You are on page 1of 10

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/321126979

Triple droop control method for ac microgrids

Article  in  IET Power Electronics · October 2017


DOI: 10.1049/iet-pel.2017.0005

CITATIONS READS

2 37

3 authors, including:

Yonggang Peng
Zhejiang University
45 PUBLICATIONS   133 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

hybrid AC/DC Microgrid View project

Automation and Robot View project

All content following this page was uploaded by Yonggang Peng on 19 December 2017.

The user has requested enhancement of the downloaded file.


IET Power Electronics

Research Article

Triple droop control method for ac microgrids ISSN 1755-4535


Received on 3rd January 2017
Revised 20th May 2017
Accepted on 27th June 2017
E-First on 17th July 2017
doi: 10.1049/iet-pel.2017.0005
www.ietdl.org

Yanghong Xia1, Yonggang Peng1 , Wei Wei1


1Department of Electrical Engineering, Zhejiang University, Hangzhou 310027, People's Republic of China
E-mail: pengyg@zju.edu.cn

Abstract: In this study, a novel droop control method for ac microgrids is proposed to enhance the performance of power
regulation, which is composed of three parts. The angle droop and the frequency droop are adopted to control the active power
in coordination, while the modified voltage droop is used to control the reactive power. There are several improvements in this
proposed triple droop control method compared with the conventional droop control. First, the dynamics of active power
regulation are enhanced because of the angle droop. Second, the stability of the system is upgraded and the droop coefficients
can vary in greater range. Third, the accuracy of reactive power regulation is improved, especially in the grid-connected mode,
the DGs can output the specified reactive power with the modified voltage droop, which benefits the economic dispatch of the
microgrid. Through these three combined droop control strategies, the performance of the whole system can be improved a lot
whether in the grid-connected mode or the islanded mode. Furthermore, the stability of the proposed triple droop control is
analysed, which shows that the stability of the system is upgraded. The effectiveness of the proposed control method is verified
by the hardware-in-loop tests.

1 Introduction at the resistive line impedance, a method applying global voltage as


a feedback signal is proposed in [11] to keep the accurate active
Microgrids are getting more and more attention because of the power sharing. Li et al. [12] propose that virtual impedance can be
pressure from environment and resource. To manage the DGs in adopted to improve the performance of droop control and analyse
the microgrid, many control methods have been researched in the power flow for low-voltage AC and DC microgrids considering
published literatures. The master–slave control methods based on droop control and virtual impedance. From another perspective, a
the fast communication system have been proposed in [1, 2]. It droop method with coupling of active and reactive power is
needs a centralised information device to collect information of the introduced in [13], which can realise accurate power sharing. To
entire slave DGs, thus the system reliability is degraded due to the keep the frequency nominal in the islanded mode, angle droop is
single point of failure. proposed in [14–16], which only considers the islanded mode
To improve the reliability, the droop control method is widely without consideration of mode switching. Furthermore, for the pure
studied. For the conventional droop control under the condition angle droop, the accuracy of the active power sharing cannot be
that the line impedance is mainly inductive, the frequency droop ensured.
and voltage droop strategies are used to control the active and On the other hand, the secondary control strategies are proposed
reactive power, respectively [3–5]. However, there are some to enhance the performance of the conventional droop control.
limitations when the conventional droop is adopted. On the one Through directly collecting the global information, centralised
hand, since the voltage droop controller is just a proportional control methods are presented in [17–19]. Especially in [19], for an
controller, the DGs cannot output the specified reactive power in online uninterruptible power system with resistive line impedance,
the grid-connected mode. Moreover, the great difference of line a reactive power to phase droop strategy is proposed to keep the
impedances among different DGs will result in inaccuracy of system frequency at 50 Hz for different load conditions. At the
reactive power sharing in the islanded mode [6, 7]. On the other same time, a centralised secondary controller is employed to
hand, the active power is only controlled by the frequency which is compensate voltage sags and phase drift due to the droop control.
integrated with time into angle. Therefore, the dynamics of the Then, the voltages of load side are always synchronised with the
active power are very slow and the stability margin is small. At the utility voltages, which results in a much simpler bypass connection
same time, there are large deviations of frequency. To overcome process. Because of the low reliability of the centralised control
those disadvantages mentioned above, many modified versions of methods, distributed control methods based on the communication
droop control have been investigated in some existing literatures. with the neighbour DGs are proposed in [20–26] to increase the
Sun et al. [8] reveal the similarities and differences of virtual reliability and scalability of the system. The global information
impedance, angle droop and frequency droop. Based on these new required to enhance the performance of the microgrid is estimated
perspectives, a unified control law is proposed and the physical based on multi agent systems in the secondary level [20], then a
meaning of corresponding controller parameters is obvious, which corresponding adaptive droop strategy is proposed and it can
benefits the designing and tuning of the controller. From another operate in different modes. Considering the gap between large
point of view, Guerrero et al. [9] think that the droop control time-scale economic dispatch (ED) and small time-scale automatic
method is a proportional controller and propose that using a PID voltage control (AGC), Li et al. [21] propose an agented-based
controller but not only a proportional controller could enhance the distributed secondary control strategy by integrating AGC and ED
dynamics of the system. Similarly, a H∞ control method is together seamlessly to increase the economical efficiency of a
proposed in [10] to regulate the frequency in the islanded mode, microgrid. In addition, a hierarchical control strategy that is
which can increase the robustness of the system. In the low-voltage compatible with droop control for islanded microgrids is also
microgrids, the line impedance is usually not inductive but high reported in [27, 28].
ratio of R/ X, hence the active and reactive power sharing will be To enhance performance of power regulation, a triple droop
not accurate according to the conventional droop control. Aiming control method is proposed in this paper. The triple droop control is

