Professional Documents
Culture Documents
Supply Voltage
There are typically two supply voltage options when it comes to temperature
controllers: low voltage (24VAC/DC) and high voltage (110-230VAC).
Size
Controllers come in several standard sizes that are referred to by DIN numbers
such as 1/4 DIN, 1/8 DIN, 1/16 DIN and 1/32 DIN. DIN is an acronym for the
roughly translated "Deutsche Institut fur Normung," a German standards and
measurements organization. For our purposes, DIN simply indicates that a device
complies with a generally accepted standard for panel dimensions.
The smallest size is the 1/32 DIN, which is 24mm × 48mm, with a corresponding
panel cutout of 22.5mm × 45mm. The next size up is the 1/16 DIN which measures
48mm × 48mm with a panel cutout size of 45mm × 45mm. The 1/8 DIN is 48mm
× 96mm with a 45mm × 92mm panel cutout. Lastly, the largest size is the 1/4 DIN
measuring 96mm × 96mm with a 92mm × 92mm panel cutout.
It is important to note that the DIN standards do not determine how deep a
controller may be behind a panel. The standards only allow for front panel
dimensions and panel cut-out dimensions.
Agency Approvals
A third type of approval is FM. This applies only to limit devices and for
controllers in the U.S. and Canada.
All controllers have several common parts. For starters, controllers have inputs.
The inputs are used to measure a variable in the process being controlled. In the
case of a temperature controller, the measured variable is temperature.
Inputs
Temperature controllers can have several types of inputs. The type of input sensor
and signal needed may vary depending on the type of controlled process. Typical
input sensors include thermocouples and resistive thermal devices (RTD's), and
linear inputs such as mV and mA. Typical standardized thermocouple types
include J, K, T, R, S, B and L types among others.
Outputs
In addition to inputs, every controller also has an output. Each output can be used
to do several things including control a process (such as turning on a heating or
cooling source), initiate an alarm, or to retransmit the process value to a
programmable logic controller (PLC) or recorder.
Typical outputs provided with temperature controllers include relay outputs, solid
state relay (SSR) drivers, triac, and linear analog outputs. A relay output is usually
a single-pole double-throw (SPDT) relay with a DC voltage coil. The controller
energizes the relay coil, providing isolation for the contacts. This lets the contacts
control an external voltage source to power the coil of a much larger heating
contactor. It's important to note that the current rating of the relay contacts is
usually less than 2A. The contacts can control a heating contactor with a rating of
10–20A used by the heater bands or heating elements.
Another type of output is an SSR driver. SSR driver outputs are logic outputs that
turn a solid-state relay on or off. Most solid-state relays require 3 to 32VDC to turn
on. A typical SSR driver turn-on signal of 10V can drive three solid-state relays.
A triac provides the relay function without any moving parts. It is a solid state
device that controls currents up to 1A. Triac outputs may allow some small amount
of bleed current, usually less than 50mA. This bleed current doesn't affect heating
contactor circuits, but it may be a problem if the output is used to connect to
another solid-state circuit such as a PLC input. If this is a concern, a standard relay
contact would be a better choice. It provides absolute zero current when the output
is de-energized and the contacts are open.
Analog outputs are provided on some controllers which put out a 0–10V signal or a
4–20mA signal. These signals are calibrated so that the signal changes as a
percentage of the output. For example, if a controller is sending a 0% signal, the
analog output will be 0V or 4mA. When the controller is sending a 50% signal, the
output will be 5V or 12mA. When the controller is sending a 100% signal, the
output will be 10V or 20mA.
Other Parameters
Another parameter is an alarm value. This is used to indicate when a process has
reached some given condition. There are several variations on types of alarms. For
instance, a high alarm may indicate that a temperature has gotten hotter than some
set value. Likewise, a low alarm indicates the temperature has dropped below some
set value.
For example, in a temperature control system, a high fixed alarm prevents a heat
source from damaging equipment by de-energizing the source if the temperature
exceeds some setpoint value. A low fixed alarm, on the other hand, may be set if a
low temperature could damage equipment by freezing.
The controller can also test for a broken output device, such as an open heating
element, by checking the amount of output signal and comparing it to the amount
of detected change in the input signal. For example, if the output signal is 100%
and the input sensor does not detect any change in temperature after a certain time
period, the controller will determine that the loop is broken. This feature is known
as Loop Alarm.
