You are on page 1of 6

Voltage Regulation Performance of Smart Inverters:

Power Factor versus Volt-VAR Control


Kaveh Rahimi, Ahmad Tbaileh, Robert Broadwater Jeremy Woyak, Murat Dilek
ECE Department, Virginia Tech Electrical Distribution Design (EDD)
Blacksburg, VA, USA Blacksburg, VA, USA

Abstract— Due to the insignificant share of inverter-based instability [3]-[10], the need to employ the voltage/frequency
Renewable Energy Resources (RER) as well as the uncertainty regulating capability of RERs is of interest.
concerning their integration impacts, the capability of RERs to
regulate voltage or frequency has not been widely used. However, Germany and France were the first countries, which updated
inverter-based voltage/frequency regulation is of interest due to their grid codes to facilitate the integration of Distributed
the fast growth of distributed RERs, especially solar Photovoltaic Energy Resources (DER) [11]. At a regional level, the state of
(PV) resources. The IEEE 1547a standard relaxed some of the California, which possesses the highest penetration of PV
restrictions on utilization of Distributed Energy Resources (DER) resources in the continental U.S., has updated its
in voltage/frequency regulation. Smart inverters may employ interconnection requirements, allowing utilization of RERs in
different control strategies, such as Fixed Power Factor, Volt- reactive power control and providing voltage and frequency
VAR, Volt-Watt, and Frequency-Watt. In this study, a ride-through responses [4]. Moreover, in 2014, the first
comparison between fixed power factor and Volt-VAR control amendment of the IEEE 1547 standard allowed the
strategies is performed in terms of voltage regulation capability. participation of DERs in voltage regulation [12], stating
One hour of quasi-steady-state simulation with one-second time “Coordination with and approval of the area EPS and DR
steps is performed, where fast and frequent irradiance variations operators, shall be required for the DR to actively participate to
are occurring. Parametric studies involving controller settings regulate the voltage by changes of real and reactive power.”
are used to compare voltage regulation performance. The IEEE
13-bus test feeder, modified by adding two PV generators, is used Currently, advanced or smart inverters are capable of
as the case study. Simulation results show that the Volt-VAR implementing different control strategies, including Fixed
control out performs the fixed power factor control when it comes Power Factor (FPF), Volt-VAR (VV), Volt-Watt, and
to voltage regulation. Frequency-Watt [13]. However, due to enforcement of the
IEEE 1547-2003 requirement, unity power factor is the most
Index Terms—Photovoltaic Systems, Reactive Power support, common control strategy for PV systems.
Smart Inverter, Voltage Regulation
Allowing DERs to participate in voltage/frequency
INTRODUCTION regulation and considering issues rising from high penetration
of inverter-based RERs, investigating different controls of
Recent technological advances have resulted in decreased smart inverters has become a necessity. In [14] the FPF control
costs of Renewable Energy Resources (RER). In addition, the is utilized for voltage regulation, and voltage changes are
political will to decrease carbon emissions and energy computed for different power factors. The authors in [15]
dependence, and government incentives, are accelerating the pointed out that applying the FPF approach could overheat
growth of RERs. Over the past decade Solar Photovoltaic (PV) inverters by drawing excessive reactive power. In [16] the
resources have been growing exponentially. In fact, they had capability of VV controllers is utilized to decrease voltage
the greatest global growth rate in 2015 among RERs [1], and variations for a real distribution feeder. The authors in [17]