IET Power Electron., 2017, Vol. 10 Iss. 13, pp. 1705-1713 1705
© The Institution of Engineering and Technology 2017
Fig. 1  Configuration and the proposed control method for ith DGs
(a) Configuration of the inverter, (b) Inner loop control method, (c) Outer loop control method

composed of three parts, that is, the frequency droop, the angle resistance R1, while C is the filter capacitance. Lline and Rline are the
droop and the modified voltage droop. First, the frequency droop line inductance and resistance between the DG and the microgrid
and angle droop are combined to control the active power, that is, bus. As shown in many literatures, the line between the DG and the
the phase angle of the output voltage is controlled by a PI bus is the high ratio of R/ X . Therefore, the frequency or angle
controller instead of an integral controller. Compared to the pure versus the active power and the voltage versus the reactive power
frequency droop, the combined control method can make the strategy are not proper anymore, but many solutions have been
dynamics of the active power faster and the frequency deviations proposed to solve this problem such as the virtual impedance or the
of the microgrid can be decreased with appropriate angle and method in [13] and so on. This is not the key point of this paper,
frequency droop coefficients. At the same time, the stability margin hence we think that the line is still inductive by adding extra
of the system is also increased. In addition, compared to the pure inductance or adopting the virtual impedance. Then, the frequency
angle droop, the combined droop can make the DGs output the or angle versus the active power and the voltage versus the reactive
specified active power in the grid-connected mode. Further, in the power strategy can be still adopted.
islanded mode, the DGs can share the active power accurately. The inner loop is mainly to control the output voltage vo to
Second, the modified voltage droop is adopted to control the follow the reference voltage generated by the outer loop. There are
reactive power. Being different from the conventional voltage many different control methods about output voltage control of the
control, the modified voltage droop is mainly using the output inverter [29, 30]. The conventional dual-loop control method based
voltage as feedback signal to control the output reactive power. on the Park transform is adopted in this paper. Fig. 1b shows the
With an adaptive droop curve, the DGs can output specified control block diagram for d-axis, where the coupling parts of q-axis
reactive power in the grid-connected mode, which the conventional are omitted. The current loop controls the current i1 with a
droop control can hardly realise. Furthermore, after appropriate proportional controller Gc s = KiP to increase the damping of the
simplification, the stability of the proposed triple droop control
system and to make the system stable, while the voltage loop
method is analysed. Through the stability analysis, it can be
controls the output voltage vo with a proportional-integral (PI)
conclude that the stability of the system is upgraded and the droop
coefficients can vary in greater range. The effectiveness of the controller Gv s = KvP + KvI /s to realise the accurate tracking.
proposed control method is verified by results obtained through the
real-time hardware-in-loop (HIL) tests based on the RTLAB and 2.2 Control strategy of the outer loop
STM32F407 MCUs.
The outer loop is mainly composed of the proposed triple droop
This paper is organised as follows. In Section 2, the proposed
control method, which provides the reference voltage for the inner
control method is introduced in detail. Section 3 analyses the
loop and realises the power sharing. The triple droop control
stability of the proposed control method. Then in Section 4, the
method is introduced in detail as follows.
effectiveness of the proposed control method is verified by results
As depicted in Fig. 2a, the power from the DG to the bus can be
of the contrast experiment based on the HIL tests. Finally, Section
calculated as
5 summarises this paper and draws the conclusions.
3 V busVsin θ 3 V busVθ
2 Description of the proposed control method P= ⋅ ≃ ⋅
2 X 2 X
The whole control method consists of two parts, namely the inner 2 2
, (1)
3 V − VV buscos θ 3 V − VV bus
loop and outer loop. As shown in Fig. 1, the main function of the Q= ⋅ ≃ ⋅
2 X 2 X
inner loop is to realise the accurate voltage tracking, while the
main function of the outer loop is to realise the power sharing and
if the phase angle difference θ is very small. V bus and V are the
provide the reference voltage for the inner loop.
magnitude of bus voltage and output voltage of the DG,
respectively, X is the line impedance.
2.1 Control strategy of the inner loop From (1), it can be concluded that the output active power can
As shown in Fig. 1a, the inverter is connected to the microgrid bus be controlled by θ and the output reactive power can be controlled
through a LC filter. L1 is the filter inductance with parasitic by V. Further, the phase angle difference θ can be controlled by the
frequency droop and angle droop, while the voltage magnitude V
1706 IET Power Electron., 2017, Vol. 10 Iss. 13, pp. 1705-1713
© The Institution of Engineering and Technology 2017
Fig. 2  Schematic of the triple droop control
(a) Simplified circuit diagram, (b) Moment for connection, (c) Frequency droop, (d) Angle droop, (e) Modified voltage droop

