GENERAL NOTES:

01. ALL ELECTRICAL WORKS HEREIN BE DONE IN ACCORDANCE WITH APPLICABLE PROVISION OF LATEST
EDITION OF THE PHILIPPINES ELECTRICAL CODE REQUIREMENTS OF THE LOCAL AUTHORITIES ENFORCING
LOAD SCHEDULE THE CODE AND REQUIREMENTS OF THE LOCAL COMPANY CONCERNED.

02. ALL WIRES SHOULD BE COPPER TYPE T.W. IN INTERMEDIATE METALLIC CONDUIT (IMC) OR UNLESS
OTHERWISE SPECIFIED.
CKT. NO. DESCRIPTION T. LOAD VOLT AMPERES PROPTECTION SIZES OF WIRE AND CONDUIT

1 9 LIGHTING OUTLET 660 220 3 20 A 2#12 THHN WIRE IN 1/2" Ø PIPE


03. ALL JUNCTION, UTILITY, SQUARE AND PULL BOXES SHALL BE GA # 16 OR APPROVED EQUIVALENT AND
2 8 LIGHTING OUTLET 620 2.82
PAINTED WITH ONE COAT PRIMER INSTALLATION.
3 9 LIGHTING OUTLET 660 3
4 640 2.91 04. ALL MATERIALS TO BE USED SHOULD BE BRAND NEW AND OF APPROVED TYPE FOR CONSTRUCTION.
10 LIGHTING OUTLET
5 9 LIGHTING OUTLET 540 2.45
05. POWER SUPPLY SHALL BE 230V, 1Ø, 60HZ, 2 WIRES.
6 11 LIGHTING OUTLET 620 2.82 LEGEND & SYMBOLS:
7 10 LIGHTING OUTLET 1000 4.55
06. ALL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF QUALIFIED AND A DULY
8 10 LIGHTING OUTLET 520 2.36 LICENCED ELECTRICAL ENGINEER OR MASTER ELECTRICIAN.
9 11 LIGHTING OUTLET 620 2.82
LIGHTING OUTLET
10 9 LIGHTING OUTLET 480 2.18 07. MINIMUM SIZE OF CONDUCTORS SHALL BE # 12 T.W. IN 13MMØ TRADE SIZE.
11 11 CONVENIENCE OUTLET 1980 9 PIN LIGHT
12 13 CONVENIENCE OUTLET 2340 10.64
08. MOUNTING HEIGHT FROM FINISH FLOOR LINE TO THE CENTER OF DEVICES SHALL BE AS FOLLOWS:
13 800 3.64 30 A 2#10 THHN WIRE IN 1/2" Ø PIPE
DIM LIGHT
REFRIGERATOR
a. CONVENIENT OUTLET 0.40 mts. above fin. line
14 WATER HEATER 1500 6.82 b. SWITCHES 1.30 mts. "
CONVENIENCE OUTLET c. FUSE BOX 1.80 mts. "
15 WATER HEATER 1500 6.82
d. SAFETY SWITCHES 1.80 mts. "
16 WATER HEATER 1500 6.82 REFRIGERATOR e. KILOWATT HOUR METER 1.80 mts. "
REF
17 WATER HEATER 1500 6.82
18 ACU 2640 12 AIRCONDITION UNIT 09. all vertical and horizontal conduit shall be concealed or embedded on concrete walls and floors.
ACU
19 ACU 2640 12
20 2640 12 10. all conduit shall be properly reamed prior to installation to avoid damaged to the skin of wire.
ACU S SINGLE POLE SWITCH
21 ACU 2640 12
22 ACU 2640 12 S2 TWO GANG SWITCH
23 ACU 2640 12
6.82
S3 THREE GANG SWITCH
24 SPARE 1500
TOTAL 34,820
POWER SERVICE ENTRANCE CAP

LIGHTING LAYOUT

COMPUTATION:
POWER LAYOUT

IT = 34820 WATTS X 80%


= 126.618 AMPS.
1 CIRCUIT HOMERUN D:\projects\ervin\metrogate\revision 4\vmap.jpg
220 VOLTS
M KILOWATT-HOUR METER
USE 1-150 AT MAIN 2PCB, 240 V.
PANEL BOARD
USE 2 # 1/0 THHN WIRE IN 1 ½" Ø RSC

VICINITY MAP
ARCHITECT / ENGINEER: PROJECT TITLE: OWNER: REVISIONS: SHEET CONTENT: SHEET NO.

PROPOSED LOAD SCHEDULE


COMPUTATION
TWO STOREY RESIDENTIAL BUILDING LEGEND
E-2
GENERAL NOTES
PRC No.: PTR No.: EMMANUEL L. BELINARIO
VICINITY MAP

TIN No.: DATE: LOCATION: LOT 12, BLOCK 420, BRGY. CAPAYA, METRO GATE SUBD., ANGELES CITY