Another type of alarm is a deviation alarm. This is set at some plus-or-minus value
from the setpoint. The deviation alarm monitors the process setpoint. The operator
is notified when the process begins to vary some preprogrammed amount from the
setpoint. A variation on the deviation alarm is the band alarm. This alarm will
activate either within or outside a designated temperature band. Typically, the
alarm points are half above and half below the controller setpoint.
For example, if the setpoint is 150° and the deviation alarms are set at ±10°, the
alarms would be activated when the temperature reached 160° at the high end or
140° at the low end. If the setpoint is changed to 170°, the high alarm would
activate at 180° and the low alarm at 160°. Another common set of controller
parameters are PID parameters. PID, which stands for proportional, integral,
derivative, is an advanced control function that uses feedback from the controlled
process to determine how best to control that process.
How it Works
All controllers, from the basic to the most complex, work pretty much the same
way. Controllers control, or hold, some variable or parameter at a set value. There
are two variables required by the controller; actual input signal and desired setpoint
value. The input signal is also known as the process value. The input to the
controller is sampled many times per second, depending on the controller.
This input, or process, value is then compared with the setpoint value. If the actual
value doesn't match the setpoint, the controller generates an output signal change
based on the difference between the setpoint and the process value and whether or
not the process value is approaching the setpoint or deviating farther from the
setpoint. This output signal then initiates some type of response to correct the
actual value so that it matches the setpoint. Usually, the control algorithm updates
the output power value which is then applied to the output.
The control action taken depends on the type of controller. For instance, if the
controller is an ON/OFF control, the controller decides if the output needs to be
turned on, turned off, or left in its present state.
A time proportioned system uses a cycle time to proportion the output value. If the
cycle time is set to 8 seconds, a system calling for 50% power will have the output
on for 4 seconds and off for 4 seconds. As long as the power value doesn't change,
the time values wouldn't change. Over time, the power is averaged to the 50%
commanded value, half on and half off. If the output power needed to be 25%, then
for the same 8 second cycle time, the output would be on for 2 seconds and off for
6 seconds.
All things being equal, a shorter cycle time is desirable because the controller can
more quickly react and change the state of the output for given changes on the
process. Due to the mechanics of a relay, a shorter cycle time can shorten the life
of a relay, and is not recommend to be less than 8 seconds. For solid state
switching devices like an SSR driver or triac, faster switching times are better.
Longer switching times, no matter what output type, allow for more oscillation in
the process value. The general rule is that, ONLY if the process will allow it, when
a relay output is used, a longer cycle time is desired.
Additional Features
Controllers can also have a number of additional optional features. One of these is
communication capability. A communication link lets the controller communicate
with a PLC or a computer. This allows data exchange between the controller and
the host. An example of typical data exchange would be the host computer or PLC
reading the process value.
A second option is a remote setpoint. This feature allows a remote device, such as
a PLC or computer, to change the controller setpoint. However, unlike the
communication capability mentioned above, the remote setpoint input uses a linear
analog input signal that is proportional to the setpoint value. This gives an operator
added flexibility by being able to change the setpoint from a remote location. A
typical signal might be 4–20mA or 0–10VDC.
Another common feature supplied with controllers is the ability to configure them
using special software on a PC connected via a communications link. This allows
quick and easy configuration of the controller and also the option to save
configurations for future use.
Another common feature is a digital input. The digital input can work together
with a remote setpoint to select the local or remote setpoint for the controller. It
can also be used to select between setpoint 1 and setpoint 2 as programmed in the
controller. Digital inputs can also remotely reset a limit device if it has gone into
the limit condition.
Profile
Multi-Loop
Besides single-loop controllers which can control only one process loop, multi-
loop controllers can control more than one loop, meaning they can accept more
than one input variable.
Multi-loop controllers provide a compact modular system that can operate either
within a stand-alone system or in a PLC environment. As a replacement for
temperature controls in PLCs, they provide fast PID control and off-load much of
the math intensive work from the PLC processor, allowing for faster PLC scan
rates. As a replacement for multiple DIN controllers, they provide a single point of
software access to all control loops. The cost of installation is reduced by
eliminating much wiring, panel cutouts, and saving panel space.
Let’s use the example of an automated production facility that makes cookies.
Process controllers are responsible for delivering a specific ratio of ingredients,
mixed them together for an exact amount of time before being portioned into a
consistent size and shape. A conveyor transports the raw cookies to the oven where
they are baked to a perfect consistency and counted out for packaging.
Years ago, workers would’ve handled all these processes manually-- checking
temperatures, mixing ingredients, timing the baking. The process was much
slower, less cost effective, and output was lower because of that. Now production
is highly automated. It is process controllers that are responsible for the increase in
efficiency.