can be controlled by the voltage droop. It should be noted that there Qimax − Qimin
ni ≥ ,
is a synchronisation process because of the introduction of angle V max − V min
droop, therefore the moment when the DG is connected to the
microgird is not arbitrary. An alternative is that the DG is where Qimax and Qimin are the maximum and minimum output
connected to the microgrid when the curve of bus voltage restarts reactive power of the inverter..
as shown in Fig. 2b.
The control law of the frequency and angle droop can be
expressed as 2.3 Characteristics of the proposed control method
The basic principle of the proposed control method has been
f i = f ∗ + m f i Pi∗ − Pi ; i f Pimin < Pi < Pimax introduced in Part 2.1 and 2.2. In this part, the characteristics of the
CPM : Pimax (or Pimin); i f Pi ≥ Pimax (or ≤ Pimin) proposed triple droop control are analysed.
, (2) In the grid-connected mode, the frequency of the system is
δi = mδi Pi∗ − Pi ; i f Pimin < Pi < Pimax clamped at f ∗ by the utility. According to Fig. 1c, Figs. 2c and (2),
CPM : Pimax (or Pimin); i f Pi ≥ Pimax (or ≤ Pimin) the output active power of the ith DG must be Pi∗ . That is, the DGs
can output specified active power in the grid-connected mode. In
where i = 1, 2, … denotes the different DGs, f ∗ denotes the rated the islanded mode, all the DGs will operate at a new frequency f ∗ ′
frequency of the system, Pi∗ is the specified active power of the ith when the system is in the steady state, or the system will be
DG injecting to the bus in the grid-connected mode, Pi is the unstable. Therefore, the frequency difference of all the DGs is the
same. According to Figs. 1c, 2c and (2), the active power changes
actual output active power of the ith DG. When the output active
of the ith DG ΔPi can be calculated as
power of the DG reaches the limiting value (the maximum or the
minimum value), the regulation capability of the DG also reaches
its limitation. Therefore, the DG operates into the constant power f∗ − f ∗′
ΔPi = Pi − Pi∗ = . (4)
mode (CPM) and outputs the maximum or minimum active power. mf i
The droop coefficients m f i, mδi can be chosen as
From (4), it can be conclude that the active power changes of DGs
f max − f min δimax − δimin are inversely proportional to the droop coefficients m f i, hence the
0 ≤ mf i ≤ , 0 ≤ mδi ≤ , active power can be accurately shared by DGs, which the pure
Pimax − Pimin Pimax − Pimin
angle droop is hard to realise.
where Pimax and Pimin are the maximum and minimum output active On the other hand, the conventional pure frequency droop is
power of the ith DG, f max and f min are the allowable maximum just like an integral controller, while the combined frequency and
angle droop is like a PI controller as shown in Fig. 1c. Hence, the
and minimum value of the frequency, δimax and δimin are the set dynamics of the system can be enhanced. Compared to the
maximum and minimum value of phase angle with consideration of conventional droop control, for the same response speeds, the
the capacity of the inverter. frequency droop coefficients can be smaller in the proposed droop
The control law of the modified voltage droop can be expressed control, so the frequency deviations of the microgrid can be
as decreased under the condition that m f i and mδi are matched each
other.
Qire f = Qi∗ + ni V ∗ − V i ; i f V i > V iH (or < V iL) For the reactive power control, when the microgrid is in the
CPM: Qi∗; i f V iL < V i < V iH , (3) grid-connected mode, the magnitude of the output voltage changes
within the interval [V iL, V iH ], the reference output reactive power is
CPM : Qimax (or Qimin); i f V i ≥ V max (or ≤ V min)
Qi∗ as shown in Figs. 2e and (3). With a PI controller as shown in
Fig. 1c, the DG can output the specified reactive power, which is
where i = 1, 2, … denotes the different DGs, V ∗ denotes the rated hard to be realised by the conventional voltage droop. In the
output voltage of the DGs, V max and V min are the allowable islanded mode, the magnitude of the output voltage changes
maximum and minimum value of the voltage, while V iL and beyond the interval [V iL, V iH ], hence the voltage droop starts to
V iH are the set maximum and minimum output voltage of the work. With assumption that Qi can track Qire f accurately and
DGs in the grid-connected mode with consideration of the capacity
according to (3), the reactive power changes of the ith DG ΔQi in
of the inverter, Qi∗ is the specified reactive power of the ith DG
the steady state can be calculated as
injecting to the bus in the grid-connected mode, the output of the
droop controller Qiref is the reference output reactive power of the ΔQi = Qi − Qi∗ = ni V ∗ − V i . (5)
ith DG. Similarity, when the output reactive power of the DG
reaches the limiting value, the regulation capability of the DG also From (5), it can be concluded that the changes of the reactive
reaches its limitation, hence the DG operates into the constant power of the DGs are proportional to the droop coefficients ni
power mode and outputs the maximum or minimum reactive omitting the influence of the voltage drop across the line
power. Finally, the actual output reactive Qi is fed back to track impedance. If considering this influence, decreasing the droop
Qire f accurately by a PI controller GQ s = KQP + KQI /s as shown in coefficients ni can improve the accuracy of the reactive power
Fig. 1c. The droop coefficients ni can be chosen as sharing.