they are expected to continue their rapid growth in the employed a VV control strategy to minimize flicker and voltage
foreseeable future. fluctuations. A comparison between VV and FPF controllers in
A decade ago, participation of RERs in voltage/frequency terms of reactive power support is performed in [18].
regulation was not permitted. The first version of the IEEE 1547 In this study, one hour worth of one second, irradiance
standard, IEEE Standard for Interconnecting Distributed measurement data is employed to simulate large irradiance
Resources with Electric Power Systems [2], issued in 2003, did fluctuations in terms of rate of change and percentage change.
not authorize the participation of Distributed Resources (DR) in In contrast with some studies, which evaluate the performance
voltage regulation, stating “The DR shall not actively regulate of smart inverters only after one disturbance, either load or
the voltage at the Point of Common Coupling.” However, due irradiance change [19]-[20], a Quasi-Steady-State (QSS)
to the steady growth of RERs, and the subsequent issues they simulation employing one second time steps for one hour is
have introduced such as under/over voltage issues, bi- carried out. Using the QSS simulation, a comparison between
directional power flows, high-frequency harmonics, and grid FPF and VV controls is performed. Parametric studies
involving the FPF and VV control parameters are conducted. used, and as long as the voltage falls inside of the dead-band,
To quantify the performance of the different controls, a voltage no reactive power injection/absorption occurs. A typical VV
regulation cost function is used. The IEEE 13-bus test feeder, control characteristic is illustrated in Fig. 2 [13]. The voltage
which is an unbalanced system, is used as the case study, and range between V2 and V3 shown in Fig. 2 represents the dead-
two PV systems are added to the 13-bus feeder model. The main band.
objective of this study to evaluate the performance of VV and Considering Fig. 2, when the voltage is less than V1, the
FPF controllers in terms of voltage regulation under severe maximum reactive power is injected. When the voltage is
irradiance fluctuations. The paper is organized as follows. between V2 and V1, reactive power is injected based on the
Section II discusses FPF and VV control strategies. Section III
slope S1 shown in Fig. 2. When voltage falls between V3 and
is devoted to the case study and simulation results, and section
V4, reactive power is absorbed based on the slope S2
IV provides conclusions.
illustrated in Fig. 2. Finally, if the voltage level is greater than
FIXED POWER FACTOR AND VOLT-VAR CONTROLLERS V4, the maximum reactive power is absorbed.
In some cases, it may be desired to employ hysteresis in the
In this section, logic and characteristics of FPF and VV VV control. With hysteresis, different locations can be defined
controllers are briefly discussed. for the points P1-P4 of Fig.2. Thus, the path followed by the
A. Fixed Power Factor (FPF) Control control when voltage is rising is different from the path
followed by the control when voltage is falling. VV control
With FPF control, the power factor at the location of the
with hysteresis is illustrated in Fig. 3 [13].
inverter is kept constant. The power factor range is between -1
and 1. Both -1 and +1 lead to the same result, generating no
reactive power. A positive power factor, or leading power
factor, indicates generating reactive power. A negative power
factor, or lagging power factor, indicates absorbing reactive
power. The regulation of the power factor is usually performed
by producing/curtailing reactive power. However, it can also be
performed by regulation of real power. Different power factor
quadrants and the states of real and reactive power
injection/absorption are illustrated in Fig. 1 [13].