Process controllers are arranged into control systems (also known as control loops)
that consist of the controller, any associated sensors, a power supply, the final
control element, as well as any necessary load handling devices.
As we know, controllers seek to maintain the measured process variable at a preset
point.
Sensors provide the input signal to the controller. That signal is based upon a
measurable physical property like temperature, pressure, pH, flow, level, etc. There
are a staggering array of sensors, transmitters, and transducers compatible with
process controllers. Nearly the only limitation is the type of signal a controller is
capable of reading. More sophisticated controllers accept voltage, current, contacts,
frequency, thermocouple/RTD, and other signal types.
The final control element refers to the device that acts upon orders from the
controller. It can be a heater that is activated when the sensor finds a temperature
lower than the set point or a valve that opens when the pressure sensor measures a
pressure higher than the set point.
Process controllers, many (though not all) sensors, and final control elements
require power to operate. A power supply is an integral element to control loops
Load handling devices are often needed when the final control element, such as
heaters or solenoids, require more power to operate than can be supplied by the
controller.
Depending upon the unit, process controllers are capable of providing multiple
types of control which are suited to different applications and process variables.
On-Off Control
On-off control, also called hysteresis control, is the simplest type of control. As
expected, on-off controllers switch abruptly between two states with no middle
state. They are for use with equipment that accepts binary input, for example a
furnace that is either completely on or completely off.
On-off controllers only switch output when the set point has been crossed. In the
case of heating control, the controller switches on when below the set point and off
when above the set point. To prevent rapid cycling of the system which can cause
damage, hysteresis or on-off differential, is added to the controller operations. The
differential prevents cycling by exceeding the setpoint by a small amount before
the controller switches on or off.
On-off controllers are often used in applications that don’t require precise control,
in systems which cannot handle having the energy turned on and off frequently,
where the mass of the system is so great that temperatures change extremely
slowly, or for temperature alarms.
PID Control
PID control uses three different control terms; proportional (P), integral (I), and
derivative (D) to help the controller’s algorithms provide a more accurate response
to deviations from the set point.
When a controller receives input that a process variable has varied from the set
point, instructions are sent to the final control element for correction. For example,
a controller receives a signal from a thermocouple that a process temperature is too
low prompting the controller to turn on a heater to bring it back up to temperature.
Simple on-off control often leads the final control element to overshoot the set
point, especially when the original deviation was small. Repeatedly overshooting
the set point causes the output to oscillate around the setpoint in either a constant,
growing, or decaying sinusoid. The system is unstable if the amplitude of the
oscillations continuously increase with time.
PID controllers use the algorithm derived from their three control terms to
maintain system stability by limiting overshoot and resulting oscillation. The
proportional variable controls the rate of correction so that it is proportional to the
error. The integral and derivative variables are time-based and help the controller
automatically compensate to changes in the system. The derivative variable
considers the rate at which the error is increasing or decreasing while the integral
variable uses knowledge of accumulated errors to the length of time the process is
not at the set point. This information is used to correct the proportional value.
PID controllers are generally considered the most efficient type of controller. They
are widely used in industrial settings. Though each of the variables must be tuned
to a particular system, PID controllers provide very accurate and stable control.
In order to make PID controllers even more responsive to real-world situations,
many manufacturers have incorporated fuzzy logic (or fuzzy control) into the
instruments. Fuzzy logic is a mathematical system that attempts to emulate human
reasoning. Rather than the binary logic of standard controllers, fuzzy logic
introduces continuous variables which provide an effective means of capturing the
approximate, inexact nature of the real world.
This ability enables controllers with fuzzy logic to make quick, subtle changes that
significantly improves response to fast-changing variables independent of the
programming done by the operator. For example, as heaters, valves and other final
control elements age, they show signs of wear and no longer respond in the same
way as they did when new. Fuzzy logic recognizes this and automatically
compensates.
Profile Control
Profile control is especially useful for cycling applications which require multiple
temperature profiles as well as specific on and off periods.
Limit Control
Limit control involves an independent switch which will shut down the system if a
process variable crosses a preset threshold. Limit controllers are for use in
processes where for safety or quality issues, a process variable must be kept within
specified tolerance levels.
Tuning
Tuning Fuji Temperature Controllers, as with any PID loop, requires tuning each
parameter separately and in sequence. To achieve good PID temperature control
manually, you can use the trial and error method explained below.
