You are on page 1of 1

Functions Protection

Sepam series 80 Tripping curves

Customizedtrippingcurve
PE0

Defined point by point using the SFT2841 setting and operating software tool, this
curve may be used to solve all special cases involving protection coordination or
revamping.

IDMT tripping curves


Current IDM T tripping curves
Multiple IDMT tripping curves are offered, to cover most applications:
b IEC curves (SIT, VIT/LTI, EIT)
b IEEE curves (MI, VI, EI)
b usual curves (UIT, RI, IAC).

3
Customized tripping curve set using SFT2841 software.
IECcurves
Equation Curvetype Coefficient values
k a b
Standard inverse / A 0.14 0.02 2.97
k T
t d( I) = ---------------------- × --- Very inverse / B 13.5  1.50
 --I---  – 1 b
a
Long time inverse / B 0  13.33
 Is 
Extremely inverse / C 0  0.808
Ultra inverse 315.2 2.5 

RIcurve
Equation: 1 T
td ( I ) = -------------------------------------------------------- × -------------------
I –1 3 ,1706
0 ,339 – 0,236 -----  
 Is 

IEEEcurves
Equation Curvetype Coefficient values
A B p b
Moderately inverse 0.010 0.023 0.02 0.241
 
 A  T Very inverse 3.922 0.098  0.138
td ( I ) = ------------------------ + B  × ---
 I p  b Extremely inverse 5.64 0.0243  0.081
 -Is
---
 –
1 

IEEEcurves
Equation Curvetype Coefficient values
A B C D E b
Inverse 0.208 0.863 0.800 -0.418 0.195 0.297
 
 B D E  T Very inverse 0.090 0.795 0.100 -1.288 7.958 0.165
td ( I ) = A + -------------------- + ----------------------- + ----------------------- x -----
 ---I- – C  ---I-- – C
2
---I-- – C   b
3 Extremely inverse 0.004 0.638 0.620 1.787 0.246 0.092
 Is  Is  Is 

0

Livre 1.indb 102 18/04/2007 11:00:48