You are on page 1of 12

Electr Eng

DOI 10.1007/s00202-017-0538-y

ORIGINAL PAPER

Reducing neutral-point voltage fluctuation in NPC three-level


active power filters
Peng Qian1 · Xiandong Ma1 · Guohai Liu2 · Zhaoling Chen2

Received: 11 December 2016 / Accepted: 29 April 2017


© Springer-Verlag Berlin Heidelberg 2017

Abstract Shunt active power filters (SAPFs) have been outperforms the voltage-compensated NPC inverter. Conse-
widely used to improve power quality of the grid by miti- quently, it is shown that the proposed approaches are effective
gating harmonics injected from nonlinear loads. This paper and feasible for improving power quality of the grid when
presents a new method for improving the performance connected to nonlinear loads.
of SAPFs using neutral-point-clamped (NPC) three-level
inverters. NPC three-level inverters often suffer excessive Keywords Shunt active power filter (SAPF) · Three-level
voltage fluctuations at the neutral-point of DC-link capac- inverter · Neutral-point-clamped (NPC) · DC-link · Voltage
itors, which may damage switching devices and cause compensation · Current compensation
additional high harmonic distortion of the output voltage.
In order to solve the problem, two compensating schemes
are proposed to restrict voltage fluctuation in the inverters.
The first is voltage dependent, adopting a voltage compensa- Abbreviations
tion method, while the second is current dependent, using
a current compensation method. The paper describes the SAPF Shunt active power filters
respective circuit architectures and principles of operation. NPC Neutral point clamped
Corresponding models are mathematically formulated and DG Distributed generation
evaluated under typical balanced and unbalanced working PV Photovoltaics
load conditions. The results show that both schemes are able THD Total harmonic distortion
to alleviate considerably voltage oscillations and hence har- SVPWM Space voltage vector pulse-width modula-
monic distortions, and the current-compensated NPC inverter tion
VNPCI Voltage-dependent NPC three-level inverter
CNPCI Current-controlled NPC three-level inverter
IGBT Insulated gate bipolar transistor
B Peng Qian u sa , u sb , u sc Three-phase alternating-current supply
p.qian@lancaster.ac.uk
i sa , i sb , i sc Grid currents
Xiandong Ma i La , i Lb , i Lc Load currents
xiandong.ma@lancaster.ac.uk
i ca , i cb , i cc Compensation currents provided by the
Guohai Liu SAPF
ghliu@ujs.edu.cn
uo Neutral-point voltage of the three-phase
Zhaoling Chen bridge arm
czl908@126.com
uN Neutral-point voltage of the DC-link capac-
1 Engineering Department, Lancaster University, itors
Lancaster LA1 4YW, UK uc Voltage of the primary side of the trans-
2 College of Electrical and Information Engineering, Jiangsu former
University, Zhenjiang, China ub Compensating voltage

123
Electr Eng

us DC-link voltage applied across the capaci- level inverter circuit [7–9] is shown in Fig. 2, where it is
tors incorporated into a SAPF. A full description of the circuit
S1 , S2 , S3 , S4 IGBT power switches will be given in subsequent sections.
T Coupling transformer In a NPC three-level inverter, the neutral point of the DC-
L, C f LC filter link capacitors and the neutral point of the three-phase bridge
u dc DC voltage applied to the single-phase full- circuit are linked together directly. The neutral-point volt-
bridge inverter age of the three-phase bridge arm will vary because of the
ui Voltage output of the single-phase inverter oscillation of the neutral-point voltage in the DC-link. The
i1 Current through the filter inductor problem is inherent because there is a neutral-point current
i2 Transformer primary side current flowing into or out of the neutral points in the circuit [10,11].
i cf Current through the filter capacitor The varying current causes a charge-discharge phenomenon
D1 Diode used to prevent reverse current flow associated with the capacitors through the neutral-points in
L 2 , C3 LC filter the circuit, thus resulting in a fluctuation in the neutral-
u dc1 Voltage input of the boost DC/DC converter point voltage. Consequently, the voltage ripples produced
u dc2 Voltage output of the boost DC/DC conver- will affect the capability of the NPC three-level inverter to
tor work efficiently [12]. Furthermore, excessive fluctuations of
i c3(off) Current in capacitor C3 when switching the DC-link voltage increase voltage stresses on the switch-
device S5 is turned off ing devices and hence the total harmonic distortion (THD)
i3 Current in the inductor L 1 of the output current, which may limit potential engineering
i4 Compensating current applications of this type of inverter.
u L1(off) Voltage across the inductor L 1 when switch- There are three main factors that may cause oscillations
ing device S5 is turned off in the neutral-point voltage in the DC-link branch. Firstly,
u L1(on) Voltage across inductor L 1 when switch S5 the capacitance associated with the DC-link capacitors may
is turned on become unbalanced after use for extended periods of time.
D Duty cycle of the switching device S5 DC-link capacitors are required to endure high ripple currents
K p , Ki Parameters of the PI controller leading to self-heating, which, in addition to high ambient
operating temperatures, can result in the deterioration of the
electrolyte material and the loss of electrolyte by vapor dif-
1 Introduction fusion. Secondly, a critical factor for the inverter to work is
delivery of the gate drive signals to the switching devices, as
Recently, distributed generation (DG) installation has been controlled by the switching frequency. Any switching delay
significantly increased, due to the deregulation of utilities, will cause load current imbalance. Thirdly, nonlinear loads
environmental constraints, and concerns regarding climate also cause harmonics to appear in the load current, which
change [1]. This type of power generation system, as shown may in turn inject harmonics back to the inverter. Mathemat-
in Fig. 1, can provide electric power at or on a site closer ical descriptions regarding the causes of voltage oscillations
to end users. However, harmonic-related problems have can be found in [13].
become a key concern because DG generators, such as wind In order to solve these problems, three main methods
and photovoltaics (PV), are coupled to power electronic con- have been investigated to alleviate voltage oscillations. The
verters and nonlinear loads [2]. In this regard, shunt active first is through the use of two independent DC sources to
power filters (SAPFs) are widely used to mitigate these ensure a stable and constant DC voltage across the inverter.
harmonic distortion problems in the grid. Compared to tra- The method is expensive [14], because two independent
ditional two-level voltage-source inverters used in SAPFs, DC sources require two isolation transformers. The second
three-level voltage-source inverters are able to bear higher involves the design of improved control strategies, which are
voltage classes and operate with lower harmonic distortion arguably the most widely used techniques at present [15–17].
and at lower switching frequencies. Three-level inverters Among the control strategies, the best known is the space
therefore offer better performance, in particular for medium- voltage vector pulse-width modulation (SVPWM) method
voltage applications [3]. In terms of topological structure, [18–22]. The control strategy proposed in [18] replaces the
three-level inverters can be classified as one of three distinct P-type or N-type small switching states with other switching
types, namely diode-clamped multilevel inverters, clamp- states that do not affect the neutral-point voltage. Reference
ing capacitor multilevel inverters, and isolated H-bridge [23] demonstrates the ability of the SVPWM method to bal-
multilevel inverters [4,5]. The neutral-point-clamped (NPC) ance the neutral-point voltage for different regions of the
three-level inverter [6] is classified as type of diode-clamped space vector plane, while a new general model was intro-
multilevel inverters. The most commonly used NPC three- duced in [24] to investigate the theoretical and practical