Start with a large Proportional Band value which gives very sluggish control with
noticeable offset and tighten by decreasing the value in half. Analyze the process
variable. If the control is still sluggish, tight-en by decreasing the value in half
again. Continue with the same procedure until the process starts to oscillate at a
constant rate. Widen the Proportional Band by 50%, or multiply the setting 1.5
times. From a cold start, test and verify that the Proportional Band allows
maximum rise to setpoint while maintaining minimum overshoot and offset. If not
completely satisfied, fine-tune the value, up or down, as needed and test until
correct. The Proportional Band is now tuned.
Start with a large Integral Time value which gives very sluggish response to
process offset and tighten by decreasing the value in half. Analyze the process
variable. If the response to process offset is still sluggish, tighten by decreasing the
value in half again. Continue with the same procedure until the process starts to
oscillate at a constant rate. Increase the Integral Time value by 50%, or multiply
the setting 1.5 times. From a cold start, test and verify that the Integral Time allows
maximum elimination of offset with minimum overshoot. If not completely
satisfied, fine-tune the value, up or down, as needed and test until correct. The
Integral Time is now tuned.
Do not add Derivative Time if the system is too dynamic. Start with a small
Derivative Time value which gives sluggish response to process upsets and double
the value. Analyze the process variable. If the response to process upsets is still
sluggish, double the value again. Continue with the same procedure until the
process starts to oscillate at a quick constant rate. Decrease the Derivative Time
value by 25%. From a cold start, test and verify that the Derivative Time value
allows maximum response to process disturbances with minimum overshoot. If not
completely satisfied, fine-tune the value, up or down, as needed and test until
correct. Note that the Derivative Time value is usually somewhere around 25% of
the Integral Time value.
1. Integral Time=0
Derivative Time=0
2. Decrease the Proportional Band to the point where a constant rate of
oscillation is obtained. This is the response frequency of the system. The
frequency is different for each process.
3. Measure the Time Constant which is the time to complete one cycle of the
response frequency. The Time Constant will be defined as "T" when
calculating Integral and Derivative Times.
4. Widen the Proportional Band until only slightly unstable. This is the
Proportional Band's Ultimate Sensitivity. The Proportional Band's Ultimate
Sensitivity width will be defined as "P" when calculating the actual
Proportional Band.
5. Use the following coefficients in determining the correct PID settings for
your particular application.
P Only 2P * *
PI 2.2P .83T *
Types of devices that use signal conditioning include signal filters, instrument
amplifiers, sample-and-hold amplifiers, isolation amplifiers, signal isolators,
multiplexers, bridge conditioners, analog-to-digital converters, digital-to-analog
converters, frequency converters or translators, voltage converters or inverters,
frequency-to-voltage converters, voltage-to-frequency converters, current-to-
voltage converters, current loop converters, and charge converters.
Signal conditioners are equipped with a range of functions that prepare signals
from sensors and transmitters for the next stage of the process. The functions you
should look for are determined by the needs of your application and equipment.
Adjustability
Though sensor outputs are nearly always shown with convenient endpoint signals
(e.g., 0.00 mV through 50.0mV), in the real world sensors provide approximate
values such as 4.73mV through 48.9mV. Adjustable signal conditioners can scale
the output signal to more convenient endpoints as well as optimize performance by
calibrating out errors due to the sensors and/or the system such as voltage drops,
other devices, etc.
As sensors age they are also prone to drifting. The ability to adjust zero and span
through the signal conditioner increases the useful life of sensors without affecting
other devices, burdening host processors, or affecting system accuracy.
Amplification
Output signals often need amplification especially when used with long cable runs.
Signal conditioners amplify output signals by increasing the voltage, thus
increasing the measurement resolution and sensitivity. When amplification of the
signal is paramount, placing the signal conditioner closer to the signal source, or
transducer, improves the measurement signal-to-noise ratio by magnifying the
voltage level before it is affected by environmental noise.
Attenuation
Isolation
Filtering
RFI/EMI
Excitation
Many sensors and transmitters require external voltage or current excitation. For
example, strain gages, accelerometers, thermistors, and resistance temperature
detectors use some variation of an introduced electrical signal upon which to base
measurement. RTD and thermistor measurements measure and convert the
variation in resistance of a current source to a measurable voltage. Accelerometers
often have an integrated amplifier, which requires a current excitation provided by
the measurement device. Strain gages typically are used in a Wheatstone bridge
configuration with a voltage excitation source.
