Zaštitni Releji
Zaštitni Releji
SEC. - PAGE
Modular voltage monitoring relays
For three-phase systems, without neutral ........................................................................................................................... 17 - 4
For three-phase systems, with or without neutral ............................................................................................................... 17 - 6
For single-phase systems .................................................................................................................................................. 17 - 8
Modular current monitoring relays
For single-phase systems .......................................................................................................................................................... 17 - 8
Modular pump protection relay .......................................................................................... 17 - 10
Modular phase shift monitoring relay .................................................................................. 17 - 11
Modular frequency monitoring relay .................................................................................... 17 - 12
Modular voltage and frequency monitoring relay .................................................................... 17 - 13
Dimensions ................................................................................................................. 17 - 14
Wiring diagrams ........................................................................................................... 17 - 15
Technical characteristics ................................................................................................. 17 - 24
C ONTROL
AND
A UTOMATION
Protection relays
Overview
PMV55
Modular version l(2U)
Minimum AC voltage l
Maximum AC voltage l
Page 17-8
17-2
Protection relays
Overview
PMA50
Modular version l(3U)
Minimum cosj for dry running
l
pump protection
Maximum AC current l
Phase loss l
Incorrect phase sequence l
Page 17-10
17
PMA60
Modular version l(3U)
Minimum cosj l
Maximum cosj l
Page 17-11
PMF20 PMVF10
Modular version l(2U) Modular version l(3U)
Minimum and maximum frequency l Minimum and maximum voltage l
Minimum frequency only l Minimum and maximum frequency l
Maximum frequency only l ROCOF l
Page 17-12 Page 17-13
17-3
Protection relays
For three-phase systems, without neutral
Operational diagram
See page 17-15.
Operational diagram
See page 17-15.
Operational diagram
See page 17-15.
Voltage monitoring relay Order code Rated voltage Qty Wt General characteristics
for three-phase systems to control Ue per – Voltage monitoring relay, self powered, for minimum
(phase to phase) pkg and maximum voltage, phase loss, neutral loss and
with or without neutral [V] 50/60Hz n° [kg] incorrect phase sequence
– 4 configurable rated voltage (Ue):
Three-phase system, with or without neutral. • PMV50N A240: 208-220-230-240VAC (phase-phase)
Minimum and maximum AC voltage. Delayed trip. 120-127-132-138VAC (phase-neutral)
Phase loss, neutral loss and incorrect phase sequence. • PMV50N A440: 380-400-415-440VAC (phase-phase)
Instantaneous trip. 220-230-240-254VAC (phase-neutral)
PMV50N A240 208-240VAC 1 0.150 • PMV50N A600: 480-525-575-600VAC (phase-phase)
PMV50N A440 380-440VAC 1 0.150 277-303-332-347VAC (phase-neutral)
– Excellent tripping accuracy
PMV50N A600 480-600VAC 1 0.150 – TRMS measurements (True Root Mean Square)
– Phase loss detection when one of the voltages is
<70% rated voltage
– Phase or neutral loss tripping time: 60ms
– 2 relay outputs, each with 1 changeover contact (SPDT)
17 PMV50N...
– Modular DIN 43880 housing, 3-module
– IEC protection degree: IP40 on front (only when
placed in IP40 enclosure or control board); IP20 at
terminals.
ADJUSTMENTS
“V max” Maximum voltage tripping threshold
105-115% Ue
“V min” Minimum voltage tripping threshold
80-95% Ue
“Delay” for each Tripping time 0.1-20s
“Reset Delay” Resetting time 0.1-20s.
Operational diagram
See page 17-16.
Operational diagram
See page 17-16.
Operational diagram
See page 17-16.
Operational diagram
See page 17-17.
Operational diagram
See page 17-20.
Operational diagram
See page 17-21.
