You are on page 1of 12

Liquid filled transformers

IEC standard small and medium,


rated power<2500 kVA, HV ≤36 kV
Even our standard solutions are special

In almost every place where people live and work you will find With this approach we can tailor the most appropriate technical
at least one transformer. But as long as it keeps working and solution to every problem. A high Duality solution with better
supplying power to the escalator in the department store, the service and support, better for the environment and yet with
hotel lift, the office computer, the oven in the local bakery, the farm greater availability and a lower total cost ownership than our
machinery or the petrochemical plant nobody gives it a second competitors.
thought.
All over the world – in underground railways, in amusement parks
However, transformers are one of the most important units in and every place where people work or live – you will find ABB
every production process. Without them the core activities of transformers at work.
nearly every business and factory would come to a standstill
– with serious financial consequences. ABB invites you to find the optimal solution to your application and
to see with your own eyes that even our standard solutions are
After nearly 100 years developing and manufacturing transformers special.
we are well aware of this dependency. This is why we never
compromise on the performance, security or reliability of our Quality statement
products. Nor on design, materials, manufacturing methods, Our production facilities are ISO 9001/14001, GOST certified. Our
environmental protection or recycling. aim is to deliver your distribution transformers fast, on time and
conform to your specifications.
Our objective is to support you and to add value to your activities
by offering a comprehensive range of quality transformers. Working with us, you have access to a worldwide network
We also provide top class service and support. of factories and facilities serving you locally with a full range
of products and solutions. Our warranty provides one ABB quality
and service.

2 Liquid filled transformers


Construction features

Description Additionally, for transformers with a conservator:


ABB factories manufacture a wide range of oil and dry type – magnetic oil level indicator,
transformers. This brochure describes three phase oil type – Buchholz relay,
distribution transformers up to 2500 kVA and 36kV. – oil filling plug on the conservator,
They are used to step down three-phase high voltage to low – dehydrating breather.
voltage for power distribution, mainly in urban areas and for
industrial applications. Our standard transformers are designed Other product types with different dimensions and technical
for use in moderate climates and can be installed both outdoors specifications can be designed and manufactured on request.
and indoors. The loading capability is designed to comply with
IEC 354. Distribution transformers can be hermetically sealed ABB technology – Common Technology (CT)
(the tank is completely filled with oil) or equipped with an oil Our transformers are manufactured to provide you with a high
conservator. Tanks are constructed with flexible corrugated walls quality and reliable transformer. ABB have developed a Common
(fins), which enables sufficient cooling of the transformer. Technology (CT) platform, which defines design standards,
The corrugated walls also compensate for the changes in the oil equipment and processes used in all our factories. Use of this
volume during operation. An advantage of the hermetically sealed Common Technology enables us to guarantee our customers
transformers is that oil is never in contact with the atmosphere a high quality and consistent product.
thus avoiding periodic oil analysis.
The key production features of our small and medium distribution
Our transformers are adaptable for pole mounting or assembly in common technology are:
substations. – oval core,
– step lap,
Standard features – automatic cutting and stacking of core legs,
Hermetically sealed: –w indings directly wound on the core legs or mandrels with 2 HV
– corrugated tank, coils in parallel (smallest units),
– HV and LV DIN bushings, –e poxy diamond dotted paper insulation between LV layers,
– off-circuit tap changer, – tapered or full width layer insulation in HV windings.
– oil drain valve,
– oil filling plug on the cover, What we achieved is:
– lifting lugs, – standardization of products,
– earthing terminals, – automation of production,
– rating plate, – stable process and quality,
– mineral oil (inhibited or uninhibited), – high reliability,
– overpressure valve. – higher LV insulation level.

Liquid filled transformers 3


Core to meet the customer’s insulation level requirements and also
The magnetic circuit is of the three-column type with mitred joints. to withstand the short circuit forces as outlined in IEC 60076-5.
It is manufactured with firstrate, grain oriented magnetic, The neutral point of LV windings are brought up to the tank cover.
cold-rolled silicon steel laminations. The mounted core is clamped
down in order to reduce vibrations and minimize noise levels. Off-circuit tap changer
Further noise level and no load losses decreasing are achieved The tappings of the HV winding, are connected to the off-circuit
by step lap core construction. tap changer located horizontally between the yoke and the tank
cover. The handle is located on the cover and should only be
Core design is an important factor of any transformer’s efficiency. operated when the transformer is deenergized. The design
The geometric core arrangement and the materials chosen prevents setting the off-circuit tap changer to intermediate
determine the losses and noise levels. Grain oriented transformer positions. The mechanism can also be padlocked during normal
sheet steel is used in the core construction. It is cut by the most transformer operation.
modern, fully automated core cutting machinery and assembled
into limb and yoke sets. This results in high dimensional accuracy, Insulating liquids
excellent space factor, and low loss values. By using step-lap The mineral oil – both inhibited and uninhibited types – with its
technology, the no-load currents can be reduced improving electrical and chemical characteristics is in compliance with
the drawbacks associated with reactive power compensation. the IEC Standards and is P.C.B. and P.C.T. free.