IET Power Electron., 2017, Vol. 10 Iss. 13, pp. 1705-1713 1707
© The Institution of Engineering and Technology 2017
As depicted in Section 2.2, the phase angle of the output voltage of
the DG is synchronised with the phase angle of the bus voltage,
hence the following equations can be concluded

ẋ1 = 2π m f P∗ − x2 + ( f ∗ − f g)
θ = x1 + mδ P∗ − x2
, (8)
ẋ3 = KQI n V ∗ − V + Q∗ − x4
ΔV = x3 + KQP n V ∗ − V + Q∗ − x4

where f g is the frequency of the microgrid. Combining (7) and (8),


the state equation of the whole system can be derived as,

Ẋ = AX + U
, (9)
Fig. 3  Control block of the triple droop control method Y = CX

In conclusion, in the gird-connected mode, the proposed triple 2π(m f P∗ + f ∗ − f g)


droop control method can make the DGs output specified active ∗
x1 3 V busV
and reactive power, which benefits the economic dispatch of the ⋅ mδP∗
microgrid. While in the islanded mode, the active power and 2 τX
x2
reactive power can be well shared by the DGs according to the X= , U= KQI ,
x3 Q∗
droop coefficients which are set with consideration of the capacity 1 + nKQP
of DGs. Furthermore, the dynamics of the system are enhanced. x4
3 2V ∗ − V bus KQP ∗ V ∗ V ∗ − V bus
With appropriate parameters, the frequency deviations caused by ⋅ Q +
the frequency droop in the islanded mode can be decreased. 2 τX(1 + nKQP) τX
P x2 0 1 0 0
Y= = ,C = ,
3 Stability analysis Q x4 0 0 0 1
In this section, the stability of the proposed triple droop control is
analysed based on the typical single-machine-infinite-bus system. (see equation below) From the system matrix A of (9), it can be
To simplify the analysis, the inner loop is viewed as ‘1’, that is, concluded that the active power control and reactive power control
vo = vo∗ (also, V = M). The situation when the DGs operate in the is decoupled with assumption that the angle difference θ and the
droop mode is analysed and the situation when the DGs operate in magnitude change V are small. Therefore, A is stable if and only if
the constant power mode is not analysed because it is relatively A1 and A2 are both stable.
easier. Based on the above analysis, the whole outer loop is The eigenequation of A1 is
presented in Fig. 3 in the form that is suitable for the stability ∗
analysis, in which the subscript i is omitted and four state variables 1 3 V busV V busV ∗
s2 + + ⋅ mδ s + 3πm f = 0. (10)
are selected. τ 2 τX τX
As shown in Fig. 3, the power feedback signals (P and Q) are
filtered by two first-order filters with time constant τ. With According to the Routh criterion, A1 is stable. From (10), it can be
assumption that V = M = V ∗ + ΔV, the P and Q can be expressed concluded that mδ increases the system damping, therefore the
as stability of the system is improved. The changes of dominant poles
of active power control along with coefficients m f and mδ are
1 1 3 V busVsin θ depicted in Figs. 4a and b, respectively, based on (10), where the
P= ⋅ Pm = ⋅ ⋅
τs + 1 τs + 1 2 X other parameters are shown in Table 1.
2
. (6) If the conventional frequency droop strategy is adopted to
1 1 3 V − VV buscos θ
Q= ⋅ Qm = ⋅ ⋅ control the active power, we can obtain the eigenequation of active
τs + 1 τs + 1 2 X
power control by setting mδ as zero, that is,
Choosing P, Q as state variables x2, x4 and considering that the ∗
angle difference θ and the magnitude change ΔV are usually very 1 V busV
s2 + s + 3πm f = 0. (11)
small, then (6) can be simplified as τ τX

3 V busV
∗ Comparing (10) and (11), it is obvious that the damping of
τẋ2 = − x2 + ⋅ θ conventional frequency droop strategy is less than that of the
2 X
. (7) proposed angle plus frequency droop strategy, that is, lacking the
∗ ∗ ∗
3 2V − V bus 3 V (V − V bus) term (3/2) ⋅ (V busV ∗ /τX)mδ, which also meets the analysis of [8].
τẋ4 = − x4 + ⋅ ⋅V + ⋅
2 X 2 X The changes of dominant poles of conventional droop control
along with droop coefficient m f are depicted in Fig. 4e based on
(11), in which the other parameters are shown in Table 1.

