Professional Documents
Culture Documents
Transformer Damage Curve PDF
Transformer Damage Curve PDF
The information presented in this application guide is for review, approval, interpretation and application
by a registered professional engineer only. SKM disclaims any responsibility and liability resulting from
the use and interpretation of this information.
Reproduction of this material is permitted provided proper acknowledgement is given to SKM Systems
Analysis Inc.
Purpose
The purpose of this guide is to provide basic information about transformer through-fault damage curves
and characteristic landmarks necessary for plotting on time-current curves, for the purpose of equipment
overcurrent protection. Damage curves are defined in the IEEE standards in per unit on the nominal base
rating (kVA) of the transformer, and are not adjusted with changes to the core, winding material or
method of cooling.
FLA is the rated continuous current carrying capacity of a transformer at a referenced ambient
temperature and allowable temperature rise, see table 1. The FLA label is located on a time-current curve
(TCC) in top decade at 1000 seconds.
The total temperature rise of an OA 65°C transformer, at an average/maximum ambient temperature of
30/40°C, is 110/120°C. These temperatures do exceed the transformer insulation rating of 105°C, and
are allowed by the standards.
Cooling Ave/Max Hot Spot Temp. Total Temp. Insul. Max Winding
Method Amb. Temp. Temp. Rise Rise Temp. SC Temp.
15°C 75°C 120°C/130°C 130°C 300°C
20°C 90°C 140°C/150°C 150°C 350°C
AA 30°C/40°C 25°C 115°C 170°C/180°C 180°C 400°C
30°C 130°C 190°C/200°C 200°C 425°C
30°C 150°C 210°C/220°C 220°C 450°C
10°C 55°C 95°C/105°C 200°C-Al
ONAN (OA) 30°C/40°C 105°C
15°C 65°C 110°C/120°C 250°C-CU
ANSI C57.109 defines damage characteristics for oil-filled, power transformers see tables 2-5. ANSI
C57.12.59 defines damage characteristics for dry-type transformers see table 6 and 7. The through-fault
current damage curves are not intended for overload capability. The standards state, “if fault current
penetrates the limits of the thermal damage curve insulation may be damaged, or if fault current
penetrates the limits of the mechanical damage curve cumulative mechanical damage may occur. The
validity of these damage limit curves can not be demonstrated by test, since the effects are progressive
over the transformer lifetime. They are based principally on informed engineering judgment and
favorable, historical field experience.”
The damage curves are plotted in the top 3 decades of a TCC from 2 to 1000 seconds.
IEEE Std C57.12.01 defines 3 categories of dry-type transformers. However, IEEE Std C57.12.59 only
defines damage curves for Category I and II transformers. Damage curves for Category III transformers,
1668-10,000kVA 1-Ø, 5001-30,000kVA 3-Ø are not defined.
One or more inrush current points may be plotted on a TCC. Inrush currents are expressed in peak
amps. The most common point is 8-12 times rated FLA at 0.1 seconds. Another less common point is 25
times rated FLA at 0.01 seconds.
Example 1
Plot the characteristic landmarks for a 1000kVA, 65°C, 4160-480/277V, ∆-YG, oil-filled, substation
transformer with an impedance of 6.0%. Consider both the frequent and infrequent fault cases for this
application.
Solution
Since the transformer is connected ∆-YG a separate set of data points must be calculated for primary-side
protective devices. Primary-side devices will only see 58% of a secondary-side, single-line-to-ground
fault.
Example 2
Repeat Example 1 but now assume the secondary is high-resistance grounded (HRG).
Solution
No shifting of the damage curve is required with a HRG secondary. In this case the primary-side
protective devices will not see a ground fault on the secondary-side. Ground fault magnitudes will always
be much lower than load current levels.
Example 3
Plot the characteristic landmarks for a 1500kVA, 150°C, 13800-480/277V, ∆-∆, dry-type, substation
transformer with an impedance of 5.75%. Consider the infrequent fault case for this application.
Solution
Since the transformer is connected ∆-∆ a separate set of data points must be calculated for primary-side
protective devices. Primary-side devices will only see 87% of a secondary-side, line-to-line fault.
• IEEE Std 242, IEEE Recommended Practice for Protection and Coordination of Industrial and
Commercial Power Systems (IEEE Buff Book)
• IEEE Std C57.12.00, IEEE Standard General Requirements for Liquid-Immersed Distribution,
Power and Regulating Transformers
• IEEE Std C57.12.01, IEEE Standard General Requirements for Dry-Type Distribution and Power
Transformers Including Those with Solid-Cast and/or Resin-Encapsulated Windings
• IEEE Std C57.12.59, IEEE Guide for Dry-Type Transformer Through-Fault-Current Duration
• IEEE Std C57.109, IEEE Guide for Liquid-Immersed Transformer Through-Fault-Current Duration
Insulating materials
Insulation Maximum
Insulating Materials
Class Temperature
Cotton, silk, paper, wood,
Y 90°C cellulose, fibre without
impregnation or oil-immersion
Class Y impregnated with natural resins,
A 105°C cellulose esters, insulating oils, etc.,
also laminated wood, varnished paper
TInsuldur® InsulationT
Hybrid A 110°C Kraft paper with epoxy binders
activated under pressure
Synthetic-resin enamels, cotton
E 120°C and paper Laminates
with formaldehyde bonding
Mica, glass fibre, asbestos, etc., with
suitable bonding substance; built-up
B 130°C
mica,
glass-fibre and asbestos laminates
The materials of Class B with more
F 155°C
thermally-resistant bonding materials
Glass-fibre and asbestos materials,
H 180°C and built-up mica, with appropriate
Silicone resins
Mica, ceramics, glass, quartz, and
C >180°C asbestos without binders or with silicone
resins of superior thermal stability
TNOMEX® insulation,
>H 220°C varnish dipped and vacuum pressure
impregnated (VPI)