123
Electr Eng

Fig. 1 Schematic diagram of a Grid


distributed generation system
A
V
Transformer

Wind
Grid
BRK PV array
AC-DC DC-AC AC DC
converter inverter inverter
WT PV
3-blade
BRK BRK
turbine

Wind
WT PV PV array
BRK BRK
AC-DC DC-AC AC DC
converter inverter inverter
3-blade
turbine
WT: wind turbine
CHP: combined heat and power
IC engine
BRK: breaker

Shunt active power


CHP filter (SAPF)
Fuel intake BRK
Synchronous
control
generator Nonlinear
load
Load
BRK

limitations of the balancing problems caused by space vector three-level inverter (CNPCI) and uses a current compensation
modulation. A control scheme based on a virtual space vector method. Both two new inverter topologies are incorporated in
PWM method is proposed in [25] to control the neutral-point a SAPF. The remainder of this paper is organized as follows.
voltage fluctuation over the full range of the modulation The principle of the SAPF is described in Sect. 2. The circuit
index and load power factor, subject to the condition that architectures, their principles of operation and mathematical
the sum of the three-phase output currents equals zero. The models describing voltage- and current-dependent inverters
third method reduces voltage oscillations through a change are outlined in Sects. 3 and 4, respectively. Simulation results
in circuit topology, as the solution by hardware circuit has its of the inverter models and the performance of the SAPF under
own advantages. This method incorporates auxiliary compo- typical balanced and unbalanced working load conditions are
nents in the traditional NPC three-level inverter circuit and shown and discussed in Sect. 5. Conclusions and suggestions
has proved to be able to achieve good performance to sup- for future work are given in Sect. 6.
press excessive neutral-point voltage fluctuation effectively
at low cost [26].
In this paper, two new NPC three-level inverter topologies 2 Shunt active power filter (SAPF)
are proposed. The first is a voltage-dependent NPC three-
level inverter (VNPCI), which adopts a voltage compensation Figure 2 shows a SAPF based on the NPC three-level inverter.
method to restrain the neutral-point voltage fluctuation of In this figure, u sa , u sb , u sc are the three-phase alternating-
the DC-link. The second method is a current-controlled NPC current supplies; the load is nonlinear, generating harmonic

