You are on page 1of 20

MAIN SHEET

MOTOR HISTORY RECORD - INDEX

S.NO
1
2
3
4
5
6
7
MOTOR HISTORY RECORD - INDEX

DESCRIPTION
NAME PLATE
DATA SHEET
FEEDER DETAILS
RELAY SETTINGS
CABLE DETAILS
MOTOR MAINTENANCE
TRIP REPORT
MAIN SHEET

BFPT AIR EXHAUST FAN A- A

NAME PLATE DETAIL


NAME BFPT AIR EXHAUST FAN A
POWER 2.2 KW S.NO 62306
VOLTAGE 415 V POWER FACTOR 0.85
CURRENT 4.4 A IP 55
SPEED 2840 BEARING NO DE 6205-2RSR
PT AIR EXHAUST FAN A- A

NAME PLATE DETAIL


MAKE
62306 DUTY S1
0.85 INSULATION CLASS F
55 MODEL YB2-90L-281Z
6205-2RSR BEARING NO NDE 6205-2RSR
MAIN SHEET

FEEDER DETAILS
FEEDER LOCATION EDR
PANEL NAME TG MCC- A
FEEDER NUMBER 2BJA04C01-01
MOTOR LOCATION TG 13.7 MTR
MAIN SHEET

TGMCC MOTOR FEEDERS - MMPR RELAY SETTINGS


NAME OF THE MOTOR BFPT VAPOUR EXHAUST FAN
RATING-Ie 4.4
CT RATIO CT-5

TRIPS
SL.NO DESCRIPTIONS /ALARMS STATUS

1 OVER TIME STARTING PROTECTION TRIP OFF

INSTANTANEOUS OVER CURRENT


2 PROTECTION TRIP ON

3 LOCKED ROTOR PROTECTION TRIP ON


TRIP ON
4 OVER LOAD PROTECTION ALARM OFF

TRIP OFF

5 THERMAL PROTECTION ALARM OFF

6 UNBALANCE PROTECTION TRIP ON

7 ZERO SEQUENCE PROTECTION TRIP ON


TRIP OFF
8 RESIDUAL CURRENT PROTECTION ALARM OFF
9 OPEN PHASE PROTECTION TRIP ON
10 PHASE SEQUENCE PROTECTION TRIP ON

11 UNDER POWER PROTECTION TRIP ON


12 VOLTAGE PROTECTIONS

UV - UNDER VOLTAGE TRIP ON


ALARM OFF
OV - OVER VOLTAGE TRIP ON
13 TECHNOLOGY INTERLOCK TRIP OFF
14 tE PROTECTION TRIP ON
- MMPR RELAY SETTINGS
BFPT VAPOUR EXHAUST FAN 2A – A RUNNNING
4.4
CT-5

PARAMETERS UOM VALUES


a)RATED CURRENT A 4.4
b)STARTING TIME S 5
a)I > STARTING A 5 X Ie
b)I >> POST START A I X Ie
c)DELAY OF I >> S 5
LOCKED ROTOR CURRENT A 2 X Ie
LOCKED ROTOR DELAY S 3
OVER LOAD CURRENT A 1 X Ie
OVER LOAD DELAY S 8
HEAT TIME CONSTANT S 20
COLD TIME CONSTANT 100
K1 1
K2 10
OVER HEAT COEFFICIENT % 50

UNBALANCE SETTING % 60
UNBALANCE DELAY S 3
ZERO SEQUENCE SETTING A 1 X Ie
ZERO SEQUENCE DELAY  S 0.5
RESIDUAL CURRENT SETTING mA 2000
RESIDUAL CURRENT DELAY S 100
OPEN PHASE DELAY S 0.05
PHASE SEQUENCE DELAY S 3
UNDER POWER SETTING KW 1
UNDER POWER DELAY S 0

LOW VOLTAGE SETTING V 249


LV MODE 00 : MAX OF V
LV MODE 01 : MIN OF V
LOW VOLTGE DELAY S 0.5
OVER VOLTAGE SETTING V 490
OVER VOLTAGE DELAY S 5
TECHNOLOGY INTERLOCK DELAY S 100
tE PR0TECTION TIME S 3
BACK

CABLE DETAILS
CABLE SIZE 3CX6
LUG SIZE 6
CABLE LENGTH
LUG TYPE RING
GLAND SIZE
MOTOR MAINTENANCE

CONDITION MONITORING SHUTDOWN MAINTENANCE


MAINTENANCE

MAINTENANCE PREVENTIVE MAINTENANCE


MAIN SHEET
CONDITION MONITOR
CURRENT VIBRATION WINDING TEMPERATURE

S.NO DATE
Rph Yph Bph DE X DE Y NDE X NDE Y Rph Yph
ION MONITORING
NG TEMPERATURE MOTOR TEMPERATURE
ANY
NON RUNNING CLEANIN
BODY DRIVEN EARTHING ABNORMA REMARKS
Bph DRIVEN HOURS G
SIDE END LITIES
END
MAIN SHEET

MOTOR MAINTENANCE
PREVENTIVE MAINTENANCE
SHUTDOWN MAINTENANCE
SHUTDOWN M
IR TEST WR TEST
S.NO DATE APPLIED VOLTAGE IR VALUE R-R' Y-Y' B-B'
SHUTDOWN MAINTENANCE
EARTHING FLAT
TERMINAL TIGHTNESS GREASING TIGHTNESS BASE BOLT TIGHTNESS
OVERHAULING SEALING REMARKS
MAIN SHEET

MOTOR MAINTENANCE
CONDITIONING MONITORING
PREVENTIVE MAINTENANCE
PREVENTIVE MAINTENANCE
SCHEDULED COMPLETED
S.NO PTW DESCRIPTION REMARKS
DATE DATE
MAIN SHEET

MOTOR MAINTENANCE
SHUTDOWN MAINTENANCE
CONDITIONING MONITORING
TRIP REPORT
S.NO DATE CAUSE OF TRIPPING ACTION TAKEN REMARKS

MAIN SHEET