0 −2πm f 0 0
∗ ∗
3 V busV 1 3 V busV
⋅ − + ⋅ mδ 0 0
2 τX τ 2 τX
A1 0
A= = nKQI KQI .
0 A2 0 0 − −
1 + nKQP 1 + nKQP
3 2V ∗ − V bus ∗
1 3 2V − V bus KQP
0 0 ⋅ − + ⋅
2 τX(1 + nKQP) τ 2 τX(1 + nKQP)
1708 IET Power Electron., 2017, Vol. 10 Iss. 13, pp. 1705-1713
© The Institution of Engineering and Technology 2017
Fig. 4  Root locus of the system
(a) Dominant Poles of active power when m f changes from 10−7 to 10−4 Hz/W, (b) Dominant Poles of active power when mδ changes from 10−7 to 10−4 rad/W, (c) Dominant
Poles of reactive power when n changes from 1 to 8000 Var/V, (d) Dominant Poles of reactive power when KQP changes from 10−4 to 10−2 V/Var, (e) Dominant Poles of
conventional droop control when m f changes from 10−7 to 10−4 Hz/W


Compared to Fig. 4a, the dominant poles in Fig. 4e is closer to the 1 3 2V − V bus KQP nKQI
imaginary axis, which means that the stable margin of the system is s2 + + ⋅ + s
τ 2 τX 1 + nKQP 1 + nKQP
decreased. ∗
(12)
The eigenequation of A2 is nKQI 3 2V − V bus KQI
+ + ⋅ = 0.
τ(1 + nKQP) 2 τX(1 + nKQP)

Generally speaking, V ∗ ≥ V bus, hence according to the Routh


criterion, A2 is stable. Furthermore, because A1 and A2 are both
stable, the whole system is stable. The changes of dominant poles