123
Electr Eng

usc isc V3 iLc


usb isb V2 iLb R
N
usa isa V1 iLa L

ica icb icc

C1 K1 L

+
DZ1 K2
A
us B
C
- DZ2 K3

C2
K4

Fig. 2 A SAPF based on the neutral-point-clamped (NPC) three-level inverter

currents; i sa , i sb , i sc and i La , i Lb , i Lc are grid currents and load unit 1 is associated with the conventional NPC three-level
currents, respectively; i ca , i cb , i cc are compensation currents inverter, as described in the preceding section. In order to
provided by the SAPF, which are used to eliminate harmonic reduce excessive neutral-point voltage fluctuations across the
currents in the grid. The SAPF is essentially composed of two DC-link capacitors, this paper considers the application of
major components, namely a conventional NPC three-level an active voltage compensation method in which the con-
inverter and an associated control scheme. In the inverter trollable voltage source is used in series between the neutral
circuit, K 1 , K 2 , K 3 , K 4 are IGBT (insulated gate bipolar point of the DC-link and the neutral point of the three-phase
transistor) power switches, while DZ1 , DZ2 are clamp diodes; bridge circuit. This voltage source is used in order to com-
note that only the components of one inverter arm are labeled pensate for voltage fluctuations across the three-phase bridge
for simplicity. The DC bus voltage is split in half using two arm of the inverter. The voltage at the neutral-point of the
DC capacitors, C1 and C2 , and into three voltage levels, u s ,0, three-phase bridge arm is detected in real time and compared
and −u s , via clamping diodes. The control scheme detects with a reference voltage, producing an appropriate value for
the load currents in real time, which are used to calculate the compensation voltage. Subsequently, the voltage source
command signals for the IGBT switches. The inverter then generates an equal but opposite voltage, thus reducing the
works as a signal amplification circuit, producing appropriate voltage fluctuation across the inverter.
compensation currents. This compensation current is equal Power unit 2 is an active voltage compensation device,
but opposite to the harmonic currents, which can be overlaid which in essence is a single-phase full-bridge inverter. The
to the load currents, thus eliminating the harmonic currents device works as a controllable voltage source and is con-
generated by the nonlinear load. nected in series between the neutral point of the three-phase
bridge arm and the neutral point of the DC-link through
a coupling transformer. The variables u o and u N denote
3 Voltage-compensated NPC inverter (VNPCI) the neutral-point voltage across the three-phase bridge arm
and the DC-link capacitors, respectively; u c and u b are the
3.1 Inverter circuit voltages across the primary and secondary sides of the trans-
former, respectively, for which u b is used as the compensating
The schematic diagram of the VNPCI circuit is shown in voltage; u s is the DC-link voltage applied across the capaci-
Fig. 3. Essentially, the circuit consists of two parts. Power tors.

123
Electr Eng

Hence, for the NPC inverter shown in Fig. 3, the voltage due
Power Unit 2
to the introduction of the compensating voltage u b can be
Cf L S1 S3 obtained via the following equations. In the ideal situation,
u dc three-phase bridge arm voltage u o should be equal to the half
DC-link voltage, i.e., 0.5 u s .
S2 S4

uN − ub = uo (2)
N 2 + uc -  
di 1
N 1 + ub - uN − n ui − L = 0.5u s (3)
dt
+ Power
K1 For the voltage output of the single-phase inverter u i
C1 DZ 1 Unit 1
LOAD R
K2 A
us B u i = S ∗ u dc (4)
+ + C
N O
K3 L
uN uo where S ∗ represents the switching function; if S1 and S4 are
C2 DZ 2
K4 switched on while S2 and S3 are switched off, then S ∗ = 1;
- -
- if S1 and S4 are switched off while S2 and S3 are switched
on, then S ∗ = −1.
Fig. 3 Schematic diagram of the voltage-compensated NPC inverter Substituting (4) into (3) gives

 
di 1
N1 T N2 i2 i1 L S1 S3 u N − n S ∗ u dc − L = 0.5u s (5)
dt
+ + +
icf +
ub uc Cf ui udc Therefore, the state equations of this active voltage compen-
- - - sation device can be described as,
-
S2 S4 du c 1
= (i 1 − i 2 ) (6)
dt Cf
Fig. 4 Schematic diagram of the active voltage compensation device di 1 1
= (u i − u c ) (7)
dt L

3.2 The active voltage compensation device The resulting control scheme of the active voltage compen-
sation device is shown in Fig. 5. It illustrates the operating
The voltage compensation device is shown in Fig. 4. It is com- principle of active voltage compensation device as controlled
posed of a single-phase, full-bridge inverter circuit, where by this scheme. In this diagram, the voltage 0.5u s ∗ (s) refers
S1 , S2 , S3 , S4 are IGBT power switches; T is the coupling to half of the DC-link voltage under balanced capacitors;
transformer with a transformation ratio of n; the inductor L u n (s) is the DC-link neutral-point voltage measured in real
and the capacitor C f form a LC filter that removes unwanted time; u c ∗ (s) is the reference compensating voltage; u i (s)
switching harmonics from the inverter output. is the output voltage of the single-phase full-bridge inverter
Now consider the mathematical model of the voltage com- circuit; u c (s) is the transformer primary side voltage; i 1 (s) is
pensation device. In the circuit illustrated in Fig. 4, u dc is a the current in the filter inductor; and i 2 (s) is the transformer
DC voltage applied to the single-phase full-bridge inverter; primary side current. The compensating voltage u c ∗ (s) is
u i is the voltage output of the single-phase inverter; i 1 is the obtained by calculating the difference between the measured
current through the filter inductor; i 2 is the transformer pri- neutral-point voltage of DC-link and half of the ideal DC-
mary side current; i cf is the current passing through the filter link voltage. The error voltage between u c ∗ (s) and u c (s) is
capacitor. then used for generating PWM signals based on the triangu-
For an ideal transformer (i.e., no losses and no leakage lar wave modulation method, which are then used to control
flux between the primary and secondary windings), the voltage output of the single-phase inverter at a desired
level. A PI controller, represented by K p + K i /s, is used
 
di 1 because it can provide a compensating voltage output more
ub = n ui − L (1) accurately, thus improving performance further.
dt