17
Phase shift monitoring Order code Rated Auxiliary Qty Wt General characteristics
relay current supply per – Minimum and maximum phase shift monitoring relay,
Ie voltage pkg AC auxiliary power supply
[A] [V] n° [kg] – Direct connection up to 16A max, or by current
transformer (CT)
Single and three-phase systems. – Excellent tripping accuracy
Minimum and maximum cosj control. Delayed trip. – Voltage control range 80-660VAC
AC auxiliary power supply. – Current control range 0.1-16A
Automatic or manual reset. – Automatic or manual resetting (manual resetting by
PMA60 A240 16A 220-240VAC 1 0.254 power removal)
PMA60 A415 380-415VAC 1 0.254 – 2 relay outputs (Min and Max), configurable, each with
1 changeover contact (SPDT)
PMA60 A480 440-480VAC 1 0.254 – Modular DIN 43880 housing, 3-module
– IEC protection degree: IP40 on front (only when
placed in iP40 enclosure or control board); IP20 at
terminals.
ADJUSTMENTS
PMA60... "Cosj min” Minimum cosj threshold
0.1-0.99 inductive
"Trip delay" Tripping time for minimum cosj
0.1-30s
"Cosj max” Maximum inductive cosj threshold
0.1-0.99
“Trip delay” Tripping time for maximum cosj
0.1-30s
“Inhibition time” Tripping delay at power up 1-60s
“Mode” • Single or three phase
• Relay outputs normally energised or
de-energised
• Tripping memory (Latch) On or Off.
Operational diagram
See page 17-22.
17
17
Voltage and frequency Order code Rated voltage Qty Wt General characteristics
monitoring relay di ordinazione to control Ue per The monitoring relay PMVF10 is designed and developed
pkg to satify requirements of the local power authority (ENEL
[V] n° [kg] guide edition 2.1 of 12/2010). The authority imposes that
the following automatic controls be done whenever an
Three-phase low-voltage system, with or without neutral. independent power source (e.g. wind turbine or
Compatible for single-phase low-voltage system. photovoltaic system, diesel generating set, etc.) is
Minimum and maximum AC voltage and frequency control connected in parallel with the electric grid (local low-
and ROCOF. voltage utility):
PMVF10 230VAC 50Hz 1 0.254 – Limits of minimum and maximum voltage values
400VAC 50Hz – Limits of minimum and maximum frequency values
– Limit of the Rate Of Change Of Frequency (ROCOF).
Status indication table When at least one of these limits are not respected,
Anomaly Green LED Red LED Red LED Red LED Relay output abnormal conditions need to be signalled using a
“ON” “Vmin” “Vmax” “Hz” 1 and 2 contact.
Typically, the contact is used to isolate the independent
None Constantly Switched Switched Switched Energised power source from the electric grid.
PMVF10 lighted off off off
Min/max Flashing Switched Switched Constantly De- The following are the relay protections available:
frequency off off lighted energised – Maximum voltage
or ROCOF – Minimum voltage
Voltage Flashing Constantly Switched Switched De- – Maximum frequency
<Vmin lighted off off energised – Minimum frequency
– ROCOF.
Voltage Flashing Switched Constantly Switched De-
TRMS measurements of this relay can obtain a correct
>Vmax off lighted off energised
operation even in presence of harmonic voltages.
It has fixed tripping thresholds for minimum and
maximum voltage while those for frequency can be
selected between two predefined values, using a rotary
switch. A reset delay is adjustable by potentiometer.
Operational characteristics
– Self powered by the system controlled
– Compatible for:
• Three-phase systems
(400VAC 50Hz, with or without neutral)
• Single-phase systems (230VAC 50 Hz)
– TRMS measurements (True Root Mean Square)
– 2 relay outputs, each with 1 changeover contact
(SPDT), rated 8A 250VAC (AC1)
– Modular DIN 43880 housing, 3-module
– IEC protection degree: IP40 on front (only when
placed in IP40 enclosure or control board); IP20 at
terminals.
