Minimum sizes of LV switchrooms

Minimum size of LV switchrooms A12(b)


Main circuit breaker rating Intake room dimensions
(A) (m)

1600 - 2500 3.5 x 3.5


1000 - 1200 3.0 x 3.0
600 - 800 2.5 x 2.5
400 - 500 2.5 x 2.0
200 - 300 2.0 x 2.0

Note: the above rooms sizes are given for guidance and other requirements for
access and safety should be taken into account (see Regulation 3.5, 4.2
and Appendix A12(d)).

The Electricity Wiring Regulations (Third Edition) 169