Formwork Support Reactions

Wind Load = 2 kN/m2

y3 2.485

Wind force = 8.87

y2 3.9

Wind force = 4.80

y1 0.45

Ry1 Ry2
α1 = 14.04 degree 1.8
α2 = 67.52 degree x1
1.8
x2

R1 = 4.95 kN R2= 23.20 kN


Lateral Shear = Rx1= 4.80 kN Rx2= 8.87 kN TOTAL
Vertical Shear = Ry1= 1.16 kN Ry2= 21.44 kN TOTAL
Max BM = 79.92 kNm

Capacity= 2 x 40 80 kNm
(Provided 2 soldiers)
Hence OK
13.67 kN
22.60 kN
Vertical Shear Check carried by member
Cross Sectional Area = 19.64 cm2
1964 mm2
Shear Capacity = 0.6 x 370 x 1964 436.008 kN

Lateral Shear Check carried by M14 bolts of Grade 4.6

Area of M14 = 153.94 mm2


Allowable Shear Stress = 160 N/mm2 BS5950
Lateral Shear 41.01 kN
Shear Capacity for Two M14 bolts 49.26 kN
OK