Figure 2. VV control strategy characteristics [13]

Figure 1. Four operating quadrants in FPF control strategy [13]

B. Vol-VAR (VV) Control Figure 3. VV control strategy with a hysteresis incorporated [13]
The VV control strategy is utilized to control the injection
or absorption of reactive power based on the voltage level at CASE STUDY AND SIMULATION RESULTS
the inverter’s terminals. The principle underlying VV control
A. Case study
is to inject reactive power when the voltage falls below a
specified level, and to absorb reactive power when the voltage The IEEE 13-bus test feeder is modified to have PV
exceeds a specified level. A voltage dead-band may also be generation and is used as the case study here. It is an
unbalanced, 3-phase model, where two 3-phase PV generators B. Voltage regulation performance evaluation
are added at busses 671 and 634, with capacities of 1300 and To quantify voltage regulation performance of the FPF and
500 kVA, respectively. The feeder and PV generator model are VV controllers, a cost function referred to as the Voltage
illustrated in Fig 4. In evaluating the voltage regulation Regulation Index (VRI) is employed. The VRI is defined as
performance of the FPF and VV controls, one second step size
simulations are performed covering one hour of operation. The ∑ | 1| (1)
simulations occur at noon when PV generation is maximum.
The solar irradiance profile shown in Fig. 5 is used to simulate , where T is 3600 and is the per unit voltage. The VRI
solar irradiance fluctuations. In some cases, irradiance drops is the sum of the absolute values of voltage deviations from the
from 100% to 20% in a matter of seconds. Note that the per unit voltage over the simulation time, which is 3600
irradiance profile used is based on real solar irradiance seconds. A smaller VRI indicates a better voltage regulation
measurements. It is assumed that time constants for smart performance. The base voltage level is considered to be 120 V.
inverter dynamics are in the order of a few cycles, and thus
inverter dynamics are neglected. C. Simulation Results
Different power factors and VV slopes are considered in the
simulations, and the VRI is computed for each simulation. Dead
bands were not used in the VV control, allowing the VV control
to rapidly react to voltage deviations, which resulted in better
voltage regulation performance. The simulation results are
summarized in Tables I and II, which for the parametric studies
present the control strategies, parameter values, and the VRI
values along with the sum of the 3-phase reactive power used
in the control, regardless of injection or absorption, for busses
671 and 634. The lowest value of the VRI index achieved at
each bus is highlighted in Table I. The time varying voltages at
bus 671, which occurred for employing FPF control strategy
with leading power factors of 1, 0.95 and 0.9, are illustrated in
Fig. 6. Similarly, the voltages at bus 671 when various slopes
are used with the VV control are presented in Fig. 7. Reactive
power injections or absorptions at bus 671 are illustrated in
figures 8 and 9 when FPF and VV control strategies are
employed respectively. Note that the simulations were
performed using Distributed Engineering Workstation [21].
TABLE I. VOLTAGE REGULATION INDICES COMPUTED FOR VV AND FPF
CONTROLLERS

VR Index
Control
Bus Phase A Phase B Phase C Total Characteristics
Figure 4. IEEE 13-bus feeder with two added PV systems Strategy
Fixed Power
671 7.38 123.77 79.05 210.20 1.0 (Leading)
Factor
Fixed Power
671 22.68 155.77 27.71 206.16 0.95 (Leading)
Factor
Fixed Power
671 22.49 156.24 19.06 197.79 0.9 (Leading)
Factor
671 4.48 114.08 73.31 191.88 Volt-VAR P1=0.7, P2=1.3
671 3.69 109.92 70.80 184.42 Volt-VAR P1=0.8, P2=1.2
671 3.88 99.38 64.36 167.62 Volt-VAR P1=0.9, P2=1.1
VR Index
Control
Bus Phase A Phase B Phase C Total Characteristics
Strategy
Fixed Power
634 42.92 89.23 40.20 172.35 1.0 (Leading)
Factor
Fixed Power
634 72.88 127.55 91.51 291.93 0.95 (Leading)
Factor
Fixed Power
634 74.46 129.11 100.11 303.68 0.9 (Leading)
Factor
634 42.89 82.00 40.71 165.60 Volt-VAR P1=0.7, P2=1.3
634 42.89 78.92 41.03 162.84 Volt-VAR P1=0.8, P2=1.2
634 42.80 71.15 41.94 155.88 Volt-VAR P1=0.9, P2=1.1
Figure 5. Irradiance fluctuations between 12:00 to 13:00 PM
TABLE II. SUM OF 3600 ABSOLUTE REACTIVE POWER VALUES DURING QSS SIMULATIONS

Sum of Absolute Reactive Sum of Absolute Reactive


Power Values (kVAR) Power Values (kVAR)
Control Control
Bus Phase A Phase B Phase C 3-Phase Characteristics Bus Phase A Phase B Phase C 3-Phase Characteristics
Strategy Strategy
671 0 0 0 0 FPF 1.0 (Leading) 634 0 0 0 0 FPF 1.0 (Leading)
671 318730 377821 444495 1141046 FPF 0.95 (Leading) 634 129511 149984 172084 451579 FPF 0.95 (Leading)
671 338549 402776 506270 1247595 FPF 0.9 (Leading) 634 137424 160518 198902 496845 FPF 0.9 (Leading)
671 4957 52973 44969 102898 VV P1=0.7, P2=1.3 634 5844 14324 8226 28395 VV P1=0.7, P2=1.3
671 6388 75713 64725 146826 VV P1=0.8, P2=1.2 634 8729 20439 12442 41609 VV P1=0.8, P2=1.2
671 10256 133435 115863 259553 VV P1=0.9, P2=1.1 634 17407 35901 25775 79083 VV P1=0.9, P2=1.1

