OWNERS AFRY CONSULT INDIA PRIVATE LIMITED ENGINEERING SUBJECT:-ICOG TO SUBPOLING List of Documents : 1 Design Methodology 2 Derating factor chart 3 Calculation 4 Cable GTP Design Methodology DESIGN BASIS & ASSUMPTIONS
Cables shall be sized based on the following considerations:
A Short circuit withstand capability B The voltage drop in the cable C Derated current of cable after installation (Derated Current capacity of cable (A) Design Parameters Following parameters are used as design inputs Sr.No Description Parameter Reference 1 Maximum system 25kA (rms) for One (0.3) sec 2 Maximum conductor temperature for 90ºC 3 Ambient Air temperature 50ºC 4 Temperature coefficient of Al. per deg C 0.004308 Table-A De-rating factors for various conditions of installations including the following shall be considered while selecting the cable sizes:
K1- (b)Variation in Air temperature 50 Deg. Cent. 0.89
K2- Grouping derating factor of Cables touching laid horizontal formation 0.82 K3- Derating Factor for variation in depth of laying @1200mm for 300mm2 N/A
Earthed cable Seletion
As Per power evacuation system, power transformers are star point solidly grounded so cable shall be earhed 33 KV H.T Cable Table-B 33KV HT THREE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED CABLES Equiv. Star Resistance (ohm / Reactance Voltage Sl No Cable Size (Sq. mm) AIR Permissible Ampacity in Amps km) at 90 deg C * (ohm/ Km at 50 Grade Hz) # 1 3C x 240 400 0.16 0.106 33 KV (E) Cable Catalouge * May very as per approved make
(A) Short circuit withstand capability
A = Is x Root(t) / K Sq.mm (As per IEC 60949 or 60724) Is = Max. System Fault current t = Duration of fault current in second K = Constant K for Al. Conductor XLPE= 0.094 A =Min. cross Section area in sq.mm (b) The voltage drop in the cable
As per IE Rule no. 54 the Voltage Variation shall not be permitted
(i) In the case of low or medium voltage(11kV), by more than 6 per cent, & with the Transformer available Tap setting Range of +5% would be
ΔVR = √ 3 x I x (R x Cos Φ + X x Sin Φ) x L / (N x 1000)
ΔVR =Total voltage drop in cables IR =Running current of feeder in Amps Cos Φ = Running power factor of feeder R = AC resistance of selected cable at 90 ºC in Ohm / Km X = Reactance of selected cable in Ohm / Km L = Length of cable in Meters N = No. of runs of cables per phase 400MW KHAVDA SOLAR PARK-P4 , GUJRAT (C ) Derated Current capacity of cable (A) K=K1xKxK3XK4 Derated Current capacity of cable (A)=Ampacity of cable X overall derating factor Cable Selection Case Study Cable sizing Transformer to Sub Pooling
Rated Load of the feeder (kVA)= 26400KVA
Nominal voltage = 33KV Maximum system fault level= 25 kA Line current in Amps 26400/(1.732x11) Line current in Amps 461.9 Max Cable Length (mtr) 950 (A) Short circuit withstand capability A = Is x Root(t) / K Sq.mm (As per IEC 60949 or 60724) Is = Max. System Fault current t = Duration of fault current in second K = Constant K for Al.Conductor XLPE A =Min. cross Section area in sq.mm Is 25 t Permissible Short Circuit current of XLPE insulated cables oprate shor circuit K Constant K for Al.Conductor XLPE=0.094 A= (25x√0.3)/0.094 A= 145.670893 Minimum cross section of cable
Verification of cable size for short circuit withstand capability
(b) The voltage drop in the cable ΔVR = √ 3 x I x (R x Cos Φ + X x Sin Φ) x L / (N x 1000 x V ) ΔVR =Total voltage drop in cables I =Running current of feeder in Amps Cos Φ = Running power factor of feeder R = AC resistance of selected cable at 70 ºC in Ohm / Km X = Reactance of selected cable in Ohm / Km L = Length of cable in Meters N = No. of runs of cables IR= 461.9 Cos Φ = 1 Sin Φ = 0.000 R @ 50 Degree = 0.13 Refer Table-B 3C X 240mm2 X = 0.106 Refer Table-B 3C X 240mm2 L = 950 N = 2 ΔVR = (1.732x461.9x(0.16x1+0.104*0)x(35) 1x1000 ΔVR = 50.32 Volt %ΔVR = ΔVR/V 5032.29 33000 %ΔVR = 0.15249 The Voltage Drop is within (C ) Derated Current capacity of cable (A) K= Overall Derating Factor K1- (b)Variation in Air temperature 50 Deg. Cent. 0.89 K2- Grouping derating factor of Cables touching laid horizontal formation 0.82 K3- Derating Factor for variation in depth of laying @1200mm for 300mm2 N/A K= K1- (b) X K-3 K= 0.73 The overall derating factor for the 33 kV power cables installed in Air=0.73
Derated Current capacity of cable (A)=Ampacity of cable XOverall derating factor
Ampacity of3C X 240mm2 cable= 400 Refer Table-B 3C X 240mm2 Derated Current capacity of cable (A)= 400x0.73 Derated Current capacity of cable (A)= 291.92 Full Load current of Equipment(Line current) 461.9 461<291.9 Derated Current capacity of cable (A)> Full Load current of Equipment