123
Electr Eng

* i1(s)
0.5us*(s) + uc (s)+ Single-phase full- - + uc(s)
KP+Ki/s 1/Ls 1/Cs
- - bridge inverter + -
un(s) i2(s)
ui(s)

Fig. 5 The control scheme for the active voltage compensation device

4 Current-compensated NPC inverter (CNPCI) Power Unit 2


L2 D1 L1
4.1 Inverter circuit

As described above, the primary reason causing neutral-point C3 S5 udc1


voltage fluctuation across the DC-link is the current that flows
in to or out of the neutral points in the circuit. The varying
current will lead to charge-discharge phenomena associated
with the capacitors through the neutral-points in the circuit,
resulting in a fluctuation in the neutral-point voltage. The + Power
voltage fluctuation can be alleviated naturally through the K1
C1 Unit 1
use of an active current compensation scheme in which a
controllable current source is connected in shunt with one of K2 R
A
the DC capacitors. This controllable current source is used us DZ1 B
+
to compensate for the current flow between the neutral point N DZ2
C
of DC-link capacitors and the neutral point of three-phase uN K3 L
LOAD
bridge circuit. It can further suppress neutral-point voltage
fluctuations because, if this scheme is applied effectively, C2 - K4
there is approximately zero current flowing between the neu- -
tral points in the inverter.
The schematic diagram of CNPCI is shown in Fig. 6. It Fig. 6 Schematic diagram of the current compensation NPC inverter
also consists of two parts: part 1 is the conventional NPC
three-level inverter and part 2 is the proposed active current i4 L2 D1 i3 L1
compensation device. The compensation device is essen-
tially a boost DC/DC conversion circuit, which works as u L1
a current source. The current flowing between the neutral iC3
uN u dc2 S5 u dc1
points of the inverter is detected in real time, and an equal
but opposite current is then generated through the current C3
compensation device, offsetting the current flow between the
neutral points in the inverter. Thus, the charge-discharge phe- Fig. 7 Schematic diagram of the active current compensation device
nomenon of DC capacitors through DC-link neutral point
can be restrained effectively. The effectiveness of the cur-
rent compensation device relies on the voltage difference current flow; L 1 is a power inductor used for energy storage;
between the boost circuit and the DC-link, which is applied L 2 and C3 form a LC filter for the circuit. Now consider
to the inductor (L 2 in Fig. 6), thus producing a compensation the mathematical model of the active current compensation
current for the DC capacitor. device. In the circuit, u dc1 is the voltage input of the boost
DC/DC converter; u dc2 is the voltage output of the boost
4.2 Inverter circuit DC/DC convertor; u N is the DC-link neutral-point voltage;
i c3 is the current in the capacitor C3 ; i 3 is the current in the
Figure 7 shows the proposed active current compensation inductor L 1 ; i 4 is the compensating current. Suppose i c3(off)
device, essentially a boost DC/DC converter circuit, where and i c3(on) are the current in capacitor C3 when the switching
S5 is the IGBT power switch; D1 is a diode preventing reverse device S5 is off and on, respectively; u L1(off) is the voltage

123
Electr Eng

Fig. 8 The control scheme for


udc2(s)
the active current compensation
device ic*(s) + - ic(s)
KP+Ki/s Boost circuit 1/Ls
- +
uN(s)


⎨ u dc2 =
1
across the inductor L 1 when the switching device S5 is off 1−D u dc1
while u L1(on) is the voltage across the inductor L 1 when the (14)

switch S5 is on. i 4 = (1 − D) i 3
When the switching device S5 is turned on, the state equa-
tions of the current compensation device can be described as, A control scheme, designed for the active current compen-
sation device, can be derived from this model, as shown in
⎧ di3 Fig. 8. In this circuit, u dc2 (s) is the voltage output of the boost
⎨ L 1 dt = u dc1 = u L 1 (on)
(8) DC/DC converter; u N (s) is the DC-link neutral-point voltage
⎩ measured in real time. The reference compensating current
C3 dudtdc2 = i 4 = i C3 (on)
i c *(s) is obtained by the real-time detection of the current
When the switching device S5 is turned off, the above equa- flowing between the neutral points of the inverter. The cur-
tion can be written as rent i c (s) is the compensation current generated by the boost
⎧ di3 circuit. The error current between i c *(s) and i c (s) is then used
⎨ L 1 dt = u dc1 − u dc2 = u L 1 (off) to generate PWM signals. This signal is based on the trian-
(9) gular wave modulation method, producing a compensating