Windings ABB provides and promotes its own solution as well. BIOTEMP®
The windings are made of two components, conductor material is biodegradable, vegetable based oil dielectric insulating fluid
and the insulation material. The conductors used are a high grade used in electrical transformers. The product reduces
electrolytic copper or aluminum. They are insulated with pure environmental threats posed by transformer insulating oil spills.
cellulose or double enamel. The HV windings are wound either
with round, double enamel insulated, or rectangular, paper On special requests other fluids are available (silicon oil or midel).
insulated wire. The LV windings are wound with rectangular paper
insulated wire, enameled wire or foil. The windings are designed

4 Liquid filled transformers


...manufactured, assembled, painted and tested in the factory

SmartChoke-protected, high dU/dt resistant transformer by ABB Distribution transformer equipped with LV surge arresters

Tank and cover – Oil level indicator


Tank walls are made of corrugated cooling surfaces. The bottom – Pressure relief valve with or without contacts
plate, side and frames are of welded construction. The welds are – Multifunction protection device
tested for oil tightness. All protection device flanges, bushings, tap – HV and LV cable boxes (IP 44 or IP 55)
switch drive and lifting lugs are fitted on the tank cover. – Off-circuit tap changer with 3,5 or 7 positions (9 on request)
The cover is bolted to the tank frame. – Thermometer pocket
– Skid base or bi-directional rollers
The underbase channel is welded to the base plate and the rollers – Pole brackets integrated on tank
are suitable for either longitudinal or transverse movements. – Arcing horns
Single pole 3-phase transformers are delivered with flat base as – Dual high voltage transformers
standard, but optionally can be equipped with underbase channel – Galvanized tank
beams where bi-directional wheels are a requirement. – Terminal box.

The complete tank is tested and approved according Smartchoke


to CENELEC HD 428.6 S1 standard. Special type lifecycle tests Unique ABB solution to protect transformers against ultra steep
of more than 10 000 cycles simulating over 30 years operation front waves which are extremely dangerous to the electrical
were carried out with positive results. equipments like transformers. It reduces both steepness and
amplitude of high dU/dt transients. As it is integrated with the
Painting and surface treatment bushings the filtering takes place before it reaches the windings.
All metal parts are carefully sand-blasted. The initial protective
coating is made up of a single coat of one pack epoxy paint. LOVOS
The final paint coating is made up of several coats of paint. Transformer can be equipped with LOVOS – a new generation of
Alternatively, hot dip galvanized transformers can be supplied for LV surge arresters without spark gap and with varistors of metal
use in heavy corrosion areas. All units are painted in RAL 7033 oxide technology. It provides protection along LV overhead lines,
but other colors are available on request. Detailed painting for different electrical equipment connected to the line, from
procedures for different environmental conditions are also transformers up to measuring instruments. Arresters installed on
available. the secondary bushings reduce the overvoltages generated in the
medium voltage system and transferred to the low voltage side
Options and accessories by capacitive, magnetic or earth coupling through a transformer
– Plug-in bushings on HV side itself. In this way high quality of electricity supply is secured.
– Dial type thermometer with two contacts

Liquid filled transformers 5


Quality and references

Quality and testing – Measurement of the harmonics of the no-load current


Our production facilities where all ABB transformers are (IEC 60076-1),
manufactured are certified according to ISO 9001:2000, – Measurement of insulation resistance to earth of the windings.
ISO 14001:2004, PN-N-18001:2004 and GOST.
Specially designed reinforced transformers suitable for pole
At the end of the manufacturing process the transformers are mounting, protected with arcing horns are tested in accordance
individually tested in accordance with the IEC Standards. with to SFS 2646 steep wave execution.

