1 2 3 Type Sequence Batch Conventional Membrane Bio - Reactor (SBR) Reactor (MBR) Supplier Enviromec Enviro Water Enviro Water - International (Pvt) Systems (Pvt) Systems (Pvt) Ltd. Ltd. Ltd. Capacity (m3/day) 80 85 85 80 Raw Effluent Quality - BOD5 (mg/l) 350 200 - 300 200 - 300 < 350 - COD (mg/l) 600 400 - 600 400 - 600 < 600 - Total Dissolved 450 400 - 600 400 - 600 < 500 Solid (mg/l) 3 - 30 < 10 < 10 < 30 - Oil & Grease 6.5 - 8.0 6.0 - 8.5 6.0- 8 .5 6.5 – 8.5 (mg/l) - pH Treated Water Quality < 15 < 30 <3 <5 - BOD5 (mg/l) < 100 < 250 < 30 < 30 - COD (mg/l) < 20 < 50 <3 < 20 - Total Dissolved < 10 < 10 <1 < 10 Solid (mg/l) 6.5 - 8.0 6.0 - 8.5 6.5 - 8.0 6.5 – 8.0 - Oil & Grease (mg/l) - pH Treated Water Will be reused up to To be discharged Shall be reused or Shall be reused for Discharge maximum extent for to the flowing discharged to rain gardening and / or gardening and also water body for 8 water drain. soaking in to the allowed for ground time dilution. soil. water infiltration Excess shall be through perforated discharged to the piping arrangement nearby storm water within the premises road drain. and excess (if any) will be discharged to the nearby drain or will be disposed by mean of municipal gully emptier. Item Proposal Recommended 4 5 Type Sequence Stabilizing Membrane Bio Reactor - Activated SludgeBatch (MBR) (SSB) Supplier Aquablue Lanka (pvt) Ltd Samurai Engineering - Services & Consultantce (pvt) Ltd Capacity (m3/day) 85.5 50 80 Raw Effluent Quality - BOD5 (mg/l) 300-400 350 < 350 - COD (mg/l) 500-600 600 < 600 - Total Dissolved 250-350 400 < 500 Solid (mg/l) 30-50 Not specified < 30 - Oil & Grease 6.0 - 8.5 Not specified 6.5 – 8.5 (mg/l) - pH Treated Water Quality - BOD5 (mg/l) <8 <5 <5 - COD (mg/l) <30 < 250 < 30 - Total Dissolved <14 < 10 < 20 Solid (mg/l) <0.5 Not specified < 10 - Oil & Grease 7.5 Not specified 6.5 – 8.0 (mg/l) - pH Treated Water Allows to water to be Not specified Shall be reused for Discharge easily and properly gardening and / or managed, for easy soaking in to the soil. Soaking, Reuse or Excess shall be discharged to the Discharge according to nearby storm water norms. road drain.