C3 dudtdc2 = i 4 − i 3 = i C3 (off) current at the desired level. As with the voltage compensation
scheme, a PI controller, represented by K p + K i /s, is used
During one switching cycle, TS , the average voltage across because it generates a more accurate compensation current.
the inductor L 1 is,
 t+DTs
1 5 Results and analysis
u L1 = u L 1 (on) (τ )dτ
TS t
 t+Ts 5.1 The inverters
+ u L 1 (o f f ) (τ )dτ (10)
t+DTs Models of the voltage compensation device and the current
u L 1 = Du dc1 + (1 − D) (u dc1 − u dc2 ) (11) compensation device have been built using Simulink Sim-
PowerSystems, as described above and shown in Figs. 3
where D represents the duty cycle of the switching device and 6, respectively. The parameters used in the models are
S5 , i.e., the proportion of time during which S5 is operated. given in Table 1. The DC-link voltage is 3 kV, a level com-
During one switching cycle, the average current in the monly used in medium-voltage power drives; the switching
capacitor C3 is equal to frequency for the NPC three-level inverter is 1 kHz; and
the switching frequencies used to control the single-phase
 t+DTs
1 inverter for the voltage and current compensation device are
i C3 = i C3 (on) (τ )dτ both set to 10 kHz. In order to evaluate the dynamic perfor-
Ts t
 t+Ts mance of the proposed inverters, a nonlinear load is used in
+ i C3 (o f f ) (τ )dτ (12) this study. This load consists of a three-phase rectifier with a
t+DTs
resistive (4 ) and inductive (15 mH) load. The use of a non-
i C3 = Di 4 + (1 − D) (i 4 − i 3 ) (13) linear load increases the neutral-point voltage fluctuation of
the DC-link, because the nonlinear load draws a current that
It is well known that the average voltage across an inductor is not necessarily sinusoidal, hence generating harmonic cur-
and the average current in a capacitor should be zero dur- rents. The NPC three-level inverter is used with a constant
ing a switching cycle. Hence, under steady state, the current voltage output control strategy, based upon space voltage
compensation device can be described as follows vector modulation (SVPWM). The error voltage between

123
Electr Eng

Table 1 Parameters used in the VNPCI and CNPCI inverters a 1700


Parameters of the VNPCI Parameters of the CNPCI 1650

Neutral point voltage


Parameters Value Parameters Value 1600
1550
u dc 500 V u dc1 100 V
1500

(V)
Cf 50 μF L1 10 mH
1450
L 0.4 mH L2 0.5 mH
1400
C3 800 μF
1350
Parameters of the NPC three-level inverter
1300
us 3000 V
1250
C1 , C2 500 μF 10 10.02 10.04 10.06 10.08 10.1
Times (s)
b
the NPC three-level inverter output voltage and the refer- 4000
THD=45.30%

Phase to phase voltage (V)


ence voltage is processed by a PI controller, which is then 3000
used as the input signal for SVPWM to generate appropriate 2000
PWM signals. This control scheme has a higher efficiency 1000
for controlling the DC-side voltage than the equivalent sine
0
pulse-width modulation method.
In real-world applications, the load can be either in a bal- -1000

anced or unbalanced condition. An unbalanced load added -2000


to the three-phase output voltage of an inverter can result -3000
in greater fluctuations in the neutral-point voltage across the
-4000
DC-link. In the simulation, the inverters are initially con- 10 10.02 10.04 10.06 10.08 10.1
nected to a balanced nonlinear load, and resistive (8 ) and Time (s)
inductive (1.5 mH) loads are then applied between phase A
and phase B in order to evaluate the dynamic performance of Fig. 9 Voltage waveforms of the conventional NPC in a load swell. a
Voltage waveform of neutral-point voltage u o . b Voltage waveform of
the proposed compensation devices under a unbalanced load phase A to phase B voltage u AB
condition. The unbalanced load occurs at 10.05 s and lasts
for 0.05 s.
Firstly, a conventional NPC three-level inverter, under bal- Figure 11a, b shows the neutral-point voltage u o , the
anced and unbalanced working load conditions, has been phase A to phase B voltage u AB of the proposed current-
modeled and investigated. Figure 9a, b shows the waveform compensated NPC inverter under the balanced and unbal-
of the neutral-point voltage u o , the phase A to phase B voltage anced working load conditions. With the current compensa-
u AB of the conventional inverter. The neutral-point voltage tion device being added, the neutral-point voltage fluctuation
fluctuation across the DC-link is severe, even in the balanced of DC-link is suppressed further to 18 V. Under the unbal-
load condition; the range of the fluctuation reaches a value of anced load condition between 10.05 and 10.1 s, the neutral-
200 V. During the unbalanced load condition, applied from point voltage fluctuation of DC-link is reduced to 25 V. The
10.05 to 10.1 s, it can be seen the neutral-point voltage fluc- THD of output voltage of the NPC three-level inverter is
tuation range increases to 300 V. The THD (total harmonic 42.08%.
distortion) of the output voltage waveform across the inverter The results clearly show that the current-compensated
is 45.30%. NPC inverter (CNPCI) has a better performance than the
Figure 10a, b shows the waveform of the neutral-point voltage-compensated NPC inverter (VNPCI). Figures 10
voltage u o , the phase A to phase B voltage u AB of the pro- and 11 demonstrate that the CNPCI can restrict the neutral-
posed voltage-compensated NPC inverter under the balanced point voltage fluctuation of the DC-link to 0.6 and 0.83%,
and unbalanced working load conditions. With the voltage respectively, when the CNPCI works under typical bal-
compensation device being added, the neutral-point volt- anced and unbalanced working load conditions. However,
age fluctuation of DC-link is suppressed effectively, being the VNPCI restrains the neutral-point voltage fluctuation of
reduced to 40 V. Similarly, an unbalanced load is applied DC-link to 1.2 and 2.3%, respectively, in the same conditions.
at 10.05 s, lasting 0.05 s. The neutral-point voltage fluctu- The waveform comparison of neutral-point voltage u o pro-
ation of DC-link is reduced to 75 V under the unbalanced duced in different condition is shown in Fig. 12. The effect of
load condition. The THD of output voltage of the inverter is the switching frequency on the output performance was also
42.24%. investigated. It was found a frequency higher than 2 kHz can