The routine tests are according to IEC 60076-1: ABB has thousands of liquid filled transformers at work all over
– Measurement of winding resistance, the world in many different applications, such as utilities,
– Measurement of voltage ratio and check of phase displacement, windmills, compact substations and industrial transformers.
– Measurement of short-circuit impedance and load loss,
– Measurement of no-load loss and current, ABB is different…
– Dielectric routine tests, …offering the best and most reliable products according to meet
– Tests on on-load tap-changers, where appropriate. the demanding requirements of all our customers. We offer our
customers:
Upon request, witnessed type/special tests can be carried out: – Quality – guaranteed by the most modern technology,
– Temperature-rise test (IEC 60076-2), equipment, processes and constantly improved in ABB R&D
– Dielectric type and special tests (IEC 60076-3), centers all over the world,
– Sound level test (IEC 60551), – Speed – the shortest delivery time – within days instead of
– Partial discharge test (IEC 60270), weeks,
– Measurement of zero-sequence impedance(s) (IEC 60076-1), – Focus Factories concept – specialized factories that are
– Short-circuit withstand test (IEC 60076-5), focused on specific product ranges to deliver consistent quality
and competitive products across the globe.

6 Liquid filled transformers


Outline drawing

L W

H
E

D
D

Description:
1 Tank
2 Cover
3 Wheel base
4 Tap-changer handler
5 Lifting lugs
6 Oil drain valve
7 HV bushing
8 LV bushing
9 Filling plug
10 Oil level indicator
11 Safety valve
12 Earthing terminal
13 Rating plate

Liquid filled transformers 7


Technical data

HV Uk Power NLL LL losses L W H oil weight total LWA


[kV] [%] [kVA] [W] (75°C) comb. appr. appr. appr. appr. [kg] weight [dB(A)]
[W] [mm] [mm] [mm] appr. [kg]
50
10 4 50 190 1100 A-A’ 780 670 890 90 365 55
50 125 1350 B-C’ 880 670 890 90 370 47
50 125 1100 A-C’ 780 670 890 90 375 47
50 125 875 C-C’ 860 645 890 100 420 47
20 4 50 190 1100 A-A’ 840 645 1015 100 395 55
50 125 1350 B-C’ 780 620 1015 95 375 47
50 125 1100 A-C’ 840 645 1015 110 420 47
50 125 875 C-C’ 900 670 1015 130 475 47
Wheelbase (D): 520mm Wheel diameter: (E): 125mm Wheel width: 40mm
100
10 4 100 320 1750 A-A’ 840 795 1040 130 580 59
100 210 2150 B-C’ 1140 745 1090 150 610 49
100 210 1750 A-C’ 1140 745 1090 145 660 49
100 210 1475 C-C’ 900 670 1090 150 690 49
20 4 100 320 1750 A-A’ 1200 770 1065 145 625 59
100 210 2150 B-C’ 1200 770 1065 145 605 49
100 210 1750 A-C’ 1200 770 1065 145 625 49
100 210 1475 C-C’ 960 690 1115 165 680 49
Wheelbase (D): 520mm Wheel diameter: (E): 125mm Wheel width: 40mm
160
10 4 160 460 2350 A-A’ 1060 690 1140 180 840 62
160 300 3100 B-C’ 960 740 1140 180 805 52
160 300 2350 A-C’ 1060 690 1140 180 840 52
160 300 2000 C-C’ 1060 690 1140 180 865 52
20 4 160 460 2350 A-A’ 1020 715 1215 205 880 62
160 300 3100 B-C’ 1060 690 1215 180 825 52
160 300 2350 A-C’ 1020 715 1215 205 880 52
160 300 2000 C-C’ 1020 715 1215 205 905 52
Wheelbase (D): 520mm Wheel diameter: (E): 125mm Wheel width: 40mm
200
10 4 200 550 2850 A-A’ 1120 715 1140 200 960 65
200 360 3800 B-C’ 1120 865 1140 215 960 55
200 360 2850 A-C’ 1120 715 1140 200 960 55
200 360 2450 C-C’ 1120 765 1140 200 1010 55
20 4 200 550 2850 A-A’ 1120 765 1215 200 990 65
200 360 3800 B-C’ 1120 865 1215 210 980 55
200 360 2850 A-C’ 1120 765 1215 200 990 55
200 360 2450 C-C’ 1380 780 1215 230 1090 55
Wheelbase (D): 520mm Wheel diameter: (E): 125mm Wheel width: 40mm
250
10 4 250 650 3250 A-A’ 1320 765 1245 205 1110 65
250 425 4200 B-C’ 1320 815 1245 215 1100 55
250 425 3250 A-C’ 1320 765 1245 205 1110 55
250 425 2750 C-C’ 1020 715 1275 200 1160 55
20 4 250 650 3250 A-A’ 1080 780 1320 220 1135 65
250 425 4200 B-C’ 1320 765 1245 230 1140 55
250 425 3250 A-C’ 1080 780 1320 220 1140 55
250 425 2750 C-C’ 1080 780 1350 230 1230 55
Wheelbase (D): 520mm Wheel diameter: (E): 125mm Wheel width: 40mm