Linearization
Some sensors, notably thermocouples, produce output signals that are not linearly
related to the physical measurement. Linearization is the process of interpreting the
signal from the sensor such that it aligns with the physical measurement.
Cold-Junction Compensation
Bridge Completion
When discussing temperature calibration it's important to note that output of the
temperature sensors, themselves, cannot be adjusted. Instead, the controller or
readout is adjusted to account for the inaccuracy of the sensor.
ITS-90
Calibration
Calibration is a comparison between two devices. The first device is the unit to be
calibrated, often called the unit under test. The second device is the standard,
which has a known accuracy. Using the standard as a guide, the unit under test is
adjusted until both units display the same results while exposed to the same
temperature. Typically, calibration of an instrument is checked at several points
throughout the calibration range of the instrument.
Not all standards are created equally. While all standards have a known accuracy,
there are some—known as primary standards— that are the highest level of
accuracy for a specific parameter. Primary standards achieve their high accuracy
by relying upon measurement technologies using fundamental physical constants
that do not drift such as the triple point of water. These fixed values minimize
uncertainty, making primary standards the most accurate calibration tools.
Traceability
There are three specifications that are of extreme importance when selecting a
temperature calibrator. Understanding these specifications and their implications
will go a long ways towards helping you select the best calibrator for your needs.
Accuracy: An expression of how closely a measured value agrees with the true or
expected value of the quantity of interest (NCSL glossary). For temperature
calibrators, accuracy is the relationship between the instrument's display
temperature and the actual temperature of calibration well. Accuracy is improved
by regular calibrations to a traceable standard.
Uniformity: Temperature homogeneity of the heat source throughout the test zone.
All calibrators have slight temperature differences from the bottom of the of the
test well to the top as well as from the middle of the test well outward. A few
simple strategies allow users to place probes in such a way as to minimize
uniformity errors.
Dry Blocks
Dry blocks are versatile temperature calibrators that work by heating, and in many
cases cooling, a metal block to a specific temperature and maintaining that
temperature. Most dry blocks utilize one or more interchangeable inserts into
which holes are drilled. These holes accommodate a range of temperature sensors
to be calibrated. The size of the holes correspond to the diameter of the
temperature sensors under test.
Good heat transfer between insert and sensor is critical for accurate calibrations
when using a dry block temperature calibrator. This transfer depends on a very
close fit between the sensor and the insert. Ideally, there should be no more than a
couple of thousandths clearance between the two. Selecting the proper insert to
match your sensor is critical.
Liquid Baths
Liquid baths are a temperature measurement and calibration tool in which a liquid,
or in some cases a material that acts as a liquid, is heated or cooled to a specific
temperature and maintained. In many ways, liquids baths are similar to dry block
calibrators except that they utilize a liquid as the calibration medium, rather than a
metallic insert, which permits easier calibration of oddly shaped or sized probes.
Since liquid baths do not rely on drilled inserts, they are also capable of calibrating
many more inserts at a time. Because the liquid is being stirred, these baths do not
suffer from vertical temperature differences experienced in dry blocks and by
consequence usually will provide much better overall uncertainty.
Depending upon the model, liquid baths using an oil medium can achieve
temperatures from about –30°C to 200°C. Specialized baths using sand, salt, or
aluminum oxide particles instead of oil can reach temperatures up to 700°C. These
"fluidized" baths act as high temperature liquid baths.
Liquid baths offer greater precision and larger calibration volumes than dry block
calibrators. They also offer excellent stability over the entire temperature range.
Accuracy with liquid baths can be as high as ≤0.2°C, better than that which can be
achieved by most dry blocks. Liquid baths offer secondary-level calibrations on
nearly any type of temperature sensor, including: RTDs, thermocouples,
thermistors, , PRTs, bi-metal thermometers, etc.
Blackbody Sources
Emissivity is the relative power of a surface to emit heat by radiation. The lower
the emissivity the more heat radiates from the surface. Higher emissivity,
"blackbodies", radiate little heat and are, therefore, not prone to errors due to
interference from radiation upon the infrared sensor. For best results, the emissivity
of the infrared sensor under test should match the emissivity of the blackbody
source.
Once emissivity issues are accounted for, calibrating infrared thermometers using a
blackbody source are straightforward. The infrared thermometer takes a
measurement of the target plate. The temperature of the plate is compared with the
reading. The infrared thermometer is then adjusted until the results match.
Depending upon the model, blackbody sources have temperature ranges from
about -30° to 500°C with an accuracy of ±0.5°C making them excellent tools for
field- or industrial-level calibrations. Some models incorporate fixed-point cells
making them suitable as primary standards.
