Professional Documents
Culture Documents
69
MCCB
Table 9.1 Impedances of 3-Phase Transformers
Load Transformer Impedance (%)
capacity (kVA) %R %X
Supply side
Load terminal in the case of
50 1.81 1.31
insulated line (the line 75 1.78 1.73
impedance on the MCCB
load side can be added.) 100 1.73 1.74
150 1.61 1.91
200 1.63 2.60
MCCB load terminals in the case of bare line (the line
impedance on the MCCB load side may not be added). 300 1.50 2.82
500 1.25 4.06
Fig. 9.1 Short-Circuit Locations for Current Calculations 750 1.31 4.92
1000 1.17 4.94
1500 1.23 5.41
2000 1.13 5.89
70
Thus, when calculating the short-circuit current at
(ZL + ZT) · ZM
ZS = = RS + j XS various points in a load system, if the value ZS is first
ZL + ZT + ZM
computed, it is a simple matter to add the various wire
RS =
[ + (X + X + X ) {X (R + R ) + R (X + X )} ]
(R + R + R ) {R (R + R ) – X (X + X )}
L
L
T
T
M
M
M
M
L
L
T
T
M
M
L
L
T
T
or bus-duct impedances. Table 9.4 gives values of
total supply impedance (ZS), using transformer imped-
)2
(RL + RT + RM + (XL + XT + XM )2 ance per Table 9.1, power-supply short-circuit capacity
of 1000MVA, and X/R of 25.
XS =
[
(RL + RT + RM) {XM(RL + RT) + RM(XL + XT)}
– (XL + XT + XM) {RM(RL + RT) – XM(XL + XT)} ]
(RL + RT + RM)2 + (XL + XT + XM)2
L
Short-
circuit
T point
B
W
ZM
ZL ZT
ZB ZW
ZM
ZB ZW
ZL ZT
ZS ZB ZW
71
9.4 Classification of Short-Circuit Current 1 2πR 1 2πR
A DC current (Fig. 9.3) of magnitude determined by that is: K3 = { 1 + 2e – x + 2 1 + e – x }
3 2
the voltage phase angle at the instant of short circuit K3 is the asymmetrical coefficient, derived from the
and-the circuit power factor will be superimposed on symmetrical value and the circuit power factor.
the AC short-circuit current. 3. Peak Value of Asymmetrical Short-Circuit Current
This DC component will rapidly decay; however, This value (Ip in Fig. 9.3) depends upon the phase
where a high-speed circuit-interruption device such angle at short circuit closing and on the circuit power
as an MCCB or fuse is employed, the DC component factor; it is maximum when θ = 0. It will reach peak
must be considered. Further, the mechanical stress π
value in each case, ωt = 2 + ϕ after the short circuit
of the electric circuit will be affected by the maximum occurrence. It can be computed as before, by means
instantaneous short-circuit current; hence, the short- of the circuit power factor and the symmetrical short-
circuit current is divided, as below. circuit current.
1. RMS Symmetrical Short-Circuit Current (Is)
–( π + ϕ)· R
This is the value exclusive of the DC component; it is p = s [1 + sinϕ·e 2 x] =
s · Kp
As/M2 of Fig. 9.3. π
–( + ϕ)· R
2. RMS Asymmetrical Short-Circuit Current (Ias) thus: Kp = 2 [1 + sinϕ·e 2 x ]
This value includes the DC component. It is defined Kp, the peak asymmetrical short-circuit current coeffi-
as: cient, is also known as the closing-capacity coefficient,
As 2 since Ip is called the closing capacity. Thus, in each
as = ( ) + Ad2 case, the asymmetrical coefficients can be derived
2
Accordingly, when the DC component becomes maxi- from the symmetrical values and the circuit power fac-
mum (i.e., θ – ϕ = ± 2π , where the voltage phase angle tor. These coefficients are shown Fig. 9.4.
at short circuit is θ, and the circuit power factor is cosϕ),
Ias will also become maximum 12 cycle after the short
1/2 Cycle
1.7
Kp
1.6
Kp
2.0 1.5
1.4
1.3
K1
K3
1.2
1.1
1.0 1.0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Power factor
72
9.5 Calculation Procedures
73
Table 9.6 Calculation Example: 3-Phase Short-Circuit Current
% impedance method Ohmic method
The supply short-circuit capacity, being unknown, is The supply short-circuit capacity, being unknown, is
defined as 1000MVA with XL/RL = 25. defined as 1000MVA with XL/RL = 25.
From Eq. 13, at the 1000kVA reference capacity: From Eq. 10, the supply impedance seen from the
3 primary sicde:
ZL = 1000 x 106 x 100 = 0.1 (%) 2
1000 x 10 ZL = (6600) 6 = 0.0436 (Ω)
1000 x 10
since XL/RL = 25, and since XL/RL = 25: ZL = 1.741 + j43.525 (mΩ)
0.1 = RL2 + (25RL)2 = 25.02RL From Eq. 11, supply impedance converted to the
secondary side is:
ZL = RL + jXL = 0.0040 + j0.0999 (%) 2
Power supply ZL = (1.741 + j43.525) x 440
( )
impedance 6600
ZL = 0.00773 + j0.1934 (mΩ)
The total motor capacity, being unknown, is assumed The total motor capacity, being unknown, is assumed
equal to the transformer capacity, with: equal to the transformer capacity, with:
%ZM = 25(%) XM/RM = 6 %ZM = 25(%) XM/RM = 6 ZM = 4.11 + j24.66
Motor impedance From Eq. 14, at reference capacity, 1000kVA: ZM = 4.11 + j24.66 (%)
ZM 1000 x 103 From Eq. 9, after percentage to ohmic conversion:
ZM = (4.11 + j24.66) x 4402
1500 x 103 x 0.8 ZM = x (4.11 + j24.66) x 10–2 (Ω)
= 3.42 + j20.55 (%) 1500 x 103 x 0.8
= 6.6294 + j39.7847 (mΩ)
(ZL + ZT)ZM (ZL + ZT)ZM
ZS = ZS =
Total power supply ZL + ZT + ZM ZL + ZT + ZM
impedance = 0.671 + j3.142 (%) = 1.299 + j6.083 (mΩ)
ZS (R and X are calculated, per §9.3.2.) (R and X are calculated, per §9.3.2.)
Multiplying the value from Table 9.2 by a wire length Multiplying the value from Table 9.2 by a wire length
of 10M, and converting to the 1000kVA reference, of 10M.
from Eq. 12: ZW = (0.0601 + j0.079) x 10
Line impedance 3
ZW ZW = 1000 x210 (0.0601 + j0.079) x 10–3 x 10 x 100 = 0.601 + j0.79 (mΩ)
440
= 0.310 + j0.408 (%)
Total impedance Z = ZS + ZW Z = ZS + ZW
Z = 0.981 + j3.550 = 3.683 (%) = 1.900 + j6.873 = 7.1307 (mΩ)
74