8 Liquid filled transformers


Technical data

HV Uk Power NLL LL losses L W H oil weight total LWA


[kV] [%] [kVA] [W] (75°C) comb. appr. appr. appr. appr. weight [dB(A)]
[W] [mm] [mm] [mm] [kg] appr.[kg]
400
10 4 400 930 6000 B-A’ 1420 890 1350 270 1350 68
400 930 4600 A-A’ 1350 850 1420 260 1310 68
400 610 6000 B-C’ 1500 940 1400 280 1340 58
400 610 4600 A-C’ 1250 850 1500 260 1400 58
400 610 3850 C-C’ 1260 850 1540 340 1600 58
20 4 400 930 6000 B-A’ 1420 890 1400 270 1350 68
400 930 4600 A-A’ 1350 850 1470 260 1310 68
400 610 6000 B-C’ 1500 940 1450 280 1340 58
400 610 4600 A-C’ 1250 850 1550 260 1400 58
400 610 3850 C-C’ 1260 850 1590 340 1600 58
Wheelbase (D): 670mm Wheel diameter: (E): 125mm Wheel width: 40mm
500
10 4 500 1100 5500 A-A’ 1420 850 1420 280 1500 69
500 730 5500 A-C’ 1470 850 1810 310 1720 59
20 4 500 1100 5500 A-A’ 1420 850 1470 280 1500 69
500 730 5500 A-C’ 1470 850 1860 310 1720 59
Wheelbase (D): 670mm Wheel diameter: (E): 125mm Wheel width: 40mm
630
10 4 630 1300 8400 B-A’ 1590 1010 1530 350 1800 70
630 1300 6500 A-A’ 1220 980 1530 410 2155 70
630 860 8400 B-C’ 1800 1100 1620 400 2070 60
630 860 6500 A-C’ 1200 900 1580 390 2040 60
630 860 5400 C-C’ 1220 850 1630 340 2040 60
10 6 630 1200 8700 B-A’ 1660 1010 1490 410 1810 70
630 1200 6750 A-A’ 1420 850 1540 390 1900 70
630 800 8700 B-C’ 1580 1010 1520 360 1800 60
630 800 6750 A-C’ 1220 980 1510 400 2000 60
20 4 630 1300 8400 B-A’ 1590 1010 1580 395 1790 70
630 1300 6500 A-A’ 1220 980 1580 410 2155 70
630 860 8400 B-C’ 1800 1100 1670 400 2070 60
630 860 6500 A-C’ 1200 900 1630 390 2040 60
630 860 5400 C-C’ 1220 850 1700 340 2040 60
20 6 630 1200 8700 B-A’ 1660 1010 1530 410 1810 70
630 1200 6750 A-A’ 1420 850 1590 390 1900 70
630 800 8700 B-C’ 1580 1010 1570 360 1800 60
630 800 6750 A-C’ 1220 980 1560 400 2000 60
Wheelbase (D): 670mm Wheel diameter: (E): 125mm Wheel width: 40mm
800
10 6 800 1300 10000 B-A’ 1740 1090 1530 490 2230 72
800 1300 8500 A-A’ 1680 940 1540 430 2190 72
800 920 10000 B-C’ 1470 980 1620 460 2400 62
800 920 8500 A-C’ 1560 870 1570 460 2270 62
20 6 800 1300 10000 B-A’ 1740 1090 1580 490 2230 72
800 1300 8500 A-A’ 1680 940 1590 430 2190 72
800 920 10000 B-C’ 1470 980 1670 460 2400 62
800 920 8500 A-C’ 1560 870 1620 460 2270 62
Wheelbase (D): 670mm Wheel diameter: (E): 125mm Wheel width: 40mm