Figure 6. 3-phase voltages at bus 671 with FPF control

Figure 7. 3-phase voltages at bus 671 with VV control


Figure 8. Reactive power injections/absorptions of FPF controller at bus 671 during one-hour QSS simulation. Negative values indicate reactive power
injection and positive values indicate reactive power absorption.

Figure 9. Reactive power injections/absorptions of VV controller at bus 671 during one-hour QSS simulation. Negative values indicate reactive power
injection and positive values indicate reactive power absorption.
[6] K. Rahimi, S. Omran, M. Dilek, R. Broadwater, “Quasi-steady-state
D. Discussions Computation of Voltage Flicker with Cloud Motion Simulator” 2017
Based on the results presented in Table I, the VV control IEEE Power and Energy Conference at Illinois (PECI), Urbana, IL, 2017,
provides better voltage regulation than the FPF control. pp. 1-6.
Increasing the S1 and S2 slopes of the VV curve of Fig. 2 results [7] A. Parchure; S. J. Tyler; K. Rahimi; R. P. Broadwater; M. Dilek; M. A.
in reducing the VRI. With the FPF controllers, decreasing the Peskin, "Investigating PV Generation Induced Voltage Volatility for
Customers Sharing a Distribution Service Transformer," in IEEE
power factor from 1.0 to 0.9 results in improving the voltage Transactions on Industry Applications , vol.PP, no.99, pp.1-1
regulation for bus 671. However, it had a reverse effect on the [8] F. Harirchi, M. G. Simões, M. Babakmehr, A. AlDurra, S. M. Muyeen
VRI of bus 634. This is due to the FPF control, which regardless and A. Bubshait, "Multi-functional double mode inverter for power
of voltage deviation either injects or absorbs reactive power, quality enhancement in smart-grid applications," 2016 IEEE Industry
and in some cases, it can result in unwanted voltages deviations. Applications Society Annual Meeting, Portland, OR, 2016, pp. 1-8
[9] Alireza Majzoobi, Amin Khodaei, Application of microgrids in
For the QSS simulations, the VV controllers inject/absorb providing ancillary services to the utility grid, Energy, Volume 123, 15
significantly less reactive power than the FPF control. Based on March 2017, Pages 555-563, ISSN 0360-5442,
Table II, the inverter at bus 671 injected/absorbed a total of http://doi.org/10.1016/j.energy.2017.01.113.
259553 kVAR with VV control. However, the same inverter [10] A. Tbaileh, C. Mishra, K. Thomas, “PV Impacts on Dynamic Voltage
injected/absorbed a total of 1247595 kVAR with a 0.9 leading Stability,”2017 IEEE SoutheastCon, Charlotte, NC, 2017, pp 1-5.
FPF control, which is approximately six times more reactive [11] E. Troester, “New German grid codes for connecting PV systems to the
medium voltage power grid,” Proceedings of the 2nd International
power than the VV control. The same trend was observed for
Workshop Concentrating Photovoltaic Power Plants: Opt. Design, Prod.,
bus 634 in terms of total reactive power injection/absorption. Grid Connection, 2009.
[12] IEEE Standard for Interconnecting Distributed Resources with Electric
CONCLUSION Power Systems - Amendment 1," in IEEE Std 1547a-2014 (Amendment
In the work here, voltage regulation performance of Fixed to IEEE Std 1547-2003) , vol., no., pp.1-16, May 21 2014
Power Factor (FPF) and Volt-VAR (VV) control strategies is [13] Common Functions for Smart Inverters, Version 3. EPRI, Palo Alto, CA:
2013. 3002002233.
investigated using two Photovoltaic (PV) systems added to the
[14] K. Kouno, M. Hirose, T. Nagase, and W. Hashimoto, W.; Hojo, M.;