IET Power Electron., 2017, Vol. 10 Iss. 13, pp. 1705-1713 1709
© The Institution of Engineering and Technology 2017
of reactive power control along with coefficients n and KQP are output specified active power accurately in the grid-connected
depicted in Figs. 4c and d, respectively, based on (12), in which mode, that is, DG1 ≈ 20 kW and DG2 ≈ 10 kW. In the islanded
KQP = 100KQI and the other parameters are shown in Table 1. mode, the DGs can compensate the active power shortage quickly
From the figures, we can see that the system is still stable when to maintain the active power balance. Also, the active power can be
the control parameters vary in large range. That is, the stability of shared according to 2 : 1 accurately by DGs. That is, before the
the system is upgraded with the proposed triple droop control load step change, DG1 ≈ 16.3 kW and DG2 ≈ 32.5 kW, after the
method. load step change, DG1 ≈ 61.25 kW and DG2 ≈ 30.5 kW. Fig. 6b is
a larger version of Fig. 6a when the load increases, it shows that
the running time of the active power regulation is about 170 ms.
4 HIL tests Fig. 6c shows the output reactive power changes of DGs. The
In this paper, HIL tests depicted in Fig. 5 are designed to verify the DGs can output specified reactive power accurately in the grid-
effectiveness of the proposed control method. As Fig. 5a shows, connected mode, that is, DG1 ≈ 14 kVar and DG2 ≈ 7 kVar, which
the studied microgrid system contains two DGs and one load. The the conventional droop control is hard to realise. In the islanded
HIL tests are conducted through the RT/LAB and STM32F407 mode, the DGs can compensate the reactive power shortage
MCUs. The configuration of the HIL tests is shown in Fig. 5b. quickly to maintain the reactive power balance. Before the load
The rated bus voltage V b∗ is 311 V and the rated frequency f ∗ is step change, DG1 ≈ 23 kVar and DG2 ≈ 12 kVar, after the load step
50 Hz, the rated load power is 51 kW + j33 kVar under the rated change, DG1 ≈ 51 kVar and DG2 ≈ 29 kVar. Due to the voltage
voltage and frequency. In the grid-connected mode, the DGs drop across the line impedance, the reactive power sharing is not
provide power about 30 kW + j21 kVar and the rest power is very accurate. Further, because the line impedance consumes some
provided by the utility. The active power and reactive power reactive power, the total reactive power of two DGs is bigger than
sharing between the DG1 and DG2 are both 2 : 1. The other the load reactive power.
parameters are shown in Table 1. Fig. 6d shows the load power changes. Due to the droop
Fig. 6 shows the results of the proposed triple droop control. control, the bus voltage is lower than the rated value. Therefore,
The microgrid is started up in the grid-connected mode and then is the load power is lower than the rated power. Fig. 6e shows the bus
switched into the islanded mode. Furthermore, a load step change voltage changes, only the difference ΔV b between the actual bus
occurs in the islanded mode and the load power increases to 102  voltage V b and the rated bus voltage V b∗ is represented. From
kW + j66 kVar under the rated voltage and frequency. Fig. 6a Fig. 6e, it can be concluded that the bus voltage can be maintained
shows the output active power changes of DGs. The DGs can within reasonable range (−7% ∼ +7%). Fig. 6f shows the frequency
changes, similarly, only the difference Δ f between the actual
frequency f and the rated frequency f ∗ is represented. From Fig. 6f,
Table 1 System parameters we can see that the frequency can be maintained within reasonable
Parameters DG1 DG2 range (−0.2 ∼ +0.2 Hz) too.
Rline /Lline 0.5 mΩ/1.5 mH 0.5 mΩ/1.5 mH In addition, a contrast experiment between the conventional
Rg /Lg 0.1 mΩ/0.5 mH droop control method and the proposed triple droop control method
is conducted to show the improved performance. In the contrast
LC filters 3 mH/2 mF 3 mH/2 mF
experiment, the outer loop is changed into the conventional droop
parasitic resistance 2 mΩ 2 mΩ control and the output power sharing between the DG1 and DG2 is
P∗ 20 kW 10 kW 2 : 1. Specifically, f i = f ∗ + mi Pi∗ − Pi , V i = V ∗ + ni Qi∗ − Qi ,
mδ 1/4 × 10−2 rad/kW 1/2 × 10−2 rad/kW where m1 = 1/12 × 10−2 Hz/kW, m2 = 1/6 × 10−2 Hz/kW and
mf −2
1/12 × 10 Hz/kW 1/6 × 10−2 Hz/kW n1 = 1/4 V/kVar, n2 = 1/2 V/kVar. The inner loop and other
Q ∗ 14 kVar 7 kVar parameters are the same as Table 1. Fig. 7 shows the results of the
conventional droop control.
n 4 kVar/V 2 kVar/V
Fig. 7a shows the output active power changes of DGs. The
KQP 5 × 10−4 V/Var 5 × 10−4 V/Var DGs can output specified active power accurately in the grid-
KQI 5 × 10−2 V/Var ⋅ s 5 × 10−2 V/Var ⋅ s connected mode, that is, DG1 ≈ 20 kW and DG2 ≈ 10 kW. In the
[V L, V H ] [305, 315 V] [305, 315 V] islanded mode, the two DGs can share the active power according
to 2 : 1, but the dynamics are very slow. As shown in Fig. 7b which
τ 0.02 s 0.02 s
is a large version of Fig. 7a when the load power increases, the
KvP, KvI 0.4 A/V, 100 A/V ⋅ s 0.4 A/V, 100 A/V ⋅ s running time of the active power is ∼600 ms, which is much longer
KiP 2 V/A 2 V/A than the running time shown in Fig. 6b.

Fig. 5  HIL tests


(a) Studied ac microgrid system, (b) HIL tests setup

1710 IET Power Electron., 2017, Vol. 10 Iss. 13, pp. 1705-1713
© The Institution of Engineering and Technology 2017
Fig. 6  Dynamics of the system based on the proposed triple droop control
(a) Output active power of the DGs, (b) Active power regulation when the load increases, (c) Output reactive power of the DGs, (d) Load power, (e) Changes of the bus voltage
ΔV b(ΔV b = V b − V b∗), (f) Changes of the frequency Δ f (Δ f = f − f ∗)