PROTECTIONS
Maximum voltage protection:
– Fixed threshold ≥ 1.13Ue
– Fixed tripping time ≤ 0.1s.
Minimum voltage protection:
– Fixed threshold ≤ 0.825Ue
– Fixed tripping time ≤ 0.2s.
ADJUSMENTS
“Mode” Multifunction rotary switch:
• Control of phase or phase-to-phase
17
voltage values
• Frequency threshold ±0.3 or ±1Hz
• ROCOF (> 0.5Hz/s) On or Off
“Reset delay” Resetting time 0.1-30s.
STATUS INDICATIONS
– 1 green LED for system with limits (flashing when out
of limits)
– 3 red LEDs for minimum and maximum voltage,
minimum and maximum frequency and ROCOF.
Operational diaagram
See page 17-23.
Protection relays
PMV10... PMV... - PMF20 PMV...N - PMA40... -
PMA20... - PMA30... PMA50... - PMA60... - PMVF10
17.5 5 3
35.8 5 58.1 (2.29") 5 58 (2.28")
(0.69") (0.20") 58 (2.28") (1.41") (0.20") 43.8 (1.72") 53.5 (2.11") (0.20") 43.7 (1.72")
43.7 (1.72")
104.7 (4.12")
104.7 (4.12")
104.7 (4.12")
98.3 (3.87")
)
98.3 (3.87")
45 (1.77")
90 (3.54")
45 (1.77")
90 (3.54")
99 (3.90")
45 (1.77")
90 (3.54")
(
Ø4.2 Ø4.2 59.9 (2.36")
Ø4.2 59.9 (2.36") (0.16")
(0.16")
(0.16")
17
17-14
Protection relays
Wiring diagrams
Voltage monitoring relays for Phase loss and incorrect phase sequence (PMV10-PMV20-PMV30-PMV40-PMV50-PMV60- MV70)
3-phase systems without neutral Reset delay Reset delay Reset delay
PMV10 - PMV20 - PMV30 - PMV40 L1 L2
PMV50 - PMV60 - PMV70
L2 L1
L1 L3
L2 L3
L3
ON ON
L1 L2 L3
TRMS MAX MAX
MIN MIN
14 12 11
ASYMMETRY ASYMMETRY
11 14 11
14
12 12
Set up V MAX
Hysteresis
Hysteresis
Set up V MIN
L1 - L2 - L3
ON
V MAX
V MIN
14
11
12
Set point
asymmetry
Hysteresis
L1 - L2 - L3
On
ASYMMETRY
14
11
12
17
17-15
Protection relays
Wiring diagrams
Voltage monitoring relays for Phase loss and incorrect phase sequence (PMV50N - PMV60N - PMV70N)
3-phase systems c/w or w/o neutral Reset delay Reset delay Reset delay Reset delay
PMV50N - PMV60N - PMV70N
L1 L1
L2 L2
L1
L3 L3
L2
L3 N ❶ N
N
ON ON
TRMS
MAX MAX
14 14
V MIN relay 11 V MIN relay 11
12 12
24 24
V MAX relay 21 V MAX relay 21
22 22
Set up V MAX
Hysteresis
Ue
Hysteresis
Set up V MIN
Ue
ON
V MAX
V MIN
14
V MIN relay 11
12
V MAX relay 21 24
22
Max frequency
Set point asymmetry Hysteresis
Hysteresis
Hz
Hysteresis
Min frequency
Ue
ON Ue
ASYMMETRY
Hz
14
17 V MIN relay 11
12
V MAX relay 21 24
ON
22 14
V MIN relay 11
12
V MAX relay 21 24
22
A1 A2 Set up V MAX
TRMS Hysteresis
14 12 11 Hysteresis