Multifunction
Fixed point cells are primary standards and offer the greatest accuracy and stability
of any temperature calibration method. Fixed cells work by heating or cooling a
highly pure substance to the temperature at which a phase change occurs. Phase
changes are the transitions between solid, liquid and gaseous states of matter.
These transitions occur at very specific temperatures and, at the point of phase
change, temperatures become very stable, often plateauing for several hours or
even days providing a highly accurate and stable reference temperature.
Fixed point cells are usually incorporated into dry blocks or liquid baths to provide
the necessary heating/cooling and temperature control. Fixed point cells can
achieve an uncertainly of just ±0.001°C.
The most accurate of fixed point cells are triple point cells. Triple point cells are
based on the principle that certain substances in a highly pure (99.9999%) state
have a triple point, or a temperature at which all three phases (gas, liquid, and
solid) of that substance coexist in thermodynamic equilibrium. The most common
of these is water which has a triple point of 0.01°C. Triple point cells have an
uncertainty better than ±0.0001°C, so accurate that ITS–90 uses triple point cells of
hydrogen, neon, oxygen, argon, mercury, and water for delineating six of its
defined temperature points.
Thermocouples and RTDs are temperature sensing devices that play and extremely
important role in a wide range of measurement and control applications. Though
both thermocouples and RTDs share many similarities including a wide measuring
range; good accuracy; and simple, reliable design, they are very different devices
that rely on very different technologies . RTDs and/or thermocouples are found in
cars, homes, offices, commercial spaces, and industrial settings—anywhere
accurate, affordable temperature readings are required.
Thermocouples
Creating a junction of any two dissimilar metals will produce an electric potential
related to temperature. Thermocouples, designed for accurate temperature
measurement in a variety of environments, use junctions of specific metals and
alloys which have a highly predictable and repeatable relationship between voltage
and temperature. Different combinations of metals and alloys are used for different
temperature ranges.
The junction created by joining together the two dissimilar metals is known as the
measurement or thermocouple junction. This is the “hot” end of the thermocouple.
The other end, where the thermocouple ties into the system (often a controller or
display) is called the reference or cold junction. A thermocouple generates a
voltage proportional to the temperature difference between the measurement
junction and the reference junction. This is a relative temperature measurement. In
order get more useful absolute temperature readings, there need to be a stable
reference temperature. This is accomplished through cold junction compensation.
Depending upon the measurement and control system, cold junction compensation
can be accomplished in a number of ways. In highly sophisticated calibration
systems, the cold reference is maintained at a controlled temperature, often 0˚C.
Though useful in a laboratory, controlling the temperature of the reference junction
isn’t practical for most applications. There are also other ways to compensate. One
is to add a small temperature sensor to monitor the cold junction temperature. A
second is to have a diode simulate a specific temperature within the cold junction.
The electronics to which the thermocouple is attached can quickly apply
corrections based upon the cold junction compensation and provide an accurate
absolute temperature.
Most thermocouples include sheathing for protection from their environment.
Thermocouples that are sheathed have options grounding their measurement
junctions. A grounded junction, the most common type, physically connects the
thermocouple wires to the metal sheathing. This configuration provides a faster
response time as it improves heat transfer from the outside. Grounded junctions are
more prone to electrical interference, however, which can cause measurement
errors.
Thermocouple Types
Although thermocouples can be made from joining together any two different
metals, science and experience have established that certain combinations of
metals produce reliable temperature measurements suitable to particular
environments. These combinations of metal are referred to as thermocouple types.
Type J Thermocouple: Type J thermocouples are the most common of all types.
They include an Iron leg and a Constantan leg. They are suitable for temperatures
from -346 to 1,400˚F (-210 to 760˚C) and have a basic accuracy of ±2.2˚C or
±0.75%. Type J thermocouples can be used in vacuum, reducing, oxidizing and
inert atmospheres.
Advantages:
Low cost
High temperature range
Very simple design
Rugged
Fast response
Temperature sensing is at the tip of a thermocouple
Disadvantages:
Low sensitivity
Moderate accuracy
Non-linear
Low voltage
Low stability/repeatability
RTD elements are available in different styles but all consist of a highly pure
conductive metal such as platinum, copper, aluminum, or nickel; inside of a
sheathed probe for protection. These materials, are used for their highly predictable
resistance versus temperature relationship and operating temperature range.