123
Electr Eng

a a 1520
1550
Neutral point voltage (V)
1540

Neutral point voltage (V)


1515
1530
1520 1510
1510
1500 1505
1490
1480 1500
1470
1495
1460
1450 1490
10 10.02 10.04 10.06 10.08 10.1 10 10.02 10.04 10.06 10.08 10.1
Time (s) Time (s)
b
4000 b
THD=42.24% 4000
Phase to phase voltage (V)

3000 THD=42.08%

Phase to phase voltage (V)


3000
2000
2000
1000
1000
0
0
-1000
-1000
-2000
-2000
-3000
-3000
-4000
10 10.02 10.04 10.06 10.08 10.1 -4000
Time (s) 10 10.02 10.04 10.06 10.08 10.1
Time (s)
Fig. 10 Voltage waveforms of the proposed VNPCI in a load swell. a
Voltage waveform of neutral-point voltage u o . b Voltage waveform of Fig. 11 Voltage waveforms of the proposed CNPCI in a load swell. a
the phase A to phase B voltage u AB Voltage waveform of neutral-point voltage u o . b Voltage waveform of
the phase A to phase B voltage u AB

1700
produce acceptable results but the use of 10 kHz switching
1650
frequency produced the best results although it might be too
Neutral point voltage (V)

fast for the device to work at such a high voltage level. 1600

The VNPCI only eliminates the voltage fluctuation at the 1550


neutral point of three-phase bridge arm; there is still fluc- 1500
tuation of the neutral-point voltage of the DC-link. This 1450
means the fluctuation problem cannot be eliminated thor- 1400
Conventional NPC inverter
oughly. However, the CNPCI can eliminate the neutral-point 1350
voltage fluctuation of the DC-link more effectively because Current-compensated NPC inverter
1300 Voltage-compensated NPC inverter
the CNPCI offsets the current that flows between the neutral
1250
point of the DC-link capacitors and the neutral point of the 10 10.02 10.04 10.06 10.08 10.1
three-phase bridge circuit in the inverter, which is the cause Times (s)
of the voltage fluctuation. In addition, for the VNPCI, an iso-
Fig. 12 Waveform comparison of the neutral-point voltage u o pro-
lated transformer is required, which should be able to handle duced in the three inverter topologies
several harmonic components without entering to the satu-
ration region in the primary side and handle secondary side
voltage range quickly to compensate the zero sequence volt- one IGBT power switching device (the most expensive com-
age generated at the NPC converter. A complicated control ponent in the circuit), while the VNPCI needs four IGBT
scheme is therefore needed to overcome these problems [27]. power switches and a coupling transformer. Thus, the CNPCI
On the contrary, the CNPCI avoids using the isolated trans- offers a more cost-effective performance.
former; the cost to manufacture and assemble the CNPCI is The selection of PI control parameters was made by trial
therefore lower than the VNPCI; the CNPCI requires only and error, aiming to achieve an optimal performance from

123
Electr Eng

tests. The proportional response can be adjusted by multi- 200


THD=18.52%
plying the error (i.e., the voltage difference in the case of the 150
VNPCI and the current difference in the case of the CNPCI) 100
by the proportional gain K p . The integral term in the PI con- 50

Current (A)
troller is the sum of the instantaneous error over time, thus
0
giving the accumulated offset, which is then multiplied by
the integral gain K i . For the VNPCI, the selected value of -50
K p and K i is 5 and 10, respectively, while, for the CNPCI, -100
the selected value of K p and K i is 10 and 0.5, respectively. -150
Results have shown that the use of these parameters can pro-
-200
vide an improved performance of the controllers. 10 10.02 10.04 10.06 10.08 10.1
Time (s)
5.2 The shunt active power filters (SAPF)
Fig. 13 Waveform of phase-A current of the power grid under the
nonlinear load
The two proposed inverters are now applied in the SAPF that
is indispensable part of the grid system. The SAPFs incor- a
porating with the current-compensated NPC inverter and the 100
voltage-compensated NPC inverter have been built and sim-
ulated. One of the typical SAPF applications is in the AC 400 50
V DG system [28]; but unlike the normal inverter, in order to
satisfy the working condition in three-phase power system, Current (A)
the DC-link voltage of SAPF must be over 3 times higher 0