Set up V MIN
V MAX
V MIN
ON
14
11
12
A1
A2
17-16
Protection relays
Wiring diagrams
Reset A1
16A
C Y
METER
Inhibition time
D E D E
B1
C F C F
14
B G OR B G Relay ON
H H
11
16A A A
12
METER
D E D E
C F C F 14
B G OR B G Relay OFF
11
A H A H
12
A1 A2 Y 14 12 11
C
Inhibition or
Reset
A2
16A
METER ON
Inhibition A1
C Y
A1 A2 Y 14 12 11 T
Inhibition or Inhibition time
C
Reset
Operation
Position Ie Relay Latch
output
A 5A OFF OFF
B ON
C ON OFF
D ON
E 16A OFF OFF
F ON
G ON OFF
H ON
17-17
Protection relays
Wiring diagrams
Current monitoring relay for Maximum current control operation with tripping latch (Latch ON)
1-phase systems A1
A2
PMA30
Single-phase connection by CT ON
L
N O
L A Reset A1
D
C Y
C(-)
B1
Inhibition time
16A
METER
Trip Max current
t > trip delay t > trip delay t < trip delay
Threshold Max current
A1 A2 Y 14 12 11 Hysteresis Max current
C
Inhibition or
Reset
C F 14
B1
B G Relay OFF
11
A H
16A 12
METER
A1 A2 Y 14 12 11
C
Inhibition or
Reset
Maximum current control operation with no tripping latch (Latch OFF)
A1
Three-phase connection by CT A2
(1 phase control)
L1 L ON
L2 O
A
L3 D
Inhibition A1
C
C(-)
Y
B1
16A
Inhibition time
METER
(1 phase control) C
D E
F
14
L B G Relay ON
L1 11
O A H
L2
A
12
L3 D
17
D E
C F 14
Relay
R OFF
C(-)
11
B1
B G
A H 12
16A
METER
A1 A2 Y 14 12 11
C
Inhibition or
Reset
Operation
Position Function Relay Latch
output
A Minimum OFF OFF
B current ON
C ON OFF
D ON
E Maximum OFF OFF
F current ON
G ON OFF
H ON
17-18
Protection relays
Wiring diagrams
ON
Reset A1
C Y
Inhibition time
D E
C F
14
B G Relay ON
11
A H
12
D E
C F 14
B G Relay OFF
11
A H
12
ON
Inhibition A1
C Y
Inhibition time
D E
C F
14
B G Relay ON
H
11
A
12
D E
B
A
C F
G
H
Relay OFF
11
14
12
17
17-19
Relay protection
Wiring diagrams
Single-phase connection by CT ON
L
N O
L A
D Inhibition time
C(-)
B1
B2
B3
B2
B3
B G
A H
Relay 14
MIN ON 11
16A
1A
50mA
12
METER
MIN current MAX current
24
D E
Relay 21
C F
MAX OFF 22
B G
A H
A1 A2 14 12 11 24 22 21 Relay 14
MIN OFF 11
12
D E
C F
Three-phase connection by CT B G Common 14-24
(1 phase control) A H relay ON 11-21
12-22
L1 L
L2 O
A D E
L3 D C F
B G Common 14-24
A H
relay OFF 11-21
C(-)
B1
B2
B3
12-22
16A
1A
50mA
METER
MIN current MAX current
ON
17
B1
B2
B3
Inhibition
A1 A2 14 12 11 24 22 21 Positions
Relay 24
D E MAX ON 21
C F
22
B G
Operation A H
Relay 14
Position Operation Relay Latch MIN ON 11