Liquid filled transformers 9


Technical data

HV Uk Power NLL LL losses L W H oil weight total LWA


[kV] [%] [kVA] [W] (75°C) comb. appr. appr. appr. appr. weight [dB(A)]
[W] [mm] [mm] [mm] [kg] appr.
[kg]
1000
10 6 1000 1700 13000 B-A’ 1770 1080 1740 610 2650 73
1000 1700 10500 A-A’ 1780 1100 1630 500 2520 73
1000 1100 13000 B-C’ 1700 1120 1800 550 2740 63
1000 1100 10500 A-C’ 1900 1220 1600 510 2750 63
20 6 1000 1700 13000 B-A’ 1770 1080 1790 610 2650 73
1000 1700 10500 A-A’ 1780 1100 1680 500 2520 73
1000 1100 13000 B-C’ 1700 1120 1850 550 2740 63
1000 1100 10500 A-C’ 1900 1220 1650 510 2750 63
Wheelbase (D): 820mm Wheel diameter: (E): 160mm Wheel width: 40mm
1250
10 6 1250 2100 15400 B-A’ 1900 1180 1760 640 3030 75
1250 2100 13000 A-A’ 1880 1170 1810 600 3080 75
1250 1320 15400 B-C’ 1960 1250 1750 605 3210 65
1250 1320 13000 A-C’ 1880 1180 1730 620 3340 65
20 6 1250 2100 15400 B-A’ 1900 1180 1810 640 3030 75
1250 2100 13000 A-A’ 1880 1170 1860 600 3080 75
1250 1320 15400 B-C’ 1960 1250 1800 605 3210 65
1250 1320 13000 A-C’ 1880 1180 1780 620 3340 65
Wheelbase (D): 820mm Wheel diameter: (E): 160mm Wheel width: 40mm
1600
10 6 1600 2600 20000 B-A’ 1940 1160 2040 900 3880 76
1600 2600 17000 A-A’ 1990 1270 1860 680 3640 76
1600 1700 20000 B-C’ 1930 1240 1760 640 3610 66
1600 1700 17000 A-C’ 1980 1160 1800 750 4140 66
20 6 1600 2600 20000 B-A’ 1940 1160 2170 945 4050 76
1600 2600 17000 A-A’ 1990 1270 1910 680 3640 76
1600 1700 20000 B-C’ 1930 1240 1810 640 3610 66
1600 1700 17000 A-C’ 1980 1160 1850 750 4140 66
Wheelbase (D): 820mm Wheel diameter: (E): 160mm Wheel width: 40mm
2000
10 6 2000 3100 21000 A-A’ 2070 1290 2040 870 4530 80
2000 2100 21000 A-C’ 1960 1140 1900 870 4590 70
20 6 2000 3100 21000 A-A’ 2070 1290 2090 870 4530 80
2000 2100 21000 A-C’ 1960 1140 1950 870 4590 70
Wheelbase (D): 1070mm Wheel diameter: (E): 200mm Wheel width: 40mm

Above data are only examples to give an overview of possible


standard transformers.

Transformers can be optimized with respect to capitalised losses


for optimization of Total Cost of Ownership (TCO).

10 Liquid filled transformers


Distribution transformers offered by ABB – HVDC Converter,
Liquid filled distribution transformers: – Windmills,
– up to 72,5 kV, – Autotransformers,
– single phase and three phase, – Grounding/Earthing Transformers,
– ground mounted, pole mounted or pad mounted. – Neutral Earthing Reactors,
– Current Limiting Reactors,
Dry transformers: – Arc Furnace,
– Open Wound, – Booster Transformers.
– Vacuum Cast Coil,
– RESIBLOC®. Services offered by ABB distribution transformers
– Environmental Services – PCB Elimination Services,
Transformers for special applications like: – Installation and Commissioning,
– Railway application, – Training,
– Marine: propulsion and distribution, – Testing and maintenance,
– Carrier Vessel Nuclear, – Retrofits, Revamping and up-grading,
– Rectifier Transformers, – Spare parts procurement,
– Variable Speed Drive, – Technical information available from www.abb.com/transformers.
– Excitation Transformers,

Liquid filled transformers 11


Contact us

ABB Sp. z o.o. Note:

2451PL024-W2-en. Edition 04.2010


Branch in Lodz We reserve the right to make technical changes or modify
the contents of this document without prior notice. With
67/93 Aleksandrowska Str.
regard to purchase orders, the agreed particulars shall
91-205 Lodz, Poland prevail.
Phone: +48 42 29 93 000 ABB does not accept any responsibility whatsoever for
Fax: +48 42 29 93 232 potential errors or possible lack of information in this
document.
We reserve all rights in this document and in the subject
www.abb.com/transformers matter and illustrations contained therein. Any reproduction
– in whole or in parts – is forbidden without ABB’s prior
written consent.

© Copyright 2010 ABB


All rights reserved.

You might also like