Platinum is the preferred material for RTD elements. As a noble metal, platinum
doesn’t react with other materials making it highly stable with a very linear and
repeatable resistance-temperature relationship over an effective temperature range
of -272.5 to 961.78°C. Platinum RTDs, which are often called PRTs (Platinum
Resistance Thermometers) , are accurate enough to serve as the sensors that
define the International Temperature Standard, ITS-90. RTDs of the highest
accuracy are called SPRTs (Standard Platinum Resistance Thermometers)
which can achieve an accuracy of up to ±0.001°C.
RTD elements are classified according to their resistance in ohms at 0°C. For
example, the most common classification, Pt100, demonstrates 100Ω of resistance
at 0°C. The resistance to temperature coefficient depends on the classification of
the RTD element with Pt100 sensors at 0.385 Ohm/°C and Pt1000 sensors at 3.85
Ohm/°C. Pt1000 sensors, therefore makes possible a higher resolution n while
Pt100 sensors provide a wider temperature range.
RTDs also differ in their wiring configurations. A simple rule of thumb is that the
more wires an RTD has the more accurate it is. Since the lead wires, usually
copper, have their own resistance value different from that of the platinum
element, they can impact the accuracy of the RTD. Two-wire RTDs do not have a
practical means for accounting for the resistance associated with the copper lead
wires and are therefore the least accurate configuration. Three-wire RTDs, the
most common configuration, use a Wheatstone bridge to compensate for the lead
wire resistance. Four-wire RTDs are the most accurate because they are able to
completely compensate for the resistance of the wires without having to pay
attention to the physical properties of them.
RTD Styles
Thin Film: Thin film elements consist of a ceramic substrate to which a very thin
(1 to 10 nanometers) layer of resistive material, normally platinum, has been
deposited. A layer of epoxy or glass provides a protective coating over the
platinum. Thin film elements provide a faster response than other construction
styles though at a cost of lower stability. The size and shape of the element makes
it easy to mount on flat surfaces, especially in tight spaces.
Coil Element: Coiled elements utilize a wire coil held in place by a mechanical
support. This produces a strain-free design which allows the coil to expand and
contract freely as the temperature changes without any influence from other
materials. It is the most accurate and stable of RTD styles and has largely
supplanted wire wound elements. Coil elements are suitable for temperatures up to
850°C.
Good stability
Excellent accuracy
Contaminant resistant
Good linearity
Highly repeatable
Area temperature sensing
Disadvantages:
Higher cost
Current source required
Slow response time
Lower temperature range
Self-heating
Medium sensitivity to small temperature changes
Principle of Measurement
Conductivity, resistivity, salinity, and TDS meters all measure the specific
conductance of a water sample in order to determine or calculate a value. The
process by which those instruments measure specific conductance consists of
measuring the AC resistance of the solution between two electrodes. Conductivity,
the inverse of resistivity is determined from the voltage and current values
according to Ohm’s law.
Since we know that conductance is dependent upon ions dissolved in the water, the
conductivity of a water sample is proportional to its ion concentration, though ionic
interactions can alter the linear relationship between conductivity and
concentration in some highly concentrated solutions.
Conductivity meters generally use a 2-cell electrode configured into either a dip or
flow-through style. The electrode surface is usually platinum, titanium, gold-plated
nickel, or graphite. A 4-cell electrode can be used for applications requiring higher
accuracy. These electrodes use a reference voltage to compensate for any
polarization or fouling of the electrode plates. The reference voltage ensures that
measurements indicate actual conductivity independent of electrode condition,
resulting in higher accuracy for measuring pure water.
Temperature Compensation
Cell Constant
When measuring solutions with lower conductivity, the electrodes can be placed
closer together or made smaller resulting in a cell constant of less than one which
will yield a better signal. Higher conductivity solutions require higher cell
constants to produce a value more easily interpreted by the meter.
Cell constants increase the efficiency of the sensor. It’s a factor that the meter uses
to make the standard value agree with the measured value. Conductivity sensors
each have a nominal values such as k=1.0. This value may vary somewhat as
oxidization, scratches, coating, bending, etc. affect the sensor. Only with
calibration is the true value of the cell constant known.
It’s important to choose a cell constant based on the anticipated measuring range:
Calibration
Conductivity meters and cells should be calibrated to a standard solution before
using. When selecting a standard, choose one that has the approximate
conductivity of the solution to be measured.
Conductivity
Resistivity
Salinity
Salinity refers to the total concentration of all dissolved salts in water. Since salts
form ionic particles when dissolved, salinity is a strong component of conductivity.