output 12
D E
C F
B G Common 14-24
A H
relay OFF 11-21
12-22
17-20
Protection relays
Wiring diagrams
L1 L
O
L2
A
ON
L3 D
L2/N
L1/L
A1
B1
L3
Reset
C
C Y
16A 600V
METER Inhibition time
14
Relay
Three-phase direct connection 11
12
L1 L
L2 O Threshold Max current
A
L3 D Hysteresis Max current
L2/N
L1/L
B1
L3
A1 A2 Y 14 12 11
C Enable
External reset enabled (ON)
A1
A2
Single-phase connection by CT
L1 L ON
N O
A
D
Reset A1
C
L2/N
Y
L1/L
B1
L3
C
14
Relay
11
Operation 12
Position Ie Connection External Threshold Max current
reset Hysteresis Max current
A 5A 1 phase OFF
Hysteresis Min cosϕ
B ON
Threshold Min cosϕ
C 3 phase OFF
D ON
E 16A 1 phase OFF
Inhibition Inhibition Inhibition Inhib. 17
F ON
G 3 phase OFF
H ON
17-21
Relay protection
Wiring diagrams
L1 L
L2 O
A ON
L3 D
L2/N
L1/L
B1
Inhibition time
C
16A 600V
D E
B1
C F
C
B G
Relay 24
A H
MAX ON 21
16A 600V
22
METER OR
D E 14
C F Relay
MIN cosϕ MAX cosϕ
B G MIN ON 11
A H 12
A1 A2 14 12 11 24 22 21
D E
C F
B G 24
A H Relay
MAX OFF 21
22
OR
Single-phase connection by CT C
D E
F Relay 14
L1 L B G MIN OFF 11
N O A H 12
A
D
L2/N
L1/L
B1
C
16A 600V
METER
MIN cosϕ MAX cosϕ Operation with no tripping latch (Latch OFF)
A1
A2
A1 A2 14 12 11 24 22 21
ON
Inhibition time
Operation
Position Connection Relay Latch
output Trip Max cosϕ
A 1 phase OFF OFF t > trip delay t < trip delay
B ON Trip Min cosϕ
F ON
Hysteresis Min cosϕ
G ON OFF
Threshold Min cosϕ
H ON
Inhibition
Positions
D E
C F
B G 24
A H Relay
MAX ON 21
22
OR
D E
C F Relay 14
B G MIN ON 11
A H 12
D E
C F
B G 24
A H Relay
21
MAX OFF 22
OR
C
D E
F Relay 14
B G MIN OFF 11
A H 12
17-22
Protection relays
Wiring diagrams
A1
A2 Reset delay MAX Delay Reset delay MIN Delay Reset delay
A1 A2
F. Detect
Set Hz MAX
Hysteresis
Rated
frequency
A1 - A2
Hz MAX A1 - A2
Hz MIN Hz MAX
ON ON
14 14
Relay 11 Relay 11
12 12
PMVF10
Max voltage
Low voltage Hysteresis 5%
utility
L Rated voltage
Hysteresis 5%
N Min voltage
L1 L2 L3 N
Ue
TRMS
V MAX
V MIN
12
22
14
11
24
21
❶ ❷
ON
K1 14 / 24
Relay 11 / 21
12 / 22
L1 L2 L3 N 17
TRMS
Ue
Hz
12
22
14
11
24
21
❶ ❷
ON
14 / 24
K1 Relay 11 / 21
12 / 22
Power source
ROCOF function ROCOF
> 0,5Hz/s ROCOF
(Rate Of Change Of Frequency) Reset time
power on ROCOF ROCOF Trip delay ≤ 0,5Hz/s
❶ Contact available for signalling, ≤ 500ms ≤ 0,5Hz/s ≤ 0,5Hz/s ≤ 200ms Reset delay
second contactor or inverter stop.
