[VH/VT] = 10.36
Turbulence and short circuit factor [F] = 1.53 Figure - Recommended value of F for various values of [VH/VT]
Length of oil water separator [L1] = 17.86 m
Length of oil water separator [L2] = 18.13 m Minimum [L/W] = 5
Length of oil water separator [L] = 18.13 m Higher value of L is selected
E. Conclusion
Dimension of conventational gravity oil water separator
Proposed depth of oil water separator [H] = 1.15 m
Proposed width of oil water separator [W] = 3.65 m
Proposed lenght of oil water separator [L] = 18.20 m
3 OF 3
3 OF 3
Project Tag No : D-420
Client Puma Energy Type : Conventational gravity separator
Service Oil water separator Case : Maximum design flow rate
Refer to API section 421
A. Determine the water flow rate
Design maximum daily rainfall rate = 0.315 m/day
[VH/VT] = 10.36
Turbulence and short circuit factor [F] = 1.53 Figure - Recommended value of F for various values of [VH/VT]
Length of oil water separator [L1] = 15.02 m
Length of oil water separator [L2] = 10.16 m Minimum [L/W] = 5
Length of oil water separator [L] = 10.16 m Higher value of L is selected
E. Conclusion
Dimension of conventational gravity oil water separator
Proposed depth of oil water separator [H] = 1.00 m
Proposed width of oil water separator [W] = 2.00 m
Proposed lenght of oil water separator [L] = 10.00 m
3 OF 3
3 OF 3
REFER TO FIGURE 4. API 421
VH/VT F
4 1.325 1.8
6 1.4
8 1.45 f(x) = 0.0308140244x + 1.2073506098
R² = 0.9949439158 1
10 1.52 1.7
12 1.575 1.675
14 1.625 1.625
15 1.675 1.6
16 1.72 1.575
F
18 1.75
1.52
1.5
1.45
1.4 1.4
1.325
1.3
1.2
3 4 5 6 7 8 9 10 11 12 13 14 15 16
[VH/VT]
2073506098 1.75
1.72
1.675
1.625
1.575
F
1.52 Linear
(F)
10 11 12 13 14 15 16 17 18 19
[VH/VT]