475.83 kN-m


Location of R x = 2.17 m
Eccentricity e = 1.68 m
B/4 = Within Base

Maximum Pressure at Toe Q1 = 65.87 kPa


Minimum Pressure at Heel Q2 = -8.8596593 kPa

DESIGN OF COUNTERFORT

Assumed counterfort thickness t = 0.35 m


Counterfort tributary width S = 0.6 m
Main Rebar Diameter Db = 25 mm
Concrete Cover Cc = 75 mm
Diameter of Ties Dt = 16 mm
Reduction Factor for Flexure Fv = 0.9

Reinforcement Calculation
d = 0.695 m
Ru = 1.627
ρ = 0.00409966
ρmin = 0.0034

Area of Reinforcing bars As = 997.2419 m2


Area of Reinforcing bars provided Asprov = 1472.62156 m2
2.03 say 3pcs
OKAY