❷ Remote disconnection control device. Max frequency
Rated frequency
17-23
Protection relays
Technical characteristics
Voltage monitoring relays
CONTROL CIRCUIT
Rated voltage 208-240VAC 208-480VAC 100-240VAC 208-240VAC
to control (Ue) 380-440VAC 208-575VAC 380-575VAC
380-600VAC 600VAC
Maximum voltage set-point 105-115% Ue — — — —
Minimum voltage set-point 80-95% Ue — — 80-95% Ue —
Asymmetry set-point — — — — 5-15%Ue
Minimum and maximum –– –– –– –– ––
frequency set-point
Tripping time 0.1-20s 60ms 0.1-20s
Resetting time 0.1-20s 0.5s 0.1-20s
(0.5s at power up) (0.5s at power up)
Resetting hysteresis 3% 5% 3%
Instantaneous tripping for Ue <70% Ue configured Umin<70% Umax <70% Ue configured <70% minimum Ue
Repeat accuracy < ±0-1% < ±1% < ±0.1% < ±0.1%
POWER SUPPLY
Auxiliary voltage (Us) Self powered
Operating range 0.7-1.2Ue 0.85-1.1Ue 0.7-1.2Ue
Frequency 50/60Hz ±5%
Power consumption (maximum) 10VA (208-240VAC)∂ 20VA∂ 28VA∂ 11VA (208-240VAC)∂
17VA (380-440VAC)∂ 30VA (380-575VAC)∂
19VA (600VAC)∂
Power dissipation (maximum) 1.5W 2.2W 2.5W
RELAY OUTPUTS
Number of relays 1
Relay state Normally enegised
De-energises at tripping
Contact arrangement 1 changeover (SPDT)
Rated operational voltage 250VAC
Maximum switching voltage 400VAC
Conventional free-air thermal 8A
current (Ith)
UL/CSA and IEC/EN 60947-5-1 B300
designation
Electrical life 105 cycles
(with rated load)
17 Mechanical life 30x106 cycles
Indications 1 green LED for power on 1 green LED for power on 1 green LED for power on
and tripping and tripping and tripping
2 red LEDs for tripping 1 red LED for tripping
CONNECTIONS
Terminal tightening torque 0.8Nm (7lbin)
(maximum)
Conductor section min-max 0.2-4.0mm2 (24-12AWG)
INSULTION (input-output)
IEC rated insulation voltage Ui 440VAC 480VAC 600VAC
IEC rated impulse withstand voltage Uimp 6kV
IEC power frequency withstand 4kV
voltage
AMBIENT CONDITIONS
Operating temperature –20...+60°C
Storage temperature –30...+80°C
HOUSING
Material Selft-extinguishing polyamide
∂ Power consumption (maximum) at 50Hz.
17-24
Protection relays
Technical characteristics
Voltage monitoring relays
— — — — — —
PMV50 PMV60 PMV70 — — —
— — — PMV50 N PMV70 N PMV80 N
Minimum and maximum Minimum AC voltage, Minimum and maximum Minimum and maximum Minimum and maximum Minimum and maximum
AC voltage, phase loss and phase loss, AC voltage, phase loss, AC voltage, phase loss, AC voltage, phase loss, AC voltage and frequency,
incorrect phase sequence incorrect phase sequence and incorrect phase sequence neutral loss and incorrect neutral loss, incorrect phase phase loss, neutral loss and
asymmetry asymmetry phase sequence sequence and asymmetry incorrect phase sequence
Self powered
0.7-1.2Ue
50/60Hz ±5%
11VA (208-240VAC)∂ 27VA max
30VA (380-575VAC)∂
19VA (600VAC)∂
2.5W 1.9W max
1 2
Normally energised
De-energises at tripping
1 changeover (SPDT) 2 changeover (SPDT each)
250VAC
400VAC
8A
B300
105 cycles
30x106 cycles 17
1 green LED for power on 1 green LED for power on 1 green LED for power on
and tripping and tripping and tripping
2 red LED’s for tripping 3 red LED’s for tripping 2 red LED’s for tripping
0.8Nm (7lbin)
0.2-4.0mm2 (24-12AWG)
600VAC
6kV
4kV
–20...+60°C
–30...+80°C
Self-extinguishing polyamide
17-25