than the phase voltage. Thus, the NPC three-level inverter is


very suitable to apply in SAPF due to high DC-link voltage. -50
The parameters used in the model are defined as follows:
DC-link voltage of SAPF is 800 V; supply fundamental fre-
-100
quency f = 50 Hz; filter line inductance Ls = 2 mH; other 10 10.02 10.04 10.06 10.08 10.1
parameters used for the inverters are referred to Table 1. It is Time (s)
noteworthy that the use of a low DC-link voltage, rather than
b
the 3000 V previously discussed, was to assess the perfor- 200
THD=2.05%
mance of the proposed inverters for this particular application 150
in SAPF. As mentioned above, nonlinear loads are often con- 100
Current (A)

nected in the power grid and the load condition will affect the 50
work efficiency of the NPC three-level SAPF. The SAPF is
0
firstly connected to a balanced nonlinear load and then to an
-50
unbalanced load emulated by a resistive (8 ) and inductive
(1.5 mH) load being applied between phase A and phase B. -100

The unbalanced load also occurs at 10.05 s and lasts 0.05 s. -150
Firstly, a SAPF based on the traditional NPC three-level -200
10 10.02 10.04 10.06 10.08 10.1
inverter connected with the three-phase nonlinear load, as
Time (s)
shown in Fig. 2, has been investigated under the balanced
and unbalanced working load conditions. Figure 13 shows Fig. 14 Waveform of the phase-A currents in the filter output and the
the waveform of grid current of phase A, as an example. The power grid employing the proposed VNPCI three-level SAPF. a Wave-
form of the phase-A current in the filter output. b Waveform of the
grid current distorts heavily in both balanced and unbalanced
phase-A current in the power grid
load condition, and the THD of the grid current is 18.52%.
Figure 14 shows the waveform of the filter output of phase
A, i.e., the currents i ca , i cb and i cc as shown in Fig. 2, and frequency component is dominant at 50 Hz, while other har-
the grid currents of the proposed VNPCI three-level SAPF, monic components in phase-A current are now eliminated
i.e., the currents i sa , i sb and i sc as shown in Fig. 2, under effectively. The THD of the grid current is reduced to 2.05%.
the typical balanced and unbalanced working load condi- Figure 15 shows the waveform of the grid currents of the
tions. Essentially, the filter output currents are effective to proposed CNPCI three-level SAPF under typical balanced
compensate the harmonics being injected from nonlinear and unbalanced working load conditions. It can be seen that
loads, hence improving the quality of the gird currents. The the harmonic currents in phase A can be eliminated more

123
Electr Eng

200 References
THD=1.70%
150
1. Pepermans G, Driesen J, Haeseldonckx D, Belmans R, D’haeseleer
100 W (2005) Distributed generation: definition, benefits and issues.
50 Energy Policy 33:787–798
Current (A)