Fig. 7c shows the output reactive power changes of DGs. The frequency f ∗ is represented. The frequency can be maintained
DGs cannot output specified reactive power accurately in the grid- within reasonable range (−0.2 ∼ +0.2 Hz).
connected mode. Further, the reactive power sharing in the From the above results of the contrast experiment, it can be
islanded mode is worse than that in Fig. 6c. In conclusion, the concluded that the proposed triple droop control method can
reactive power regulation of the conventional droop control is improve the performance of the system compared with the
worse than that of the proposed triple droop control. conventional droop control method.
Fig. 7d shows the load power changes. Because of the droop
control, the bus voltage is much lower than the rated value.
5 Conclusion
Therefore, the load power is much lower than the rated power. In
addition, the power comes down more drastically than the load A novel triple droop control method for ac microgrids is researched
power shown in Fig. 6d. Fig. 7e shows the bus voltage changes, in this paper, which consists of three parts. The angle droop and the
only the difference ΔV b between the actual bus voltage V b and the frequency droop are adopted to control the active power in
rated bus voltage V b∗ is represented. From Fig. 7e, it can be coordination, while the modified voltage droop is used to control
concluded that the bus voltage drop is very big and cannot be the reactive power. There are several improvements in this
maintained within reasonable range (−7 ∼ +7%). Especially when proposed triple droop control method compared with the
the load increases, the voltage has reached the threshold value conventional droop control. First, the dynamics of active power
(290 ∼ 332 V). Fig. 7f shows the frequency changes, also only the regulation are enhanced because of the angle droop. Second, the
difference Δ f between the actual frequency f and the rated stability of the system is upgraded and the droop coefficients can
vary in greater range. Third, the accuracy of reactive power
IET Power Electron., 2017, Vol. 10 Iss. 13, pp. 1705-1713 1711
© The Institution of Engineering and Technology 2017
Fig. 7  Dynamics of the system based on the conventional droop control
(a) Output active power of the DGs, (b) Active power regulation when the load increases, (c) Output reactive power of the DGs, (d) Load power, (e) Changes of the bus voltage
ΔV b(ΔV b = V b − V b∗), (f) Changes of the frequency Δ f (Δ f = f − f ∗)

regulation is improved, especially in the grid-connected mode, the Foundation of China (grant no. 51377142) and in part by the
DGs can output the specified reactive power with the modified Zhejiang Provincial Natural Science Foundation of China (grant
voltage droop, which benefits the economic dispatch of the no. LY16E070002).
microgrid. However, the accuracy of reactive power regulation is
mainly dependent on the stability of the grid voltage. If the grid 7 References
voltage changes out of the allowable variation range, the reactive
power cannot be regulated accurately in the grid-connected mode [1] Rajagopalan, J., Xing, K., Guo, Y.: ‘Modeling and dynamic analysis of
paralleled DC/DC converters with master-slave current sharing control’. IEEE
anymore. In addition, in the paper, only the stability of the single- Proc. APEC, San Jose, USA, March 1996, pp. 678–684
machine-infinite-bus system is analysed. However, the detailed [2] Mazumder, S.K., Tahir, M., Acharya, K.: ‘Master–slave current-sharing
stability analysis for the microgrid system consisting of multiple control of a parallel DC–DC converter system over an RF communication
droop-based DGs is still not solved well, which is a very interface’, IEEE Trans. Ind. Electron., 2008, 55, (1), pp. 59–66
[3] Zhang, X., Liu, J., Liu, T., et al.: ‘A novel power distribution strategy for
challenging problem and is also our future work. parallel inverters in islanded mode microgrid’. IEEE Proc. APEC, Palm
Springs, USA, February 2010, pp. 2116–2120
[4] De Brabandere, K., Bolsens, B., Van den Keybus, J., et al.: ‘A voltage and
6 Acknowledgments frequency droop control method for parallel inverters’, IEEE Trans. Power
This work was supported in part by the National Key R&D Electron., 2007, 22, (4), pp. 1107–1115
[5] Jin, H., Unger, T., Mauch, K.: ‘Parallel operation of single phase inverter
Program of China (grant no. 2017YFB0903303), in part by the modules with no control interconnections’. IEEE Proc. APEC, Atlanta, USA,
Zhejiang Provincial Key Research and Development Program February 1997, pp. 94–100
(grant no. 2017C01039), in part by the National Natural Science