Protection relays
Technical characteristics
Current monitoring relays
17-26
Protection relays
Technical characteristics
Pump protection and phase shift monitoring relays
17-27
Protection relays
Technical characteristics
Frequency monitoring relay
TYPE PMF20
DESCRIPTION Single-phase minimum and maximum frequency control
FREQUENCY CONTROL CIRCUIT
Rated frequency 50 or 60Hz selectable
Operating frequency range 40-70Hz
Adjustment MAX tripping 101-110% operating frequency
MIN tripping 90-99% operating frequency
Resetting hysteresys 0.5%
Inhibition time 0.1-20s
Reset delay 0.1-20s
Resetting Automatic
Repeat accuracy < ±0.1%
AUXILIARY SUPPLY
Auxiliary supply voltage Us 220-240VAC
380-415VAC
Operating range 0.85-1.1 Us
Rated frequency 50/60Hz
Power consumption (maximum) 10VA (220-240VAC); 17VA (380-415VAC)
Power dissipation (maximum) 1.5W
RELAY OUTPUTS
Number of relays 1
Relay state Normally energised, de-energises at tripping∂
Contact arrangement 1 changeover contact (SPDT)
Rated operational voltage 250VAC
Maximum switching voltage 400VAC
IEC conventional free air thermal current Ith 8A
UL/CSA and IEC/EN 60947-5-1 designation B300
Electrical life (with rated load) 105 cycles
Mechanical life 30x106 cycles
Indications 1 green LED for power on/tripping
2 red LEDs for min-max tripping
CONNECTIONS
Tightening torque maximum 0.8Nm (7lbin)
Conductor section min-max 0.2-4.0mm2 (24-12AWG)
INSULATION (input - output)
IEC rated insulation voltage Ui 575V
IEC rated impulse withstand voltage Uimp 6kV
IEC power frequency withstand voltage 4kV
AMBIENT CONDITIONS
Operating temperature –20...+60°C
Storage temperature –30...+80°C
17 HOUSING
Material Self-extinguishing polyamide
∂ Normally de-energised, energises at tripping with MAX function configured.
17-28
Protection relays
Technical characteristics
Voltage and frequency monitoring relay
TYPE PMVF10
TRIPPING THRESHOLDS FOR VOLTAGE
Tripping for maximum voltage 113% of rated voltage Ue
Tripping for minimum voltage 82.5% of rated voltage Ue
Voltage threshold hysteresis 5%
Tripping delay for maximum voltage ≤0.1s
Tripping delay for minimum voltage ≤0.2s
TRIPPING THRESHOLDS FOR FREQUENCY
Frequency threshold tripping ±0.3Hz or ±1Hz configurable
Frequency threshold hysteresis 0.2%
Tripping delay ≤100ms
Transient immunity time ≥40ms
ROCOF threshold ≥0.5Hz/s
ROCOF hysteresis 25mHz/s
ROCOF tripping delay ≤200ms
ADJUSTABLE DELAYS
Reset delay 0.1-30s
AUXILIARY SUPPLY
Rated supply voltage (Us) 230VAC / 400VAC
Operating range 0.7-1.3 Ue
Rated frequency 50Hz
Power consumption/dissipation max 27VA / 1.9W
Resetting Automatic
Reset time at power up ≤500ms
RELAY OUTPUTS
Number of relays 2
Contact arrangement 1 changeover each (SPDT each)
Rated operational voltage 250VAC
Maximum switching voltage 400VAC
IEC conventional free air thermal current (Ith) 8A
UL/CSA and IEC/EN 60947-5-1 designation B300
Electrical life (with rated load) 105 cycles
Mechanical life 30x106 cycles
CONNECTIONS
Maximum tightening torque 0.8Nm (7 lbin)
Conductor cross section min-max 0.2-4.0mm2 (24-12AWG)
INSULATION (input-output)
IEC rated insulation voltage Ui 400V
AMBIENT CONDITIONS
Operating temperature –20...+60°C
Storage temperature –30...+80°C
HOUSING 17
Material Self-extinguishing polyamide
17-29