2. Pouresmaeil E, Montesinos-Miracle D, Gomis-Bellmunt O,


0 Sudrià-Andreu A (2011) Instantaneous active and reactive current
control technique of shunt active power filter based on the three-
-50 level NPC inverter. Int Trans Electric Energy Syst 21:2007–2022
-100 3. Allmeling JH (2004) A control structure for fast harmonics com-
pensation in active filters. IEEE Trans Power Electron 19(2):508–
-150 514
4. Liang W, Donglai Z, Yi W, Bin W, Hussain SA (2016) Power and
-200 voltage balance control of a novel three-phase solid-state trans-
10 10.02 10.04 10.06 10.08 10.1
former using multilevel cascaded H-bridge inverters for microgrid
Time (s) applications. IEEE Trans Power Electron 31(4):3289–3301
5. Roodsari BN, Nowicki EP (2013) Fast space vector modulation
Fig. 15 Waveform of the power grid currents employing the proposed algorithm for multilevel inverters and its extension for operation
CNPCI three-level SAPF of the cascaded H-bridge inverter with non-constant DC sources.
IET Power Electron 6:1288–1298
6. Ke M, Frede B (2012) The impact of power switching devices on
effectively. The THD of the grid current is reduced further the thermal performance of a 10 MW wind power NPC converter.
to 1.7%. Energies 5(7):2559–2577
7. Muyeen SM, Takahashi R, Tamura J (2010) Wind power and hydro-
gen generation system with cooperatively controlled three-level
NPC-VSC based energy capacitor. Int Trans Electric Energy Syst
6 Conclusions 20:1071–1081
8. Zaveri T, Bhalja BR, Zaveri N (2012) Load compensation using
The paper presents two new NPC three-level inverter topolo- DSTATCOM in three-phase, three-wire distribution system under
gies in order to eliminate excessive voltage fluctuation various source voltage and delta connected load conditions. Int J
Electric Power Energy Syst 41:34–43
happened at the neutral point of DC-link capacitors of the 9. Saad S, Zellouma L (2009) Fuzzy logic controller for three-level
inverter. The first is voltage dependent, which adopts a shunt active filter compensating harmonics and reactive power.
voltage compensation method to restrain the neutral-point Electric Power Syst Res 79:1337–1341
voltage fluctuation. The second is current dependent, using 10. Celanovic N, Boroyevich D (2000) A comprehensive study of
neutral-point voltage balancing problem in three-level neutral-
a current compensation method to restrict the voltage fluc- point-clamped voltage source PWM inverters. IEEE Trans Power
tuation. The results show that both topologies can suppress Electron 15:242–249
the neutral-point voltage fluctuation of the DC-link effec- 11. Ui-Min C, Frede B, Kyo-Beum L (2015) Method to minimize the
tively under typical balanced and unbalanced working load low-frequency neutral-point voltage oscillations with time-offset
injection for neutral-point-clamped inverters. IEEE Trans Ind Appl
conditions. The current-compensated NPC inverter outper- 51:1678–1691
forms the voltage-compensated NPC inverter. Furthermore, 12. Rodriguez J, Bernet S (2010) A survey on neutral-point-clamped
these compensated NPC three-level inverters are applied to inverters. IEEE Trans Ind Electron 57:2219–2230
a shunt active power filter in the grid lines. It is shown that 13. Helle L, Nielsen SM, Enjeti P (2002) Generalized discontinuous
DC-link balancing modulation strategy for three-level inverters. In:
the proposed approaches are effective and feasible for elim- Power conversion conference, Osaka, Japan, vol 2, pp 359–366
inating harmonic currents and therefore improving power 14. Yazdani A, Iravani R (2005) Generalized state-space averaged
quality of the grid system when connected with nonlinear model of the three-level NPC converter for systematic DC-voltage-
loads. balancer and current-controller design. IEEE Trans Power Deliv
20:1105–1114
Future work will focus on experimental testing of the 15. Zaragoza J, Pou J, Ceballos S, Robles E, Jaen C (2009) Voltage-
proposed NPC three-level SAPFs to further verify their per- balance compensator for a carrier-based modulation in the neutral-
formance. Optimal selection of PI control parameters for point-clamped converter. IEEE Trans Ind Electron 56:305–314
the inverters will also be investigated in order to further 16. Ui-Min C, June-Seok L, Kyo-Beum L (2014) New modulation
strategy to balance the neutral-point voltage for three-level neutral-
optimize system performance under different load condi- clamped inverter systems. IEEE Trans Energy Convers 29:91–100
tions. In addition, the application of the proposed current- 17. Pulikanti SR, Dahidah SA (2011) Voltage balancing control of
compensated NPC inverter is being considered in both a three-level active NPC converter using SHE-PWM. IEEE Trans
wind power generation system and a small grid system Power Deliv 26:258–267
18. Ghennam T, Berkouk EM, Francois B (2010) A novel space–vector
in the laboratory in order to address the power quality current control based on circular hysteresis areas of a three-phase
issues related to inverter-coupled generation and associated neutral point-clamped inverter. IEEE Trans Ind Electron 57:2669–
loads. 2678

123
Electr Eng

19. Lewicki A, Krzeminski Z, Abu-Rub H (2011) Space–vector pulse 25. Sergio B, Josep B, Dushan B, Sergio S (2004) The nearest three
width modulation for three-level NPC converter with the neutral virtual space vector PWM–A modulation for the comprehensive
point voltage control. IEEE Trans Ind Electron 58:5076–5086 neutral-point balancing in the three-level NPC inverter. IEEE
20. Xiyou C, Kazerani M (2006) Space vector modulation control of an Power Electron Lett 2:11–15
AC–DC–AC converter with a front-end diode rectifier and reduced 26. Mishra MK, Joshi A, Ghosh A (2003) Control schemes for equal-
dc-link capacitor. IEEE Trans Power Electron 21:1470–1478 ization of capacitor voltages in neutral clamped shunt compensator.
21. Huibin Z, Finney SJ, Massoud A, Williams BW (2008) An SVM IEEE Trans Power Deliv 18:538–544
algorithm to balance the capacitor voltages of the three-level NPC 27. Yong L, Yanjian P, Fang L, Denis S, Daniil P, Chonggan L, Long
active power filter. IEEE Trans Power Electron 23:2694–2702 L, Yijia C (2016) A controllably inductive filtering method with
22. Bouhali O, Francois B, Berkouk EM (2007) DC link capacitor volt- transformer-integrated linear reactor for power quality improve-
age balancing in a three-phase diode clamped inverter controlled ment of shipboard power system. In: IEEE transactions on power
by a direct space vector of line-to-line voltages. IEEE Trans Power delivery
Electron 22:1636–1648 28. Shengwei L, Yongli L, Jingliao S, Qiang J, Xuguang L (2009) A
23. Dongsheng Z, Didier GR (2001) Experimental comparisons of novel control algorithm for inverter-based distributed generation
space vector neutral point balancing strategies for three-level topol- in unbalanced three phase power systems, In: International confer-
ogy. IEEE Trans Power Electron 16:872–879 ence on sustainable power generation and supply, Nanjing, China,
24. Nikola C, Dushan B (2000) A comprehensive study of neutral-point pp 1–6
voltage balancing problem in three-level neutral-point-clamped
voltage source PWM inverters. IEEE Trans Power Electron
15:242–249

123

You might also like