Though salinity can be measured via a complete chemical analysis, this method is
difficult and time consuming. More often, salinity is estimated using algorithms
based upon conductivity, which is much easier to measure. Salinity values can be
expressed as parts per thousand (ppt) or as practical salinity units (psu) which
compares the sample to a salinity standard such as seawater.
Total dissolved solids (TDS) is the measure of all dissolved particles smaller than 2
microns in a water sample. This includes all inorganic and organic substances in
molecular, ionized or micro-granular suspended form. In clean water samples, TDS
is approximately equal to salinity while in polluted waters , TDS includes organic
solutes as well.
The primary sources of dissolved solids are agricultural and residential runoff,
leaching of soil contamination, industrial discharge, and discharge from sewage
treatment plants. While TDS is not necessarily a “pollutant”, it is used as a general
indication of water quality. High TDS levels indicate hard water which can cause
scale buildup in pipes, valves, and filters, reducing performance and adding to
system maintenance costs.
TDS can be determined in a couple of ways though, most commonly, it is
calculated from conductivity readings as this is a simple, effective method of
testing. When calculating total dissolved solids from a conductivity measurement,
a TDS factor is used. The TDS factor is empirically determined by the nature of
the dissolved solids and the water source. TDS measurements, therefore, measure
conductivity and multiply the reading by the TDS factor. Values are usually
expressed as parts per million.
The basis of good flow meter selection is a clear understanding of the requirements
of the particular application. Therefore, time should be invested in fully evaluating
the nature of the process fluid and of the overall installation.
1. What is the fluid being measured by the flow meter(s) (air, water, etc…)?
2. Do you require rate measurement and/or totalization from the flow meter?
3. If the liquid is not water, what viscosity is the liquid?
4. Is the fluid clean?
5. Do you require a local display on the flow meter or do you need an
electronic signal output?
6. What is the minimum and maximum flow rate for the flow meter?
7. What is the minimum and maximum process pressure?
8. What is the minimum and maximum process temperature?
9. Is the fluid chemically compatible with the flow meter wetted parts?
10.If this is a process application, what is the size of the pipe?
Although many users—and even some manufacturers— use the terms sensors,
transmitters and transducers interchangeably, technically there are differences
between them.
Pressure transmitters are current output devices that, generally, have two or three
wires that are used to both power the device as well as transmit the output signal.
They are often scaled from 4-20 mA although other ranges are available.
Transmitters are ideal for longs runs as wiring is simpler and cheaper and there is
no significant degradation of the output signal with distance.
Pressure transducers are voltage output devices that, generally, have three or four
wires to power the device as well as transmit the output signal. Transducers are
better for short runs as electrical resistance can cause errors on longer runs. They
are also sensitive to electromagnetic interference.
Pressure sensor is a catch-all term that includes both pressure transmitters as well
as pressure transducers.
As pressure is defined as force over a unit area, there are a number of ways to
articulate pressure readings depending upon the unit of force and the unit of area.
Most commonly, we will see PSI ( pounds per square inch) or bar. Other units of
measure include kg/cm2, inH2O, mmHg, Pa, and many others.
There are also different types of pressure to consider. The type of pressure refers to
the zero reference point of a measurement. For example:
Though there are many sensing technologies available, most pressure sensors,
transmitters, and transducers use force collector type sensors. These electronic
sensors employ a force collector such as a diaphragm or piston to measure the
strain caused by force applied over an area. Simply put, pressure applies force to a
diaphragm or piston which causes the piston or diaphragm to move in relation to
the amount of pressure. Sensors detect that movement (the strain) and convert to a
unit of pressure.
Among force collector sensors, there are two types that we see most often:
Piezoresistive sensors are based upon the piezoresistive effect which describes
changes in the electrical resistivity of a semiconductor or metal —commonly
silicon, polysilicon thin film, bonded metal foil, thick film, or sputtered thin film—
when mechanical strain (pressure) is applied. Increasing pressure results in changes
in the resistivity of the strain gauges which is detected and converted into an
electrical signal proportional to pressure. Generally, the strain gauges are
connected to form a Wheatstone bridge circuit to maximize the output of the sensor
and to reduce sensitivity to errors.
Capacitive sensors generally feature two closely spaced, electrically-isolated
metallic surfaces one of which acts as a diaphragm by slightly flexing under
applied pressure. The flexing alters the gap between the plates creating, in effect, a
variable capacitor. The resulting changes in capacitance can be measured and
converted into an electrical signal proportional to pressure.