1712 IET Power Electron., 2017, Vol. 10 Iss. 13, pp. 1705-1713
© The Institution of Engineering and Technology 2017
[6] Vandoorn, T.L., Renders, B., Degroote, L., et al.: ‘Active load control in [19] Zhang, C., Guerrero, J.M., Vasquez, J.C., et al.: ‘Control architecture for
islanded microgrids based on the grid voltage’, IEEE Trans. Smart Grid, parallel-connected inverters in uninterruptible power systems’, IEEE Trans.
2011, 2, (1), pp. 139–151 Power Electron., 2016, 31, (7), pp. 5176–5188
[7] Vandoorn, T.L., Meersman, B., Degroote, L., et al.: ‘A control strategy for [20] Li, Z., Zang, C., Zeng, P., et al.: ‘Analysis of multi-agent-based adaptive
islanded microgrids with dc-link voltage control’, IEEE Trans. Power Deliv., droop-controlled AC microgrids with PSCAD: modeling and simulation’, J.
2011, 26, (2), pp. 703–713 Power Electron., 2015, 15, (2), pp. 455–468
[8] Sun, Y., Hou, X., Yang, J., et al.: ‘New perspectives on droop control in AC [21] Li, Z., Zang, C., Zeng, P., et al.: ‘Agent-based distributed and economic
MicroGrid’, IEEE Trans. Ind. Electron., 2017, 64, (7), pp. 5741–5745 automatic generation control for droop-controlled AC microgrids’, IET Gener.
[9] Guerrero, J.M., Vicuña, D., García, L., et al.: ‘A wireless controller to Transm. Distrib., 2016, 10, (14), pp. 3622–3630
enhance dynamic performance of parallel inverters in distributed generation [22] Savaghebi, M., Jalilian, A., Vasquez, J.C., et al.: ‘Secondary control scheme
systems’, IEEE Trans. Power Electron., 2004, 19, (5), pp. 1205–1213 for voltage unbalance compensation in an islanded droop-controlled
[10] Goya, T., Omine, E., Kinjyo, Y., et al.: ‘Frequency control in isolated island microgrid’, IEEE Trans. Smart Grid, 2012, 3, (2), pp. 797–807
by using parallel operated battery systems applying H∞ control theory based [23] Bidram, A., Davoudi, A., Lewis, F.L., et al.: ‘Secondary control of microgrids
on droop characteristics’, IET Renew. Power Gener., 2011, 5, (2), pp. 160–166 based on distributed cooperative control of multi-agent systems’, IET Gener.
[11] Zhong, Q.C.: ‘Robust droop controller for accurate proportional load sharing Transm. Distrib., 2013, 7, (8), pp. 822–831
among inverters operated in parallel’, IEEE Trans. Ind. Electron., 2013, 60, [24] Bidram, A., Davoudi, A., Lewis, F.L., et al.: ‘Distributed cooperative
(4), pp. 1281–1290 secondary control of microgrids using feedback linearization’, IEEE Trans.
[12] Li, C., Chaudhary, S.K., Savaghebi, M., et al.: ‘Power flow analysis for low- Power Syst., 2013, 28, (3), pp. 3462–3470
voltage AC and DC microgrids considering droop control and virtual [25] Shafiee, Q., Guerrero, J.M., Vasquez, J.C.: ‘Distributed secondary control for
impedance’, IEEE Trans. Smart Grid, IEEE Early Access Articles, doi: islanded microgrids—A novel approach’, IEEE Trans. Power Electron., 2014,
10.1109/TSG.2016.2537402 29, (2), pp. 1018–1031
[13] He, J., Li, Y.W.: ‘An enhanced microgrid load demand sharing strategy’, [26] Simpson-Porco, J.W., Dörfler, F., Bullo, F.: ‘Synchronization and power
IEEE Trans. Power Electron., 2012, 27, (9), pp. 3984–3995 sharing for droop-controlled inverters in islanded microgrids’, Automatica,
[14] Majumder, R., Ghosh, A., Ledwich, G., et al.: ‘Angle droop versus frequency 2013, 49, (9), pp. 2603–2611
droop in a voltage source converter based autonomous microgrid’. IEEE Proc. [27] Guerrero, J.M., Vasquez, J.C., Matas, J., et al.: ‘Hierarchical control of droop-
PES, Calgary, USA, July 2009, pp. 1–8 controlled AC and DC microgrids—A general approach toward
[15] Majumder, R., Chaudhuri, B., Ghosh, A., et al.: ‘Improvement of stability and standardization’, IEEE Trans. Ind. Electron., 2011, 58, (1), pp. 158–172
load sharing in an autonomous microgrid using supplementary droop control [28] Guerrero, J.M., Chandorkar, M., Lee, T.L., et al.: ‘Advanced control
loop’, IEEE Trans. Power Syst., 2010, 25, (2), pp. 796–808 architectures for intelligent microgrids, part I: decentralized and hierarchical
[16] Majumder, R., Ghosh, A., Ledwich, G., et al.: ‘Load sharing and power control’, IEEE Trans. Ind. Electron., 2013, 60, (4), pp. 1254–1262
quality enhanced operation of a distributed microgrid’, IET Renew. Power [29] Loh, P.C., Newman, M.J., Zmood, D.N., et al.: ‘A comparative analysis of
Gener., 2009, 3, (2), pp. 109–119 multiloop voltage regulation strategies for single and three-phase UPS
[17] Lee, C.T., Jiang, R.P., Cheng, P.T.: ‘A grid synchronization method for droop- systems’, IEEE Trans. Power Electron., 2003, 18, (5), pp. 1176–1185
controlled distributed energy resource converters’, IEEE Trans. Ind. Appl., [30] Blasko, V., Kaura, V.: ‘A novel control to actively damp resonance in input
2013, 49, (2), pp. 954–962 LC filter of a three-phase voltage source converter’, IEEE Trans. Ind. Appl.,
[18] Li, Y., Vilathgamuwa, D.M., Loh, P.C.: ‘Design, analysis, and real-time 1997, 33, (2), pp. 542–550
testing of a controller for multibus microgrid system’, IEEE Trans. Power
Electron., 2004, 19, (5), pp. 1195–1204

IET Power Electron., 2017, Vol. 10 Iss. 13, pp. 1705-1713 1713
© The Institution of Engineering and Technology 2017

View publication stats

You might also like