IEEE 13-bus test feeder. A severe, one-hour irradiance profile, Ohnishi, T., "Effectiveness of constant power factor control of mega-
derived from real-world one-second measurement data, is solar system for voltage regulation with long distribution line," 2013
employed for the performance evaluation. A cost function, IEEE 10th International Conference on Power Electronics and Drive
referred to as the Voltage Regulation Index, along with total Systems (PEDS), vol., no., pp.317,322, 22-25 April 2013.
inverter reactive power injection/absorption, is computed for [15] K. Kouno, M. Hirose, T. Nagase, and W. Hashimoto, W.; Hojo, M.;
quasi-steady-state, one-second time step simulations that last Ohnishi, T., "Effectiveness of constant power factor control of mega-
for one hour. solar system for voltage regulation with long distribution line," 2013
IEEE 10th International Conference on Power Electronics and Drive
Simulation results show that the VV control provides more Systems (PEDS), vol., no., pp.317,322, 22-25 April 2013.
effective voltage regulation than FPF control. Furthermore, it is [16] J.W. Smith, W. Sunderman, R. Dugan, and B. Seal, "Smart inverter
observed that as much as six times less reactive power volt/var control functions for high penetration of PV on distribution
systems," 2011 IEEE/PES Power Systems Conference and Exposition
injection/absorption occurs when VV control is used. (PSCE), vol., no., pp.1,6, 20-23 March 2011.
Future work will target the evaluation of Volt-Watt control [17] H. Alatrash, R.A. Amarin, and C. Lam, "Enabling large-Scale PV
performance in voltage regulation, as well as an investigation integration into the Grid," 2012 IEEE Green Technologies Conference,
vol., no., pp.1,6, 19-20 April 2012.
of optimal control strategies and settings.
[18] A. Agrawal, K. Rahimi, R. P. Broadwater and J. Bank, "Performance of
PV generation feedback controllers: Power factor versus Volt-VAR
Refrences control strategies," 2015 North American Power Symposium (NAPS),
[1] REN21. 2016. Renewables 2016 Global Status Report (Paris: REN21 Charlotte, NC, 2015, pp. 1-6.
Secretariat). ISBN 978-3-9818107-0-7 [19] M. Davoudi, V. Cecchi and J. R. Agüero, "Effects of stiffness factor on
[2] IEEE Standard for Interconnecting Distributed Resources with Electric bus voltage variations in the presence of intermittent distributed
Power Systems," in IEEE Std 1547-2003 , vol., no., pp.1-28, July 28 generation," 2015 North American Power Symposium (NAPS),
2003 Charlotte, NC, 2015, pp. 1-6.
[3] California Energy Commission, European Renewable Distributed [20] M. Chamana, I. Mazhari, B. Parkhideh and B. H. Chowdhury, "Multi-
Generation Infrastructure Study: Lessons Learned from Electricity mode operation of different PV/BESS architectures in a microgrid: Grid-
Markets in Germany and Spain - Consultant Report, CEC400-2011- 011, tied and island mode," 2014 IEEE PES T&D Conference and Exposition,
December, 2011. Chicago, IL, USA, 2014, pp. 1-5.
[4] California Public Utilities Commission (CPUC), “Advanced Inverter [21] M. Dilek, F. de Leon, R. Broadwater, and S. Lee, “A Robust Multiphase
Technologies Report, Grid Planning, Reliability, and Energy Division”, Power Flow for General Distribution Networks”, IEEE Trans. Power
January, 2013. Systems, vol. 25, pp. 760-768, May 2010.
[5] K. Rahimi, S. Mohajeryami and A. Majzoobi, "Effects of photovoltaic
systems on power quality," 2016 North American Power Symposium
(NAPS), Denver, CO, 2016, pp. 1-6.

You might also like